Concept

Ponding — where it appears

The loop in which a flat roof's sag admits water, the water deepens the sag, and the two feed each other until the bay stiffens or fails. It is mathematically the same instability as a buckling column, with rain in the role of the axial load, and it has the same runaway at a critical stiffness.

Named by 5 essays across one field — each of them below, with the objects they name alongside it.

The water that will not run off. Water depth against sag at the middle of the bay, for a roof bay starting with a reversed construction camber of 0.01. There is no critical value to reach: the deflection grows from the first increment, slowly at first and then without bound as the ratio approaches 1.00 — which is the depth at which the bay fills faster than it stiffens, and which the roof bay therefore never attains. The perfect roof bay, drawn for comparison, sits on the vertical axis until it arrives there and then has no answer at all.

The water that will not run off

A flat roof deflects, the deflection makes room for water, the water deepens the deflection. It is the same equation as a buckling column, with rain in place of the axial load.

deflection · Serviceability
Four camber rules, and what each leaves on the finished beam. The same 12 m composite beam, cambered against four different things, followed through its own load history. Positive is a sag and negative a hog, and the point at the left of each line is the shape it was fabricated to. Cambering against the wet concrete leaves 12.7 mm of sag at the end and a flat beam on the day the slab is poured; cambering against the total load leaves the beam dead flat when fully loaded and hogged 37.9 mm — one part in 316 of the span — before anything is on it at all.

Built to the wrong shape on purpose

A cambered beam is fabricated curved upward so that load bends it down to something like straight. Nothing in the analysis changes, no stress anywhere is altered, and almost every mistake made with it is a bookkeeping mistake about which loads count.

deflection · Camber
Two members each half-way to ponding are unstable together. The girder's ponding parameter Cp against the joist's Cs. Either member alone is stable up to 1; together the roof is stable only below the solid curve, (1 − Cp)(1 − Cs) = (8/π²)·Cp·Cs, which meets the diagonal at 0.526 — two members each about half-way to ponding on their own are critical together. The dashed line is the simplified rule Cp + 0.9Cs ≤ 0.25. The marked roof is a 12 by 9 m bay whose girders and joists are each sized to deflect L/240 under 1.5 kN/m²: Cp = 0.26 and Cs = 0.19, stable, with its joists' sag amplified 1.79 times where the joist alone would say 1.24 and the girder alone 1.35.

The roof that ponds on its girders

A flat roof's joists sit on girders, and the water fills the sum of both their sags. Two members each half-way to ponding on their own are unstable together, and long before that the growth of the water is far larger than either member's own amplification says. AISC's simplified rule turns out to be a line of constant growth, and a member sized to a deflection limit has a ponding parameter proportional to its span — so a bay sized to L/240 under 1.5 kN/m² meets the rule up to 6 m, doubles its water at 12 and ponds at 24.5.

deflection · Serviceability
Where the outlet sits decides whether the roof ponds at all. The load the water puts in the more heavily loaded member of a square bay, over what the same head of water would put in it on a rigid roof, against the bay's side, with girders and joists each sized to deflect L/240 under 1.5 kN/m². With the level fixed by a scupper it is 2.01 at 12 m and 3.92 at 18 m, and the bay ponds at 24.5 m. With a drain on the girder line it is 1.24 and 1.41; with a drain at the bay's middle, 0.82 and 0.75, falling as the bay grows, because the water's surface goes down with the roof.

The roof that drains towards its sag

The depth of water a ponding check takes as given is set by the drainage: an overflow's height above the roof, plus the head a storm needs to leave through it. Which head a roof can carry depends less on how stiff it is than on where the overflow sits. With the level fixed by a scupper in the parapet, a 12 by 9 m bay allows 85 mm of water and an 18 m square bay 39. With a drain at the middle of the bay, whose inlet goes down as the roof sags, the same bays allow 182 and 205 mm — more than a rigid roof would — because the water's surface follows the sag down instead of filling it.

deflection · Serviceability
How much of the drain has to work. The load in the more heavily loaded member, with the roof's own 0.5 kN/m², over its 2.0 kN/m² capacity, for a 12 by 9 m bay in a 150 mm/h storm, with a drain at its middle that passes the storm at 30 mm when clear and a 400 mm scupper at its edge whose sill is 50 mm above the supports, against the share of a clear drain's flow the drain still passes. Members at L/180, L/240, L/360 and rigid: with the drain fully blocked, 1.25, 0.99, 0.84, 0.66; a tenth open, 0.80, 0.77, 0.71, 0.62; half open, 0.44, 0.45, 0.46, 0.48; clear, 0.37, 0.37, 0.38, 0.40. A softer roof is the worse with the drain blocked and very slightly the better once about a fifth of it works.

The drain that is mostly blocked

A roof's ponding check is made with its primary drains blocked, and a drain is seldom blocked outright: leaves and gravel choke it to a fraction of its flow. A fraction turns out to be nearly enough. On a 12 by 9 m bay sized to L/240, a drain passing a seventh of its clear flow still takes the whole of a 150 mm/h storm, because the water standing over it at the bottom of the sag is the bay's own deflection plus the level. A softer roof's drain works harder still. Only near complete blockage does the scupper take over, and only there does stiffness help.

deflection · Serviceability

Named alongside it

The objects these essays reach for when they reach for this one.

ServiceabilityDeflectionDeflection limitAmplificationAmplification factorCritical loadLoad pathStabilityStiffnessComposite actionConstruction sequenceCreep