Concept

Bracing — where it appears

A member supplied to shorten another's buckling length, which needs a threshold stiffness rather than a strength and buys nothing beyond it. The stiffness required is exact and is reached at a knee past which more buys nothing, and the force the brace carries comes from the member's initial crookedness rather than from the eigenvalue.

Named by 32 essays across 5 fields — each of them below, with the objects they name alongside it.

The count is necessary and not sufficient. Two pin-jointed frames, each satisfying m + r = 2j exactly. One of them folds anyway, because the equations are not independent; the ghosted outline is the motion that costs no member any change of length, drawn at an exaggeration of 0.55 of the span.

The count that does not see it

A frame can have exactly as many unknowns as equations and fold up anyway. The count asks whether there are enough equations; it never asks whether they are different from one another.

equilibrium · Determinacy
The ends decide the length that matters. Four columns of identical height and section, buckling under four sets of end conditions. The effective length factor is the fraction of the column that behaves like a pin-ended one, and the buckling load goes as its inverse square.

The ends decide the length that matters

Four columns of identical height and section, buckling at loads sixteen times apart. Nothing differs but what is holding the two ends.

stability · Effective length
A brace is a stiffness requirement, not a strength one. Critical load against brace stiffness for a pinned column braced at mid-height. The curve climbs from the unbraced Euler load of 9.87EI/L² and flattens at 39.48EI/L², which is the Euler load of the braced segment — past that the column buckles in a shape the brace does not obstruct, and further stiffness buys nothing. The knee is at about 159EI/L³. A stiffness of 60EI/L³ is marked, reaching 21.75EI/L².

The brace that need not be strong

A brace holding a column at mid-height carries almost no force. What it has to be is stiff — and the stiffness required is exact, large, and reached at a knee past which more buys nothing at all.

stability · Effective length
One restraint, and several times the load. The same portal — the same columns, the same beam, the same steel — buckling with its head held against sway and with its head free to sway. The braced frame's critical load is 16.46 EI/L² and the swaying one's is 5.69 EI/L², a factor of 2.89, and the effective length factor that comes out of each eigenvalue is 0.774 against 1.317. Both are eigenvalues of the assembled frame at a beam-to-column stiffness ratio of G = 1.00; the buckled shapes are the mode vectors themselves, drawn at 18 per cent of the storey height so that the movement can be seen.

Held, and not held

One horizontal restraint at the head of a storey, carrying no vertical load whatever, moves the critical load of the columns beneath it by a factor of 2.89. Effective length is a property of the frame, not of the member.

stability · Sway stability
How stiff a brace has to be before the frame stops swaying. The effective length factor of a swaying portal against the stiffness of a horizontal spring at its head. The curve starts at k = 1.317, the unbraced value, and falls to 0.774 — the factor for the same frame with its head held — at a brace stiffness of 23.2 EI/L³. Past that point the frame buckles in the non-sway mode, which the brace does not restrain, and further stiffness buys nothing at all. The threshold is worth stating as 1.41 N꜀ᵣ/L, which is the form the number is memorable in: for a storey carrying a thousand kilonewtons over four metres it is about 0.35 kN per millimetre of sway. Against the frame's own lateral stiffness of 12.0 EI/L³ it is a factor of 1.93.

The most dangerous day is before it is finished

A structure is analysed once, complete, with every restraint present. It spends weeks in states nobody drew — a beam landed with no deck on it holds 17% of the moment its section is worth, a frame not yet braced buckles at a third of the load it will, and a bolt not yet tightened is a pin where the analysis assumed a fixity.

stability · Erection stability
The arch does not squash; it leans. The first two buckling modes of the same rib, drawn against its undeformed shape at an exaggeration of a few hundred. The first, at wcr L³/EI = 49.7, is antisymmetric: one half rises while the other falls and the crown moves sideways. The second, at 117.1, is symmetric — the whole rib settling. The two differ by a factor of 2.36, which is why an arch is braced against sideways movement of its crown rather than against the load it is carrying, and why a tied arch with a single hanger at midspan is doing nothing for the mode that governs it.

The arch that leans instead of squashing

A masonry arch is asked whether a line of thrust fits inside it. A steel rib is asked a different question entirely: it is a column carrying an axial force along its whole length, and the mode it buckles in puts one half up and the other half down while the crown moves sideways.

stability · Arch buckling
A brace on the wrong flange never gets there, however stiff it is. The critical moment of an 8 m beam against the stiffness of a single midspan brace, drawn three times for the three heights the brace could sit at. On the compression flange it climbs from 143 kNm to the two-half-wave plateau of 447 — the beam braced into two 4.0 m beams — and reaches 99% of it at 447 kN/m. At the shear centre it needs 2252 kN/m, 5.0 times as much. On the tension flange it never arrives at all: at the stiffness that would have done the job on the other flange it has bought a factor of 1.068, and a stiffer brace in the same place buys the same nothing. Past the plateau the beam stops using the brace, which is where the idea of an ideal stiffness comes from.

The brace on the wrong flange

A brace on a column has one property that matters, and it is stiffness. A brace on a beam has two, and the second decides whether the first is worth anything: put the identical restraint on the tension flange and it does not reach the answer at any stiffness whatever.

stability · Beam bracing
The restraint chooses the buckling length, and it is not the member's. A compression flange 12 m long held sideways not at points but everywhere, by a restraint of 0.35 N/mm per mm of length. Unrestrained it would buckle at 173 kN in a single half-wave, drawn faintly. Restrained it buckles at 1968 kN — 11.4 times as much — in two half-waves, because the sum n²π²EI/L² + kL²/n²π² has its minimum there and every other n is worse. The effective length that answer implies is 3555 mm, which is 0.30 of the member and is a property of the restraint rather than of the span.

Held everywhere, and it forgets its length

A brace at a point divides a member's buckling length. A restraint spread along the whole member does something else — the member chooses its own number of half-waves, and past a few of them the critical load stops depending on the length at all.

stability · Continuous restraint
The corner columns take what the middle ones did not. Axial stress in the columns across one flange face of a 30 by 40 m framed tube, at the base. Plane sections says the flat line: every column on the face at the same distance from the neutral axis, therefore at the same stress. The solved distribution is the curve — 69.4 N/mm² at the corner against 18.2 in the middle, a ratio of 3.81. The middle columns lag because the only route the axial force has into them is the in-plane shear of the spandrel frame, bay by bay from the corner. The face is carrying its resultant on an effective width of 51 per cent, and the tube deflects as though its second moment were 72 per cent of the gross.

The corner columns take more than their share

A framed tube is a hollow cantilever, and a hollow cantilever's flange ought to be uniformly stressed. It is not, and the reason is that the only route the axial force has into a column in the middle of a face is the in-plane shear of the frame — one bay at a time, from the corner inwards.

structures · Framed tube
Four ways to make a cell resist being racked, and one that is not one. One cell of a grid shell under the membrane shear it has to carry, by the four mechanisms available for carrying it, with the racking each produces over a 30 m span under 1.2 kN/m² of asymmetric load. A serviceability limit of span/250 is 120 mm. Four pin-jointed bars in a quadrilateral have no in-plane shear stiffness whatever — the cell folds, and the answer is not a large deflection but a mechanism. Rigid nodes carry the shear by bending the members over a cell, which smears to 12EI/s³ and comes to 0.35% of what a continuous sheet of the same stretching stiffness gives: 1205 mm, ten times the limit. One diagonal per cell, or a third member direction, carries it axially instead and lands within a factor of two of the sheet. That is the whole difference between a grid shell and a row of arches.

A shell only if the grid takes shear

A curved surface carries load in its own plane at a fraction of the material a flat one needs, and every gridshell ever built is an attempt to buy that with members instead of with a surface. The attempt succeeds or fails on one property nobody draws — whether four bars meeting at a corner can resist being racked — and a pinned quadrilateral grid cannot resist it at all.

structures · Gridshell
The load that makes itself worse. The amplification of a deflection against the ratio of applied load to buckling load. A structure at half its buckling load deflects twice as far as first-order analysis predicts, and the curve runs away well before the load is reached.

The load that is really a lean

No frame is ever plumb. The columns are out of upright by something like a three-hundredth, and every tonne of gravity load standing on that lean has a horizontal component. The force that represents it is not a safety allowance — it is an exact statics substitution for a geometry nobody drew.

equilibrium · Notional load
The length at which a beam stops being a beam. Elastic critical moment against the distance between lateral restraints, with the section's plastic capacity drawn across it. The two cross at 4086 — beyond that length the beam buckles sideways before it reaches the strength its cross-section has, and the capacity is set by the restraints rather than by the steel.

The load that moves with the twist

A beam about to buckle sideways is beginning to rotate, and everything attached to it rotates with it. A load hung from the top flange swings out over the side and drives the rotation on; the same load hung underneath swings back and stops it. Two identical beams, two different capacities, and the only difference is a height.

stability · Load height
A Pratt truss of 8 panels. A Pratt truss under equal panel-point loads. The joint equilibrium equations were assembled and solved; 14 members came out in tension, 13 in compression and 2 carrying nothing.

The tie that spends an afternoon as a strut

A tension member is chosen by its area and nothing else. A compression member is chosen by how that area is arranged. So a member whose force reverses under some load case is not merely being asked for the same number with the other sign — it is being designed against a different variable, and the same steel can carry seventy times more or less depending on a shape nobody chose for that purpose.

stability · Load reversal
The corner columns take what the middle ones did not. Axial stress in the columns across one flange face of a 36 by 36 m framed tube, at the base. Plane sections says the flat line: every column on the face at the same distance from the neutral axis, therefore at the same stress. The solved distribution is the curve — 78.5 N/mm² at the corner against 13.4 in the middle, a ratio of 5.88. The middle columns lag because the only route the axial force has into them is the in-plane shear of the spandrel frame, bay by bay from the corner. The face is carrying its resultant on an effective width of 45 per cent, and the tube deflects as though its second moment were 64 per cent of the gross.

The columns that lean

A framed tube carries its wind load by bending the spandrel beams between its columns, and it does it badly — the corner columns take nearly six times what the middle ones do. Tilt the columns instead, so the perimeter is triangulated, and the same shear is carried axially. The concentration falls to 1.21 and the tube recovers most of the stiffness the plan said it had.

structures · Diagrid
The two braces balance until one of them buckles. An inverted-V brace after the compression member has gone. While both braces are elastic they carry equal and opposite forces and their vertical components cancel on the beam above, which is why the beam in a chevron bay is usually sized for gravity alone. The compression brace buckles at 445 kN and then sheds most of what it was carrying — 30% is left here — while the tension brace goes on to yield at 1065. The difference between the two vertical components is 659 kN, applied at the middle of the span with no help from either brace, and it asks the beam for 1317 kNm against the 200 kNm the gravity load asks for — 6.6 times as much. The beam drawn does not: 1517 kNm against a capacity of 731. The force is not a load case anybody applies; it is what the frame leaves behind on its way to the state it will actually be in.

The force the brace leaves behind

Two braces meeting under a beam carry the storey shear as a tension and a compression whose vertical components cancel, so the beam above sees nothing. They cancel only while both braces are elastic. Once the compression brace buckles it sheds most of its force, the tension brace goes on to yield, and the difference is a point load at midspan that nobody applied.

structures · Chevron brace
Effective length is a property of the storey. The effective length factor of the one column that resists sway, against the total gravity load on the storey as a multiple of its own. At the left-hand end it carries the storey alone and its K is 1.99 — the 2.0 every chart gives a column fixed at the base and free to sway at the top, reproduced here by a route that never mentions a chart. Then columns are added that have pinned bases and therefore no lateral stiffness whatever. They contribute load and nothing else, so they cannot buckle on their own and they lower the load at which everything buckles together. K rises as the square root of the load ratio, exactly, and at the storey drawn — three leaning columns carrying 69% of the gravity load — it is 3.57. That is off the end of every published alignment chart, and the leaning columns themselves, which a designer would take at K = 1.0 for pinned ends, are at 2.54.

The column that leans on its neighbours

A column with a pinned base and a pinned top has no lateral stiffness at all and cannot stand up alone, and yet thousands of them do. What holds them is the rest of the storey, and what it costs is paid by whichever columns do have stiffness — whose effective length rises as the square root of the load being leaned on them, straight off the end of every chart.

stability · Storey buckling
A stiffener is a boundary condition, and it is bought at a threshold. The buckling stress of a 2400 × 12 mm plate with one longitudinal stiffener, against how rigid that stiffener is. Below γ the stiffener rides on the buckle and the plate takes the whole-width mode; at γ the stiffener stays straight and the plate buckles between stiffeners at 74 N/mm², 4.0 times the bare plate's 18.5. Above γ nothing further happens at all, because the sub-panel mode does not know the stiffener is there. The curve is a ramp and then a horizontal line, so a stiffener at twice γ is exactly as good as one at γ. Here γ = 31.5, which asks for an outstand of 144 mm; the 150 mm one drawn gives γ = 35.5, a margin of 1.13.

The rib that is a boundary condition

A rib on a plate is not a member carrying load. It is a line the buckle is not allowed to cross — and it becomes one at a threshold. Below the required rigidity it rides on the buckle and buys a fraction; at the threshold it stays straight and the plate buckles between stiffeners; above it, nothing further happens at all.

stability · Stiffener rigidity
The load being amplified is not the load doing the amplifying. The sway amplifier 1/(1 − ΣP/P_cr) against the storey's total gravity load, as columns are added that carry load and provide no lateral stiffness. The critical load of the storey is fixed at 8203 kN by the bracing that exists, and every leaning column moves the structure along the axis without changing it. At the storey drawn the amplifier is 1.57, so the second-order sway moment is 57% on top of the first-order one — and none of that 70% of the load which is causing it appears in any stability calculation done column by column. The storey stays stable across the whole of this axis. That is the practical reason a gravity-only column is drawn on the frame model rather than designed on its own: it is not being checked, it is being counted.

Counted, not checked

A column with pinned ends and no bracing cannot buckle on its own, so nothing about it fails a stability check. It still carries load, and load with no stiffness attached lowers the buckling load of everything around it — which is why a gravity-only column is put on the frame model and never designed by itself.

stability · Second-order

Twice the moment, four times the brace

A lateral brace has to be on the right flange and its demand is very nearly linear in the load. A torsional brace has no flange to be wrong about, and its demand is exactly quadratic — so the restraint that is indifferent to where it is attached is the one that gets expensive fastest.

stability · Beam bracing

A row of frames is not a foundation

The top chord of a half-through girder is held sideways by U-frames, and the standard calculation smears them into a continuous elastic foundation. That is right while the frames are close and quietly wrong once they are not. The crossover sits at seven-tenths of the buckle's own half-wavelength, whatever the frames' stiffness — and beyond it the chord buckles between frames at a load no stiffening of the frames can raise.

stability · Continuous restraint

What the frames hold is the bow

A row of U-frames is sized for a force, and the rules give that force as a percentage of the compression chord's force that nobody derives. Derived, it is not a property of the frames at all. It is the chord's initial bow, grown by how near the chord works to buckling — and it is least, not greatest, near the stiffness at which the chord stops using the frames. Stiff frames tend to a limit that is π²/500 of the chord force: the familiar two per cent, arriving from a bow of one five-hundredth.

stability · Continuous restraint

The restraint that works where the twist is

A deck fastened along a beam's top flange resists its twist a little everywhere. A secondary beam framing in at mid-span resists it a lot at one point. Given the same total stiffness, the point does better — half the deck's total at mid-span holds the beam as well as the whole deck — because it works where the beam twists most. But a point restraint has a price the deck never charged: it takes the torque through one connection, up to three fifths of the whole applied torque, and if it is stiff it moves the worst twist out to the quarter-points rather than removing it.

deflection · Twist serviceability

The box that is a trough until its deck is cast

A composite tub girder is a box only once its concrete deck has hardened. Before that it is an open steel trough — two leaning webs and a bottom flange — whose shear centre lies seven hundred millimetres below its bottom flange, in the air, and whose resistance to twisting is the thickness of its plates cubed. A light truss across the top is what holds it together while the deck is poured, and it is a plate for shear and nothing else: an angle of ordinary size is worth half a millimetre of steel. That half-millimetre multiplies the trough's torsion constant two thousandfold, and leaves its shear centre almost exactly where it was. The bracing closes the box for twisting; it does not close it for the shear centre.

sections · Shear centre

The frames the deck pushes first

A half-through girder's U-frames are the ends of the cross-girders that carry its deck. Load the deck and every cross-girder sags, its ends rotate, and every frame's foot swings inward by millimetres before the compression chord has asked the frames for anything. It looks like a second imperfection on top of the chord's bow. It is a much weaker one: the frames all move together and the chord simply goes with them, so a 7.5 mm push adds 1.4 kN to frames that the bow loads with 13.6, and stiffer frames make it smaller, not larger. What the push leaves is mostly in the frames' own members, not in what they ask of the chord.

stability · Continuous restraint

Three braces where the moment is

A row of torsional braces is spaced equally because that is how it is drawn, and under a uniform moment equal spacing is very nearly the best there is. Under a moment that peaks at midspan it is not. Moving the outer two of three braces toward the middle cuts the total stiffness a 24 m girder needs by a quarter under a uniform load and a third under a point load, and the bays it leaves at the ends cost nothing, because they carry so little of the moment.

stability · Beam bracing

The braces that stay where the framing puts them

Three cross-frames on a girder usually go where the floor beams or the bridge's bays put them, and cannot be moved toward the moment. They can still be made unequal. Giving the middle one three-fifths of the row's stiffness saves a sixth of the total under a uniform load and more than a quarter under a point load — most of what moving them would save. Moved and graded together, they save no more than moved alone, because both are ways of making every brace twist by the same amount.

stability · Beam bracing

The brace that holds a mode

A shallow arch rising eight radii of gyration turns sideways at a load of 461 when its symmetric snap would not come until 844. A member that only stops the quarter points moving in opposite senses — a brace on the sideways mode, not on any one point — gives the whole difference back once it is 1.75 times as stiff as the rib's own resistance to that mode, and nothing more after that. The stiffness needed grows as the square of the rise. And the brace is not the light member the argument suggests: an arch built a tenth of a radius of gyration out of shape puts an eighth of its whole load through it at the peak.

stability · Snap-through

The braces that have to hold each other

One brace at mid-height must have a stiffness of twice the column's load over the length it halves. Spread the same column over four braces and each one must be stiffer, not softer: 3.62 times the load over its segment, rising towards four with every brace added, because the shape the braces have to stop is a zigzag in which every brace point is pushed by both its neighbours. Braces that tie the column to itself instead of to the ground need one, however many there are. A row with surplus stiffness can carry one brace at two thirds of the ideal, but not one that is missing, and the force each brace has to resist grows with the count.

stability · Effective length

The braces that pull only one way

A brace made of a single tie, or a cross-frame whose diagonals can only pull, resists a girder twisting one way and not the other. A buckling girder has no preference between the two directions, so it takes the one its braces leave free. Three such braces all facing the same way leave a 24 m girder exactly as weak as if they were not there. Facing alternately, they reach 3,087 kN·m at the stiffness that takes two-way braces to 5,627, and no stiffness takes them past 4,063. Opposing the outer pair does not help; one one-way brace anywhere in the row is enough to cap it. Every brace has to resist both ways, and made of ties that costs twice the steel.

stability · Beam bracing

The prop at the crown of the arch

A shallow arch that turns sideways before it snaps can be braced at its quarter points, which holds the sideways mode and carries almost nothing. A single prop at the crown is cheaper and does something else. The crown does not move in the sideways mode, so the prop cannot stop it; it raises the load at which the arch turns aside only by taking part of the load itself. But behind a prop about three times as stiff as the rib's own first mode, the sideways branch stops falling, and the arch no longer snaps at all — at every rise, by the same prop.

stability · Snap-through

The braces with slack in their bolts

A cross-frame bolted into clearance holes resists nothing until the girder it braces has twisted far enough to take up the clearance, and then resists fully. It is a two-way brace that starts late. The girder, erected a little crooked, twists freely into its braces while the load is still small, and from then on the braces hold a girder that is more crooked than the one they were fitted to. The slack acts as an imperfection, and a costly one: each milliradian of it adds more to the middle brace's force than a milliradian of extra crookedness would, and no stiffness takes it back out. On a 24 m plate girder braced at twice the stiffness it needs, three milliradians of slack — a pair of ordinary clearances over its depth — raise the middle brace's force by 70 per cent.

stability · Beam bracing

The floor the columns lean on

A storey of pin-ended columns, every one a little out of plumb, leans on its floor, and the floor leans on a core. Count the floor as rigid and the core needs the sum of the columns' demands. A floor that shears in its own plane is a brace in series with the core, and the far columns lean on it before their push arrives. With a floor a hundred times stiffer per bay than a column's own sway softening, the storey's buckling factor falls from 4.0 to 1.5 and the core is asked for twice as much.

stability · Effective length

Named alongside it

The objects these essays reach for when they reach for this one.

ImperfectionCritical loadEffective lengthStiffnessBucklingLateral-torsional bucklingEigenvalueWarpingSecond-orderBuckled mode shapeLateral systemLoad path

All concepts