Structural form

The column that stops

A load path that runs straight to the ground costs almost nothing. Interrupting one costs depth in proportion to the square root of the load times the distance it is moved — and the interruption's own deflection becomes the settlement of everything standing on it.

Assumes Depth is the cheapest strength there is, One support too many, and what it costs to know and Stiffness is not strength, and usually it is the one that governs.

A column that runs from the roof to the foundation is nearly free. It is a stack of short compression members, each one sitting on the one below, and its cost per storey barely changes with how many storeys are above it — the load simply goes somewhere, straight down, by the shortest route there is.

Then the ground floor has to be a foyer, or a road passes underneath, or the car park below wants its columns on a 7.5 m grid where the flats above want them on 5.4 m. One column has to stop, and its load has to be carried sideways to a column that continues. The drawing of that is a beam, and the beam looks like any other beam on the sheet.

The depth is decided by how far it moves, not by what it can carryA column carrying 6000 kN landing 3 m into a 12 m transfer member. The free body is the member itself, cut under the column: M = P·a(L − a)/L = 13500 kNm, with 4500 kN of shear on one side of the cut and 1500 on the other. At an allowable stress that moment asks for 1.94 m of depth — the dashed outline — and keeping the settlement it causes inside the floors' own bending asks for 2.55 m, which is the member drawn solid. 31% more depth is bought by nothing the strength calculation can see. The depth grows as √(P·a), so four times the load is exactly twice the depth, and depth in a transfer member is a storey nobody occupies.P = 6000 kNfrom 10 storeys abovea = 3 mstrength wants 1.94 mstiffness wants 2.55 mslope 4500 kN1500 kN13500 kNm under the column12 m
Fig. 1 A column carrying 6000 kN landing 3 m into a 12 m transfer member. The free body is the member itself, cut under the column: M = P·a(L − a)/L = 13500 kNm, with 4500 kN of shear on one side of the cut and 1500 on the other. That moment asks for 1.94 m of depth at an allowable stress — the dashed outline — while holding the settlement it causes inside the floors’ own bending asks for 2.55 m, which is the member drawn solid.

It is not any other beam. Thirteen and a half thousand kilonewton-metres is delivered in one member, and the depth that answers for it is more than half a storey — depth that is lost on every floor the member passes through. The transferred load is paid for once; the transfer member’s depth is paid for by everybody who wanted to stand where it is.

What the cut under the column says

The number comes from one free body and one equation, and both are worth naming before anything is built on them.

Cut the transfer member vertically, immediately under the stopped column, and keep the left-hand piece. Acting on it are the left reaction P(La)/L=4500P(L-a)/L = 4500 kN upward, and, on the cut face, the shear and moment the right-hand piece was applying. Moments about the cut give

M=Pa(La)L=6000×3×912=13500 kNm,M = \frac{P\,a\,(L-a)}{L} = \frac{6000 \times 3 \times 9}{12} = 13\,500\ \text{kNm},

and vertical equilibrium gives the shear on that face directly: 4500 kN on the short side of the load, 1500 kN on the long side. Nothing in that is special to a transfer; it is the point-load moment every textbook carries. What is special is the size of PP, which is the accumulated weight of ten floors rather than a floor load, and the existence of aa, which is a decision somebody made in plan.

The depth that answers for the moment follows from the section rather than from the frame. For a rectangle of width bb at an allowable stress σ\sigma, M=σbd2/6M = \sigma b d^2/6, so

d=6Mσb=6Pa(La)σbL.d = \sqrt{\frac{6M}{\sigma b}} = \sqrt{\frac{6\,P\,a\,(L-a)}{\sigma\,b\,L}}.

Every term the design controls sits under the square root. Depth is the cheapest strength there is precisely because the moment goes as d2d^2, and here that generosity runs in reverse: the load has to quadruple before the depth doubles.

Four times the load is exactly twice the depth

Four times the load is exactly twice the depthDepth of a 0.6 m wide transfer beam against the load it moves 3 m across its 12 m span. Strength wants √(6M/σb) with M = P·a(L − a)/L, so the depth goes as √P and nothing else: 1.936 m at 6000 kN and 3.873 m at 24000 — a ratio of 2.000, which is 2 to three decimals and is a property of the square root rather than of this beam. The upper curve is the depth the settlement criterion asks for instead, and it is above the strength curve everywhere on this chart: deflection goes as 1/d³ where strength goes as 1/d², so the two converge as the load grows and the stiffness criterion governs every ordinary transfer. At 6000 kN it asks for 2.55 m against 1.94.050001000015000200002500030000012345load moved across the span (kN)depth the member needs (m)6000 kN · 1.94 m24000 kN · 3.87 msettlementstrengthfour times the load, twice the depth
Fig. 2 Depth of a 0.6 m wide transfer beam against the load it moves 3 m across a 12 m span. Strength wants √(6M/σb), so the depth goes as √P and nothing else: 1.936 m at 6000 kN and 3.873 m at 24000, a ratio of 2.000. The upper curve is the depth the settlement criterion asks for instead, and it is above the strength curve everywhere on the chart.

The ratio printed on that chart is 2.000 to three decimal places, and it is not a rule of thumb that happens to work near the middle of the range. It is the square root, arriving as arithmetic. Quadruple the load on a transfer member and its depth exactly doubles; double the load and the depth grows by 41 per cent.

The other term is the one worth carrying into a plan meeting, and it is not linear in aa. Moving the stopped column from 3 m into the span to 1.5 m cuts the moment from 13 500 to 7875 kNm, a 42 per cent saving; moving it from 3 m to 6 m raises it to 18 000 kNm, a 33 per cent penalty. The depth follows at half the rate in each direction. The transfer is cheapest when the column that stops lands nearly on top of a column that continues, which is a statement about the plan rather than about the beam, and is the only part of this whole subject that costs nothing to act on.

The depth is decided by how far it moves, not by what it can carryA column carrying 20000 kN landing 5 m into a 14 m transfer member. The free body is the member itself, cut under the column: M = P·a(L − a)/L = 64286 kNm, with 12857 kN of shear on one side of the cut and 7143 on the other. At an allowable stress that moment asks for 4.23 m of depth — the dashed outline — and keeping the settlement it causes inside the floors' own bending asks for 5.28 m, which is the member drawn solid. 25% more depth is bought by nothing the strength calculation can see. The depth grows as √(P·a), so four times the load is exactly twice the depth, and depth in a transfer member is a storey nobody occupies.P = 20000 kNfrom 10 storeys abovea = 5 mstrength wants 4.23 mstiffness wants 5.28 mslope 12857 kN7143 kN64286 kNm under the column14 m
Fig. 3 The same law at a size that puts a tower on a podium: 20000 kN moved 5 m across a 14 m member. The cut under the column gives M = 64286 kNm, with 12857 kN of shear on one side and 7143 on the other. Strength asks for 4.23 m and stiffness for 5.28 m — a member two storeys deep, sized by a criterion that has nothing to do with its strength.

Stiffness governs, and the deflection belongs to somebody else

The dashed outline in the first figure is 1.94 m and the solid member is 2.55 m, thirty-one per cent deeper. The extra depth is bought by nothing the strength calculation can see, and the reason is a change of free body.

A beam’s deflection is normally the beam’s own problem. It is checked against a span fraction, it is a serviceability matter rather than a strength one, and the consequence of getting it slightly wrong is a door that binds. A transfer member’s deflection is not its own problem, because a column is standing on it. Whatever the transfer member does at that point, the column above does too, and so does every floor connected to that column. The deflection of the beam is the settlement of a support, ten times over.

The number is 57.6 mm in the long term, for the beam sized by its moment: 23.4 mm when the load first arrives and three times that when creep has finished with it, because concrete at ten thousand days has deflected roughly 1+φ1+\varphi times what it did on the day. Span over 208 — a deflection ratio no beam in the building would fail on, and a settlement no floor above it can absorb.

Three ways to move the same column

The bending stiffness of a rectangle goes as d3d^3, so buying stiffness with depth is even more efficient than buying strength with it, and every way of making a transfer is a way of getting depth.

Three ways to move the same column, and they are not closeThe same 6000 kN moved 3 m across 12 m, built three ways and drawn to one scale. The deep beam is 1.94 m of concrete, 35.0 tonnes, and settles 57.6 mm in the long term. The storey-deep truss takes the same moment as a couple at 3.6 m centres, so its chords carry M/h and it weighs 7.1 tonnes — a fifth of the beam — while settling 16.0 mm, and it does not creep. The wall is 62.7 tonnes and hardly moves at all, 4.34 mm, of which 41% is shear rather than bending — which is what a member as deep as it is long always does, and is why beam theory does not describe one. A wall as a deep beam is the stiffest of the three by a factor of 13.3.a deep beam1.94 m deep35.0 t of material57.62 mm of settlement5% of it sheara storey-deep truss3.60 m deep7.1 t of material15.97 mm of settlementno creep, and no concretea wall as a deep beam7.20 m deep62.7 t of material4.34 mm of settlement41% of it shear
Fig. 4 The same 6000 kN moved 3 m across 12 m, built three ways and drawn to one scale. The deep beam is 1.94 m of concrete, 35.0 tonnes, and settles 57.62 mm in the long term. The storey-deep truss takes the same moment as a couple at 3.6 m centres and weighs 7.1 tonnes — a fifth of the beam — while settling 15.97 mm and not creeping at all. The wall is 62.7 tonnes and hardly moves: 4.34 mm, of which 41% is shear rather than bending.

The truss is the striking column of that table. It carries the identical moment with one fifth of the material, and it does so by the oldest trick in the collection: resolving a moment into a pair of forces and then pushing them as far apart as the storey allows. At 3.6 m centres the chords carry 3750 kN each, against a lever arm the deep beam could only reach by being 3.6 m deep itself.

Chord force against truss depthThe force in a truss chord for a fixed bending moment, against the depth of the truss. The relationship is a reciprocal: the chords form a couple whose lever arm is the depth, so a shallow truss pays for it steeply.0.511.52050100150200250300depth of the truss2501671251007150the same moment, resisted by a longer lever arm
Fig. 5 Chord force against depth for a fixed moment, which is the whole of why a storey-deep truss beats a beam. The relationship is a reciprocal: 250 units of chord force at 0.4 m of depth and 50 at 2.0 m. The chords form a couple, and the couple’s lever arm is the depth.

Its price is occupancy of a different kind. The beam takes 0.54 of a storey and leaves the rest; the truss takes the whole storey height and gives back the triangles between its diagonals — a storey that can be walked through but not planned freely. Its deflection was found by virtual work over the members after they were sized, which is one deflection obtained without solving the structure twice: the unit-load forces in a determinate truss are the real ones divided by PP, so the sum ΣF2L/EA\Sigma F^2 L/EA needs no second analysis. And the truss is steel, so nothing about that 16 mm arrives three years late.

The wall is the extreme case and the honest one, because it is what a real podium usually does: the storey above the transfer is a party wall or a core wall, and a wall spanning 12 m over a 7.2 m depth is not a beam at all.

At a span-to-depth ratio of one, bending theory is the wrong modelA 250 mm wall panel 3,000 mm deep, spanning 3,000 mm — a span-to-depth ratio of 1. Bending contributes 0.0005 mm and shear 0.0015 mm, so 75.7% of the movement is the term beam theory drops and the total is 4.11 times what a bending calculation reports. The solver calls the regime "shear". The same panel spanning ten times as far is 3.0% shear and back in the "bending" regime, so the regime belongs to the span and not to the section. The two shapes are drawn at about 274,225 times the real movement, which is 1 in 1,532,432 of the span.3,000 mm span, 3,000 mm deepbending alone would give 0.24 of the drawn movementL/d = 175.7% shear24.3% bendingL/d = 103.0% shear97.0% bendingthe regime is "shear": the shape above has almost no curvature in it, plane sections do not stay plane,and a bending calculation is not an approximation to this behaviour but a description of a different one
Fig. 6 Why a wall used as a transfer is not a beam. A 250 mm panel 3,000 mm deep spanning 3,000 mm has 75.7% of its movement in the term beam theory drops, and the total is 4.11 times what a bending calculation reports; the same panel spanning ten times as far is 3.0% shear. The two shapes are drawn at roughly 274,000 times the real movement, which is 1 in 1,532,432 of the span.

Forty-one per cent of the transfer wall’s 4.34 mm is shear deformation, and that fraction is not a correction — it is the deflection that is not bending, scaling as (d/L)2(d/L)^2 and therefore unavoidable in exactly the members the √ law has made deep. A transfer member is deep by construction. Beam theory is at its least reliable precisely where transfer structures live.

The lever arm used for the wall’s tension tie is 5.28 m against a 7.2 m depth, and that ratio is a curve fit rather than a derivation: 0.6 of the span while the wall is at least as deep as it is long, a straight line to an ordinary bent section by the time the span is twice the depth. It descends from the deep-beam testing done at Stuttgart by Leonhardt and Walther in the mid-1960s, which established what the figure above shows — below a span-to-depth ratio of about two, plane sections do not stay plane and the lever arm stops growing with the depth. Everything deeper is material that has stopped helping.

The floor above does not get a bigger moment. It gets a different one

A floor continuous over several supports carries hogging over each support and sagging in each bay, and that redistribution is what continuity buys.

3 continuous spans against 3 simple onesThe bending moment in a continuous beam, solved by the stiffness method, drawn over the moment in the same spans made simply supported. The peak sagging moment falls from 30.6 to 19.6, and a hogging moment of 24.5 appears over the supports where there was none.moment19.6 sagging24.5 hogging30.6 if the spans were simplereactions 14.0 38.5 38.5 14.0 — the inner supports carry far more than a sharethe continuous case needed stiffness; the comparison did not
Fig. 7 What continuity does to a floor before any of this starts. Three continuous spans against three simple ones: the peak sagging falls from 30.6 to 19.6 and a hogging moment of 24.5 appears over the supports where there was none. The reinforcement follows that diagram — top steel over the supports, bottom steel in the bays.

Now settle one of those supports. The second free body of this essay is the floor above the transfer, cut nowhere and loaded not at all: a continuous beam over two 8 m bays, with no load applied whatever, and its middle support pushed down 57.6 mm. That is the support that moved, at building scale, and the moments that come back are in equilibrium with nothing.

The moment over the transferred column does not grow. It turns overBending moments in one of the 10 floors above, continuous over two 8 m bays, when the column under its middle support settles 57.6 mm — which is what the transfer member below does under the load it is carrying. The lower curve is the floor's own bending under 30 kN/m: 240 kNm of hogging over that support and 135 kNm of sagging in the bays. The middle curve is what the settlement adds on its own, 432 kNm at the support, and it is in equilibrium with no applied load at all. It is a sagging moment, so it does not pile on to the hogging — it eats it and keeps going: the total at the support is 192 kNm, which has changed sign, and the peak sagging has gone from 135 to 346 kNm. The face in tension over that column is now the one with no reinforcement in it, and reporting the peak magnitude alone misses that entirely. The settlement that makes the induced moment match the floor's own is w·bay⁴/24EI, which is 3.2 times that floor's own simply supported deflection — a ratio of two bending shapes and of nothing else.0246810121416-2000200400along two bays of the floor above (m)bending moment (kNm)-240 hoggingnow 192 saggingthe settlementalone: 432 kNmthe floor's own240 kNmthe two togetherpeak 346 kNmthe settled column
Fig. 8 Bending moments in one of the 10 floors above, continuous over two 8 m bays, when the column under its middle support settles 57.6 mm. The floor’s own bending under 30 kN/m is 240 kNm of hogging over that support and 135 kNm of sagging in the bays. The settlement alone adds 432 kNm, in equilibrium with no applied load at all — and it is a sagging moment, so the total at the support is 192 kNm, which has changed sign, while the peak sagging has gone from 135 to 346 kNm.

Two things in that diagram are worse than a larger number would have been. The first is the sign. The induced moment is sagging over the settled support, so it does not pile onto the 240 kNm of hogging — it cancels it and keeps going, and past the crossing the top face over the transferred column is in compression while the bottom face, carrying the light bottom steel of a support region, is in tension. A designer reading only the peak magnitude sees 346 kNm where 240 was expected, notes an increase of 44 per cent, and misses that a different face has become the critical one.

The second is that this happens on every floor. The settlement is imposed at the bottom of the stack and the column carries it up rigidly, so the tenth floor is displaced as much as the first, and each of the ten picks up its own 432 kNm. The transfer member has one design problem and has created ten.

A threshold with nothing in it but two shapes

The question a designer actually wants answered is how much settlement is too much, and it has a closed form of unusual purity.

Push the middle support of a two-span continuous beam down by δ\delta and the induced moment there is 3EIδ/23EI\delta/\ell^2. Set that equal to the floor’s own hogging under a uniform load, w2/8w\ell^2/8, and the settlement that makes the two equal is

δ1=w424EI.\delta_1 = \frac{w\,\ell^4}{24EI}.

That is 32 mm for these floors. Now compare it with the deflection those same floors would have if their spans were simply supported, 5w4/384EI5w\ell^4/384EI, which is 10 mm:

δ1δss=38424×5=3.2.\frac{\delta_1}{\delta_{\text{ss}}} = \frac{384}{24 \times 5} = 3.2.

No load, no modulus, no second moment, no span. All four cancel, because both quantities are the same load acting on the same beam through two different bending shapes, and the ratio of two shapes is a pure number. A floor can absorb a support settlement of about three times its own simply supported deflection before the settlement is doing as much to it as its design load does — and since a floor’s own deflection is a number every designer already knows to within a factor of two, the threshold needs no analysis at all. It is the same species of result as span to the fourth: a coefficient that belongs to the geometry of bending rather than to any structure, and that survives every change of material and scale.

The floors hold the column up

Everything so far has treated the settlement as imposed. It is not. The floors that are being bent by the settlement are pushing back on the column while they bend, and the column is passing that push down to the transfer member — so the transfer member never sees the whole 6000 kN.

At the depth strength asks for, the floors above are bent nearly twice as hard by the settlementThe moment a 10-storey stack of floors picks up from the settlement of the column below them, divided by the moment those floors carry under their own 30 kN/m, against how deep the transfer member is. At the depth strength asks for — 1.94 m — the ratio is 1.80: the settlement is doing more to the floors than the load they were designed for. The curve falls through one at 2.45 m, which is 27% more depth than the moment needed. The criterion solved in closed form asks for 2.55 m and lands at 0.909 rather than exactly one, and the gap is not an error: that calculation lets the transfer member take the whole 6000 kN, while the floors it is bending hold the column up in return. They shed 18% of the load, and the settlement with that coupling is 57.6 mm against 70.3 free.22.533.5400.511.522.53depth of the transfer member (m)settlement moment ÷ the floor's ownstrength alone: 1.94 m, ratio 1.80equal at 2.45 mthe floors holdthe column up:18% of the loadnever reaches it57.6 mm, not70.3 mm
Fig. 9 The moment a 10-storey stack picks up from the settlement below it, divided by the moment those floors carry under their own 30 kN/m, against the depth of the transfer member. At the depth strength asks for — 1.94 m — the ratio is 1.80: the settlement is doing more to the floors than the load they were designed for. The curve falls through one at 2.45 m, 27% more depth than the moment needed. The closed-form criterion asks for 2.55 m and lands at 0.909, because the floors shed 18% of the load and the settlement with that coupling is 57.6 mm against 70.3 free.

That gap between 0.909 and 1.000 is a finding rather than an error, and it is the reason the curve is drawn at all. The closed-form depth is computed as though the transfer member carried the full load; the curve solves the coupling. Each floor resists the settlement of the column it is continuous over with a stiffness of 1875 kN per metre, ten floors give 18 750 kN/m, and the transfer member’s own flexibility decides how the 6000 kN divides between the two. The fixed point is exact and needs no iteration, because both relations are linear:

δ=cP1+cnkf,\delta = \frac{cP}{1 + c\,n\,k_f},

with cc the transfer member’s flexibility. It gives 57.6 mm where the uncoupled calculation gives 70.3, and 4920 kN reaching the transfer member where 6000 was applied. Eighteen per cent of the load never arrives.

The share follows the stiffness, and always falls a little short of itThe share of a shared load taken by one member, against its stiffness measured in units of everything it shares with. The curve is r/(1 + r) and the dashed line is r itself, the share a member would take if it were paid in proportion to what it brought: the two meet only in the limit, because a member's own stiffness is part of the total it is being divided by. Three cases are marked. An equal pair splits 50% each. A 6 m beam crossing a 9 m beam is at a ratio of 3.37 and takes 77.1% — a point computed by a different solver, from compatibility of two deflections, and it lands on this curve. A beam twice as deep as its neighbour is at 8 and takes 89%. Softening is the only way down: to halve the shallow member's force its stiffness has to fall to 0.47 of what it was, not to a half.0.111000.20.40.60.81one member's stiffness ÷ the stiffness of everything it shares withthe share of the load it takesthe 6 m beam crossing the 9 m onetwice the depth: 89%an equal pair: half eachproportional to stiffness — the bound
Fig. 10 Why that 18% is not a coincidence but the general rule. Two things that share a displacement rather than a force divide the load as r/(1 + r), where r is one stiffness in units of the other — always a little short of proportional, because a member’s own stiffness is part of the total it is divided by. An equal pair splits 50% each; a stiffness ratio of 8 takes 89%.

This is the stiffest path taking the load, arriving in a place where nobody drew a second path. The floors above a transfer were designed to carry load horizontally to columns; they are also, whether anyone intended it or not, a set of springs holding one column up. The coupling makes the transfer member’s job slightly easier and makes the floors’ job substantially harder, which is a trade nobody chose and no drawing shows.

Where the model stops

The transfer member is simply supported. It is drawn on a pin and a roller, and a real one is monolithic with the columns at its ends, which reduces its span moment and its deflection and introduces moments into those columns instead. The direction of the error is favourable, and its size is whatever the end restraint is — which is neither pinned nor rigid and is not usually established.

The load arrives all at once, on a finished structure. It does not. The transfer member is propped while it is cast and the stack is built one floor at a time, so the deflection develops as the building rises and each floor’s induced moment depends on when it was built. The structure was never complete while it was being loaded, and the ten identical floors of the figure are ten different problems.

Creep is one number. The factor of three used here compresses the whole of concrete’s time behaviour into a single multiplier applied to an elastic answer. The floors above are also creeping, which relaxes some of the induced moment they are being asked to carry, and the two effects work against each other on timescales the elastic analysis has no way to represent.

The column is axially rigid. Ten storeys of column shorten under 6000 kN by an amount comparable to the settlement being discussed, and the difference between that shortening and the shortening of the columns beside it is another imposed displacement on the same floors, from a completely separate cause.

Nothing here fails. The whole essay is elastic, and a reinforced floor that cracks over a settling support sheds stiffness exactly where the induced moment is highest, which reduces the moment. The elastic calculation is a conservative upper bound on the induced moment and says nothing about the crack widths that bought the relief.

The pictures on this page cannot show the one thing that makes a transfer structure worth arguing about, which is that it is a single member with no alternative route around it. Every figure here draws a load path that works. What none of them draws is the same building with that member removed — and a transferred column is a column whose survival depends on one beam, in a structure whose other columns each depend on the ground. That asymmetry is the subject of the structure that survives losing a member, and it is why transfer members are detailed to a standard the rest of the frame is not. The moment diagram is silent on it, because a moment diagram is drawn for a structure that exists.

The ladder from here

Later rungs on this anchor: the strut-and-tie model of a deep transfer beam, where the load path is drawn explicitly as struts and ties and the plane-sections calculation is abandoned. Transfer plates, where the transfer is two-way and the moment has nowhere tidy to be cut. The construction sequence properly resolved, floor by floor, with the props struck at a stated stage. Differential column shortening in tall buildings, which is this argument with no transfer member in it at all. The outrigger, which is a transfer of moment rather than of load. Robustness and the key element, and what it means to design a member that is not permitted to fail. Transfer in seismic design, where a stiffness discontinuity at the podium is the soft-storey mechanism that has flattened more buildings than any other. And the economics of the whole thing: at what column offset it becomes cheaper to move the grid above than to build the transfer, which turns out to be a question about Pa\sqrt{P a} and about nothing else.

Named alongside this one

Essays reaching for the same objects. Nobody chose these; they are what the concept index makes visible.

What links here

Every essay whose body links to this one.

The objects this essay names

Each one links to every other essay that touches it.

CompatibilityCreepLever armLoad pathServiceabilityStiffnessSupport settlementTransfer structure