Concept

Amplification factor — where it appears

The ratio by which a response exceeds the one a slowly applied load of the same size would produce. For a suddenly applied static load it is two, and near a structure's own frequency it is bounded only by the damping.

Named by 8 essays across 2 fields — each of them below, with the objects they name alongside it.

The load that makes itself worse. The amplification of a deflection against the ratio of applied load to buckling load. A structure at half its buckling load deflects twice as far as first-order analysis predicts, and the curve runs away well before the load is reached.

The load that makes itself worse

A structure that has leaned carries its weight off the axis, which makes it lean further. The amplification is one over one minus the load ratio, and it runs away long before the buckling load.

stability · Second-order
A column that was never straight. Load against lateral deflection at mid-height, for a column starting with an initial bow of 0.002. There is no critical value to reach: the deflection grows from the first increment, slowly at first and then without bound as the ratio approaches 1.00 — which is the Euler load, and which the column therefore never attains. The perfect column, drawn for comparison, sits on the vertical axis until it arrives there and then has no answer at all.

The column that was never straight

Euler's load is the load at which a perfectly straight column becomes indifferent to being bent. No column is perfectly straight, so no column ever reaches it — and the load it never reaches can still be measured.

stability · Buckling
The water that will not run off. Water depth against sag at the middle of the bay, for a roof bay starting with a reversed construction camber of 0.01. There is no critical value to reach: the deflection grows from the first increment, slowly at first and then without bound as the ratio approaches 1.00 — which is the depth at which the bay fills faster than it stiffens, and which the roof bay therefore never attains. The perfect roof bay, drawn for comparison, sits on the vertical axis until it arrives there and then has no answer at all.

The water that will not run off

A flat roof deflects, the deflection makes room for water, the water deepens the deflection. It is the same equation as a buckling column, with rain in place of the axial load.

deflection · Serviceability
Wrong in both directions until the building racks. Across buildings from a pure bending tower to a pure racking frame (αH on a logarithmic scale), each 20 storeys with gravity putting its own critical factor at 5.0: solid, the least storey sway factor over the building's own, which is what taking the least storey as the building's costs; dashed, the ground storey's second-order increase estimated from its own sway factor, over the true increase. At αH = 0.1 the least storey factor is 0.77 of the true one and the ground storey's estimate 0.09 of the true increase; at αH = 10, 0.86 and 0.37; at αH = 100, 0.94 and 0.98. The first error is on the safe side and the second is not, and both vanish only for a building that racks.

The storey that cannot see the building lean

A sway check made storey by storey asks each storey how much it drifts under a push and how much gravity sits on it, and reads a critical load factor for the storey from the two. For a frame whose storeys rack like a stack of shelves that is exact. For a building that bends — a braced core, a wall — it is wrong twice. Taking the least storey as the building's reads a critical factor of 3.9 for a building whose own is 5. And amplifying each storey by its own factor finds a 2 per cent second-order increase at the ground storey, where the truth is 20, because the ground storey hardly drifts and carries the lean of everything above it.

stability · Sway stability
The buckling mode moves up to where the spine is not. The building's first buckling mode, each floor's sideways movement as a fraction of the roof's, up the height of a 20-storey building of a bending spine and a racking frame (αH 1.0), its gravity scaled to an elastic critical factor of 5.0, under an equal lateral load at every floor: the spine to the roof, and stopping at storeys 15 and 10. With the spine to the roof the mode is the bending tower's, growing all the way up. With the spine stopping, at storey 15 its top moves less than a thousandth as far as the roof, and at storey 10 its top moves less than a thousandth as far as the roof: the building buckles in the first storey of frame above the spine, every floor above that storey moving with it as one, and the spine takes no part.

The storey above the core decides

A building whose bending core runs to the roof shares one sway mode between its core and its frame, and the storey-by-storey stability check reads it wrongly twice. Stop the core five storeys short and the check becomes exact: the first storey of bare frame above the core reads the building's own critical factor to three figures, because the whole building buckles there and nowhere else. The check stays wrong below the core, and it goes wrong again when the frame above is more than about twice as stiff.

stability · Sway stability
Two members each half-way to ponding are unstable together. The girder's ponding parameter Cp against the joist's Cs. Either member alone is stable up to 1; together the roof is stable only below the solid curve, (1 − Cp)(1 − Cs) = (8/π²)·Cp·Cs, which meets the diagonal at 0.526 — two members each about half-way to ponding on their own are critical together. The dashed line is the simplified rule Cp + 0.9Cs ≤ 0.25. The marked roof is a 12 by 9 m bay whose girders and joists are each sized to deflect L/240 under 1.5 kN/m²: Cp = 0.26 and Cs = 0.19, stable, with its joists' sag amplified 1.79 times where the joist alone would say 1.24 and the girder alone 1.35.

The roof that ponds on its girders

A flat roof's joists sit on girders, and the water fills the sum of both their sags. Two members each half-way to ponding on their own are unstable together, and long before that the growth of the water is far larger than either member's own amplification says. AISC's simplified rule turns out to be a line of constant growth, and a member sized to a deflection limit has a ponding parameter proportional to its span — so a bay sized to L/240 under 1.5 kN/m² meets the rule up to 6 m, doubles its water at 12 and ponds at 24.5.

deflection · Serviceability
Hung from its deck, the rib's bending is not amplified at all. The bending moment along a 60 m parabolic rib at a 12 m rise (EI 250,000 kN·m²) under 25 kN/m of dead load and 10 kN/m of live load on the left half. Standing free on pinned springings (solid) it peaks at 1,303 kN·m, against 576 at first order (dashed): the thrust amplifies the half-span bending 2.26 times. The same rib hung over a deck 0.10 times as stiff as the rib on vertical hangers (thick) peaks at 524 kN·m, 0.99 times its first-order 528, and the deck (thin) carries 59. The deck closes the thrust in tension, and the tension it carries straightens the deck as much as the thrust bends the rib.

The rib that cannot lean on its own tie

A free arch rib under a half-span live load bends in the shape of its own buckling mode, and its thrust amplifies the bending more than twofold. Hang a deck from the same rib on vertical hangers and close the thrust in the deck, and the amplification disappears: the thrust and the tie's pull move together, so the couple they make keeps its lever arm, and the only second-order term left is the small difference between the rib's deflection and the deck's. The critical load rises sixteenfold, and the deck's share of the bending is simply its share of the stiffness.

stability · Arch buckling
A hat makes the top storeys look stiff. Each storey's own sway factor α up the height of a 20-storey building of a core to the roof and a racking frame (αH 1.0), its gravity scaled to an elastic critical factor of 5.0, under an equal lateral load at every floor: with no hat, with a hat truss at the roof holding the core's rotation with 10 times the core's EI/H, and with the same restraint at storey 10; the building's critical factor 5.0 as a vertical line. With no hat the top storeys read the least, 4.06 at the roof. With the hat the roof storey reads 15.47 and the least, 4.14, has moved down to storey 9. With the outrigger at mid-height the least is back at the top, 3.85.

The hat that hides the lean

A hat truss on a core-and-frame building holds the top of the core, nearly doubles the building's critical load, and makes its top storeys look three or four times as stiff as they did. The storey check believes them. Under the hat the roof storey reads a sway factor of 15 and estimates 7 per cent of second-order drift; the building still buckles leaning, and the roof storey's true increase is 24 per cent. The hat turns the storey check from pessimistic to unsafe at exactly the storeys it was built to stiffen.

stability · Sway stability

Named alongside it

The objects these essays reach for when they reach for this one.

Critical loadP-deltaBuckling modeStorey driftSway stabilityCritical load factorDeflection limitImperfectionLateral systemPondingSecond-order effectsServiceability