Sway stability — where it appears
Named by 6 essays across 2 fields — each of them below, with the objects they name alongside it.
The load that is really a lean
No frame is ever plumb. The columns are out of upright by something like a three-hundredth, and every tonne of gravity load standing on that lean has a horizontal component. The force that represents it is not a safety allowance — it is an exact statics substitution for a geometry nobody drew.
Counted, not checked
A column with pinned ends and no bracing cannot buckle on its own, so nothing about it fails a stability check. It still carries load, and load with no stiffness attached lowers the buckling load of everything around it — which is why a gravity-only column is put on the frame model and never designed by itself.
The pinned base that is not pinned
A column base drawn as a pin is a plate bearing on grout, and a plate in contact over its whole length resists rotation whether anybody wanted it to or not. The stiffness it delivers depends on the axial load, so the assumption is one a frame can leave and re-enter as its loads change.
The storey that cannot see the building lean
A sway check made storey by storey asks each storey how much it drifts under a push and how much gravity sits on it, and reads a critical load factor for the storey from the two. For a frame whose storeys rack like a stack of shelves that is exact. For a building that bends — a braced core, a wall — it is wrong twice. Taking the least storey as the building's reads a critical factor of 3.9 for a building whose own is 5. And amplifying each storey by its own factor finds a 2 per cent second-order increase at the ground storey, where the truth is 20, because the ground storey hardly drifts and carries the lean of everything above it.
The storey above the core decides
A building whose bending core runs to the roof shares one sway mode between its core and its frame, and the storey-by-storey stability check reads it wrongly twice. Stop the core five storeys short and the check becomes exact: the first storey of bare frame above the core reads the building's own critical factor to three figures, because the whole building buckles there and nowhere else. The check stays wrong below the core, and it goes wrong again when the frame above is more than about twice as stiff.
The hat that hides the lean
A hat truss on a core-and-frame building holds the top of the core, nearly doubles the building's critical load, and makes its top storeys look three or four times as stiff as they did. The storey check believes them. Under the hat the roof storey reads a sway factor of 15 and estimates 7 per cent of second-order drift; the building still buckles leaning, and the roof storey's true increase is 24 per cent. The hat turns the storey check from pessimistic to unsafe at exactly the storeys it was built to stiffen.
Named alongside it
The objects these essays reach for when they reach for this one.
P-deltaAmplification factorBuckling modeCritical loadFree bodyLateral systemSecond-orderStorey driftBracingCritical load factorEccentricityEffective length