Stability

The column that fails years later

A concrete column under sustained load goes on straining at constant stress, so its deflection grows — and because the second-order moment is the load times that deflection, the demand grows with it. There is a load below which the two settle and one above which they never do.

Assumes The load that makes itself worse, The deflection that arrives three years late and Strong enough and still falls over.

Two facts about concrete are taught in different courses and are almost never put together.

The first is that concrete creeps: hold a stress on it and the strain goes on growing for years, reaching two or three times its instantaneous value. The second is that a compression member’s deflection is amplified by 1/(1−N/Ncr)1/(1 - N/N_{cr}), because the axial load acts on the deflection it has already produced.

Put them together and the amplifier has a denominator that closes with time.

The deflection goes on growing, and sometimes it does not stop. Second-order deflection of a sustained-loaded concrete column against age, on a log time axis. Creep takes the effective modulus down, which takes the buckling load down with it — from 11580 kN on the day to 3309 in the long term, 29 per cent of it — so the amplifier 1/(1 − N/N_cr) grows even though nothing was added to the load. At 2200 kN the column settles: 25 mm of eccentricity on the day and 60 mm at the end, a factor of 2.4 for a load that never changed. At 5294 kN — still only 46 per cent of the day-one critical load — it does not settle, and the divergence arrives at 55 days for no new reason at all.
Fig. 1 Second-order eccentricity of a sustained-loaded column against age, on a logarithmic time axis. At 2,200 kN the column settles: 25 mm of eccentricity on the day and 60 mm at the end, a factor of 2.4 for a load that never changed. At 5,294 kN — still under half the day-one critical load — it does not settle, and the divergence arrives after 55 days.

Which free body produced the number

Cut the column at mid-height and take the lower half. The moment there is the axial force times the total eccentricity, and the total eccentricity is the first-order one plus whatever the column has already bent.

For a pin-ended column with a sinusoidal imperfection or a sinusoidal first-order moment, that closes into the standard amplifier

e=e01−N/Ncre = \frac{e_0}{1 - N/N_{cr}}

which is exact for the sine shape and near enough for everything else. The only quantity in it that time can touch is NcrN_{cr}, and NcrN_{cr} is π2EI/L2\pi^2 EI/L^2 — the ordinary elastic critical load, a stiffness divided by a length squared, with no clock in it anywhere.

The load that makes itself worse. The amplification of a deflection against the ratio of applied load to buckling load. A structure at half its buckling load deflects twice as far as first-order analysis predicts, and the curve runs away well before the load is reached.
Fig. 2 The amplifier by itself, with no time in it at all: the factor a deflection is multiplied by, against the ratio of applied load to buckling load. A member at half its buckling load deflects twice as far as a first-order analysis says, and the curve runs away well before the load is reached. Everything after this figure is the same curve read from right to left, by a column whose critical load is falling while the load standing on it does not move.

Creep touches EE. The effective-modulus method is the simplest honest way to say how: a stress held constant produces a strain that grows by the factor (1+φ)(1 + \varphi), so the member behaves as though its modulus were E/(1+φ)E/(1+\varphi), and

Ncr,∞=Ncr,01+φ∞N_{cr,\infty} = \frac{N_{cr,0}}{1 + \varphi_\infty}

For an ordinary creep coefficient of 2.5, that is 29 per cent of the day-one value. A column checked at a comfortable third of its buckling load on the day it is propped is above its long-term buckling load.

The deflection that arrives years late. The multiplier on a concrete member's deflection under a sustained load, against time. The elastic deflection arrives on the day the load does and is the 1.0 at the left. After a year it has been multiplied by 3.09, after five years by 3.39, and it approaches 3.48. Nothing has been added to the load and nothing about the strength has changed: this is a serviceability failure arriving on a structure that passed every strength check on the day it was built.
Fig. 3 The coefficient the whole argument runs on. It is not a small correction and it is not fast: half of it arrives in the first year and the rest over the following decade, so the structure this essay describes is doing its most dangerous work long after everybody has gone home.

Two regimes, and a boundary that is a fraction

The consequence is a clean division.

Below Ncr,0/(1+φ∞)N_{cr,0}/(1+\varphi_\infty) the column settles. Its deflection grows — by a factor of 2.4 on the column drawn, from 25 mm to 60 — and stops, because φ\varphi approaches a limit and so does the amplifier. That is a serviceability outcome: a column visibly bent, its moment larger than the design one, and stable.

Above it there is nothing to settle to. φ\varphi passes the value at which N=Ncr(t)N = N_{cr}(t), the amplifier passes through infinity, and the column fails at a moment fixed by a material property rather than by an event.

The date is not found by watching a number run away. It is found by inverting the creep law: the divergence happens when

φ(t)=Ncr,0N−1\varphi(t) = \frac{N_{cr,0}}{N} - 1

and the creep law is a known function of time, so the answer comes back directly. At 46 per cent of the day-one critical load it is 55 days. At 38 per cent it is 123 days. At 57 per cent it is 34.

Below a line it settles, above it there is a date. When a sustained-loaded column stops moving, or does not, against how much of its day-one buckling load it is carrying. Creep takes the effective modulus to E/(1 + φ), so the long-term critical load is 29 per cent of the short-term one for a creep coefficient of 2.5. Below that fraction the second-order deflection converges to a finite value, and the column is safe with a deflection several times what a day-one calculation gave. Above it there is no equilibrium to converge to, and the curve is the age at which the amplifier diverges — found by inverting the creep law rather than by watching a number run away. At 0.95 of the day-one critical load it arrives after 28 days, with nothing having been added to the load and nothing having changed on site.
Fig. 4 When the column stops moving, or does not, against how much of its day-one buckling load it carries. The shaded region settles; the curve is the age at which the amplifier diverges, and it is steep — a column ten per cent above the boundary lasts a third of a year and one fifty per cent above it lasts a month.

Which is why the check is written the way it is

The design rules for slender concrete columns look arbitrary until this is in view.

They ask for a creep-adjusted stiffness, computed with an effective creep ratio that is not the material’s φ∞\varphi_\infty but φ∞\varphi_\infty scaled by the fraction of the load that is permanent — because a column carrying half its load as imposed floor loading only creeps under the half that stays. They ask for an imperfection, because the amplifier has no answer for a perfectly straight column and every real column is not. And they ask for a nominal stiffness or a nominal curvature rather than a section analysis, which is a way of admitting that the stiffness in the denominator is not a property anyone can compute exactly.

Every one of those is a response to the same structure: an amplification whose denominator depends on a stiffness that is falling.

The deflection goes on growing, and sometimes it does not stop. Second-order deflection of a sustained-loaded concrete column against age, on a log time axis. Creep takes the effective modulus down, which takes the buckling load down with it — from 11580 kN on the day to 4632 in the long term, 40 per cent of it — so the amplifier 1/(1 − N/N_cr) grows even though nothing was added to the load. At 2200 kN the column settles: 25 mm of eccentricity on the day and 38 mm at the end, a factor of 1.5 for a load that never changed. At 7411 kN — still only 64 per cent of the day-one critical load — it does not settle, and the divergence arrives at 40 days for no new reason at all.
Fig. 5 The same column with the creep coefficient at 1.5 rather than 2.5, which is roughly what an effective creep ratio does to a member carrying three-fifths of its load permanently. The long-term buckling load rises from 3,309 kN to 4,632 — 40 per cent of the day-one value rather than 29 — and the load at which the column stops settling moves from 46 per cent of the day-one critical load to 64. At 2,200 kN the eccentricity now grows from 25 mm to 38 rather than to 60.

That is the whole content of the phrase effective creep ratio, and it is a statement about the load rather than about the concrete. Two columns cast from one mix on one morning, checked against the same material coefficient, sit on either of those two curves according to nothing but what fraction of what they carry will still be there in twenty years.

The same shape in three materials

The structure of this argument is not about concrete. It is about a compression member whose stiffness falls while it is loaded, and there are at least three of those in this collection.

Timber has a duration-of-load factor — a strength reduction for permanent loading — and a creep factor that does exactly what φ\varphi does here, with the added difficulty that both depend on moisture content. A timber column’s long-term buckling load is a smaller fraction of its short-term one than concrete’s.

Steel at temperature is the same equation with the clock running much faster. The hour that is really a temperature is the strength side of it; the stiffness side is that steel’s modulus falls faster than its strength does above about 400 °C, so a steel column in a fire loses buckling capacity before it loses squash capacity, and a slender one fails in minutes at a load a stub column would carry. What makes fire and creep one problem is that both are a member’s modulus collapsing under a load that is not changing; what makes them two is only how long there is to notice.

And any structure with a soil under it. A footing on clay is a spring whose stiffness falls as consolidation proceeds, and a frame whose sway stiffness depends on that spring is a frame whose NcrN_{cr} falls with time — the same divergence, with the creep in the ground rather than in the member.

The load that is permanent, and the load that is not

The strongest simplification in the analysis above is that all of the load creeps, and correcting it is where the design rule earns its complexity.

Creep responds to the stress that is held. A column carrying 2,200 kN of which 1,400 is dead load and 800 is a floor loading that comes and goes creeps under something much closer to 1,400 — so its effective creep ratio is the material’s coefficient scaled by the ratio of permanent to total.

That scaling has a consequence worth stating plainly: two columns carrying the same total load can have long-term buckling loads a factor of two apart, according to which of them is holding a warehouse and which is holding a car park. The load case that governs the day-one check is the full one; the load case that governs the long-term check is the permanent part; and the two are different structures asked different questions.

It also means the mode is worst in exactly the buildings where it is least expected. A heavily loaded transfer column under a residential tower is nearly all permanent load, creeping at nearly the full coefficient, for the whole life of the structure.

The deflection goes on growing, and sometimes it does not stop. Second-order deflection of a sustained-loaded concrete column against age, on a log time axis. Creep takes the effective modulus down, which takes the buckling load down with it — from 11580 kN on the day to 3309 in the long term, 29 per cent of it — so the amplifier 1/(1 − N/N_cr) grows even though nothing was added to the load. At 1400 kN the column settles: 23 mm of eccentricity on the day and 35 mm at the end, a factor of 1.5 for a load that never changed. At 5294 kN — still only 46 per cent of the day-one critical load — it does not settle, and the divergence arrives at 55 days for no new reason at all.
Fig. 6 The same column asked to hold only the permanent 1,400 kN of its 2,200. The two buckling loads are untouched at 11,580 kN and 3,309, because they belong to the member and not to what is standing on it, and the upper curve still turns over at 46 per cent of the day-one load. What changes is the settled answer: the eccentricity grows from 23 mm to 35 rather than from 25 to 60, a factor of 1.5 instead of 2.4.

The two calculations that follow from the same coefficient are usually done by different people. The creep that softens a column against its own buckling load is also the creep that shortens it differentially against its neighbours, and a differential-shortening study and a slenderness check are separate documents in most offices — written from one material property, about one set of members, and never laid beside each other.

The failure has no cause and no warning

The most useful thing to say about this mode is what it looks like from outside.

Nothing happens. The load has not changed, no new load has been applied, no material has been substituted, and the weather is the same as it was. A column bends slowly for months and then bends quickly, and the interval between “visibly out of plumb” and “gone” is short because the amplifier’s growth is not linear — it is a reciprocal approaching a zero.

There is therefore no event to investigate. A collapse of this kind produces an inquiry that finds no cause, because the cause was the absence of a check performed twenty years earlier at a moment when the structure was demonstrably safe.

That is the argument for the check being about a fraction rather than about a stress. A stress-based check on the column drawn passes comfortably at every age; the load is a fifth of the day-one buckling load and the concrete is nowhere near its strength. What fails is a comparison between a load and a stiffness, and stiffness is the quantity structural checks are least often written in.

The deflection goes on growing, and sometimes it does not stop. Second-order deflection of a sustained-loaded concrete column against age, on a log time axis. Creep takes the effective modulus down, which takes the buckling load down with it — from 11580 kN on the day to 3309 in the long term, 29 per cent of it — so the amplifier 1/(1 − N/N_cr) grows even though nothing was added to the load. At 2200 kN the column settles: 6 mm of eccentricity on the day and 15 mm at the end, a factor of 2.4 for a load that never changed. At 5294 kN — still only 46 per cent of the day-one critical load — it does not settle, and the divergence arrives at 55 days for no new reason at all.
Fig. 7 The same column built four times straighter, with an initial eccentricity of 5 mm instead of 20. At 2,200 kN it now runs from 6 mm on the day to 15 mm at the end — and the factor between those is 2.4, exactly the factor the crooked column gave. Straightness buys a smaller deflection and buys nothing whatever in the ratio, because the amplifier does not know how large the thing it is amplifying is.

That is the sense in which a perfectly straight column is not the useful idealisation. The amplifier needs something to amplify, and the bifurcation load of a perfect member is not a quantity this failure ever reaches; what the column does is take a crookedness it already had and grow it, at a rate set by the load ratio and the creep coefficient and by nothing else on the drawing.

The number a designer can actually move

There are four quantities in Ncr,∞=π2EI/(1+φ)L2N_{cr,\infty} = \pi^2 EI/(1+\varphi)L^2, and they are not equally available.

φ\varphi belongs to the concrete and the environment, and the range a designer controls is narrow — a lower water-cement ratio, a later age at loading, a larger member. EE moves with the aggregate and hardly at all with the grade. LL is the storey height, which is architecture.

What is left is II, and it is the one that responds quadratically. Taking the 400 mm column drawn to 500 mm multiplies its second moment by 2.4 and its long-term critical load with it, and costs a hundred millimetres of plan.

That is why the practical response to a slender concrete column is almost never a stronger concrete. A grade increase buys a little modulus — EE goes roughly as the cube root of the strength — and buys nothing at all in the quantity that is falling. A creep problem is solved with geometry. It is the same conclusion the section-shape comparison reaches by a completely different route, and it holds here more strongly, because the property being lost is stiffness rather than strength.

The deflection goes on growing, and sometimes it does not stop. Second-order deflection of a sustained-loaded concrete column against age, on a log time axis. Creep takes the effective modulus down, which takes the buckling load down with it — from 28272 kN on the day to 8078 in the long term, 29 per cent of it — so the amplifier 1/(1 − N/N_cr) grows even though nothing was added to the load. At 2200 kN the column settles: 22 mm of eccentricity on the day and 27 mm at the end, a factor of 1.3 for a load that never changed. At 12924 kN — still only 46 per cent of the day-one critical load — it does not settle, and the divergence arrives at 55 days for no new reason at all.
Fig. 8 The identical calculation with the 400 mm column taken to 500. The day-one buckling load goes from 11,580 kN to 28,272 and the long-term one from 3,309 to 8,078 — a factor of 2.44 on both, which is the second moment’s factor and nothing else, since the ratio between them is fixed at 29 per cent by the creep coefficient alone. The eccentricity at 2,200 kN now grows from 22 mm to 27 rather than from 25 to 60.

The axis that moved there is the section’s own geometry. Creep leaves the one length a section takes into a column exactly where it was and takes the modulus down instead, so the only response available is on the axis the modulus is not on. Put the other way round: losing two-thirds of the modulus is arithmetically the same as making the column 3.5\sqrt{3.5} times more slender overnight, and no grade of concrete undoes that.

The reason no test finds it

A structural test is a load applied over minutes. Creep buckling is a load applied over years, and that difference is why the mode is known from theory and from collapses rather than from laboratories.

The obvious response — hold a column at a load for a decade and watch — has been done a handful of times and is not a routine. What is done instead is to accelerate: load at a high stress ratio, where the creep coefficient is reached in months rather than decades, and extrapolate. That works for the arithmetic and imports its own assumption, because concrete’s creep is not linear in stress above about forty per cent of its strength, and the accelerated test is run in exactly that region.

So the design rule for slender concrete columns rests on a chain: a creep model fitted to short-term specimens, an effective modulus that assumes a constant stress, and an amplification derived for an elastic member. Each link is defensible and the chain has never been tested end to end at the timescale it is written for. That is worth knowing when reading a code clause that looks as settled as a strength check. It is not the only curve built that way, either: the fatigue curve extrapolates from an experiment shorter than the life of the structure by the same order of magnitude, and both are honest about it only in the small print.

The creep coefficient is not a constant either

There is a second loop inside the first, and it makes the divergence sharper than the linear arithmetic says.

Creep is proportional to stress only up to about 40 per cent of the concrete’s strength. Above that it becomes progressively nonlinear, and near 70 or 75 per cent it accelerates without limit — the tertiary creep that makes a sustained-load strength a real quantity rather than a curiosity.

Now follow a bowing column. Its lateral deflection grows, which grows the moment, which raises the stress in the compression face well above the average stress in the member. A column at a comfortable mean stress of 0.3 fcf_c can have an extreme fibre well past 0.4 once the second-order moment has arrived — and that fibre is then creeping faster than the linear coefficient says.

So the chain has an extra link in it. More bow, more moment, more extreme-fibre stress, faster creep in the fibre that is causing the bow, more bow. The linear model treats φ\varphi as a material property being applied uniformly; the real member is creeping hardest exactly where creeping hardest does the most damage.

Two consequences follow. The divergence is earlier and sharper than the linear calculation gives, so the date the curve returns is optimistic rather than conservative. And the effect is confined to columns already at a high load ratio, which is the population the whole essay is about — a lightly loaded column never gets its extreme fibre into the nonlinear region and the linear model describes it perfectly well.

What can be done about it

The levers are few and their ranking is unusual.

Reduce the load ratio. The only lever that acts on the mechanism itself, and it works because the whole failure is a comparison between a load that does not change and a critical load that falls.

Add a restraint. Halving the unbraced length quadruples the critical load at every age, which does not stop the decline but moves the date it crosses the applied load by decades. It is the cheapest structural intervention available and it is a stiffness rather than a strength.

The deflection goes on growing, and sometimes it does not stop. Second-order deflection of a sustained-loaded concrete column against age, on a log time axis. Creep takes the effective modulus down, which takes the buckling load down with it — from 46321 kN on the day to 13235 in the long term, 29 per cent of it — so the amplifier 1/(1 − N/N_cr) grows even though nothing was added to the load. At 2200 kN the column settles: 21 mm of eccentricity on the day and 24 mm at the end, a factor of 1.1 for a load that never changed. At 21175 kN — still only 46 per cent of the day-one critical load — it does not settle, and the divergence arrives at 55 days for no new reason at all.
Fig. 9 The same column held at mid-height, so the buckling length is 3,000 mm rather than 6,000. The day-one critical load rises from 11,580 kN to 46,321 and the long-term one from 3,309 to 13,235, and the eccentricity at 2,200 kN grows from 21 mm only to 24 — a factor of 1.1 where the unrestrained column gave 2.4. The load at which this column would stop settling is now 21,175 kN, which nothing is going to put on it.

Nothing in that figure repaired the concrete. The creep coefficient is the same 2.5, the modulus falls by the same factor over the same decade, and the long-term critical load is still 29 per cent of the day-one one. What moved is where 2,200 kN sits on that falling number, and a member restrained at mid-height sits so far below it that the decline never catches up.

Or take the load off. Which is the remedy nobody lists, because it is not a design measure at all. A prop that is struck has stopped creep-buckling, permanently, on the day it is removed — and since the members this failure happens to are almost all temporary, the commonest fix is to finish the job.

Where the model stops

The effective-modulus method is the crudest of the creep formulations. It is exact for a stress held constant from a single instant and approximate for anything else; a load applied in stages, or partly removed, needs a superposition method or an age-adjusted modulus, and both give a slower loss of stiffness than the number here.

Cracking is a fixed factor. The 0.6 applied to EIEI stands in for a section that is partly cracked, and a real column’s cracked stiffness depends on the moment it is carrying — which is the moment this calculation is trying to find. The honest version is iterative and the answer moves in the unhelpful direction: more moment, more cracking, less stiffness, more moment.

The creep coefficient is treated as a property. It depends on the humidity, the member’s surface-to-volume ratio, the age at loading and the mix, and a factor of two either way across those is ordinary. Since it appears as 1/(1+φ)1/(1+\varphi), that factor of two is a factor of nearly two in the long-term critical load.

The creep law is a curve fitted to tests. The expression used here reaches its final value asymptotically with a time constant of a few hundred days, which is the ordinary shape, and the date it returns for a divergence is only as good as that shape near the value of φ\varphi that matters. Two creep models that agree about the thirty-year answer can disagree by months about when a particular coefficient is reached, and it is the second that this calculation asks for.

And the column is pin-ended and prismatic. A real column is in a frame, and its effective length depends on members whose own stiffness is creeping — so the buckling length is also a function of time, and not necessarily in the safe direction.

What the pictures cannot show

The time axis is logarithmic, which is the only way to draw a process that is half over in a year and continues for thirty. It makes the divergence look like an event at a date; on a linear axis it would look like a curve that becomes vertical, which is closer to the truth and impossible to plot next to the first month.

Nor can any figure show the thing that decides whether this failure mode ever arrives, which is what else is holding the structure up. A column in a braced frame that fails in creep buckling sheds its load to its neighbours; a column that is the only thing under a transfer beam does not. The mode is a property of a member and the consequence is a property of the structure, and nothing on this page is about the second.

The assumption the figure rests on

The load is assumed to be constant from the day it is applied.

Almost no load is. A building is loaded in stages as it is built, its imposed load comes and goes, its prestress relaxes, and the concrete’s own creep redistributes force from the members that creep most to the members that creep least. Each of those makes the effective creep coefficient smaller than the material’s, which is why the check in practice uses a ratio of permanent to total load rather than the coefficient itself.

The one case where the assumption is exactly right is the one that matters most. A prop, a temporary column, a falsework leg under wet concrete: loaded at once, at an age when the concrete is young and creeps fastest, at a load fraction chosen for a short-term check, and left in place for as long as the programme requires. That is where creep buckling has actually happened, and it is not a category of structure anybody designs with a long-term stiffness in mind.

Named alongside this one

Essays reaching for the same objects. Nobody chose these; they are what the concept index makes visible.

What links here

Every essay whose body links to this one.

The objects this essay names

Each one links to every other essay that touches it.

AmplificationBucklingCreepCreep bucklingDivergenceDuration of loadEccentricityEffective modulusFireImperfectionSecond-orderServiceabilitySlendernessStiffnessSustained load