Lack of fit — where it appears
Named by 2 essays across 2 fields — each of them below, with the objects they name alongside it.
Built to the wrong length
A redundant structure's members do not have independent lengths. Choose all but one and geometry decides the last, so a member made a different length has to be pulled or pushed into place — and the force required stays in the structure for as long as the structure does. Nothing has been applied to it, there is no load case and no factor, and the members are carrying real force.
The camber that lives in the member lengths
A beam is cambered by bending it; a truss cannot be, because it has no curvature to bend — its shape is nothing but the lengths of its members. So a truss's camber is a cutting list, and each millimetre on that list arrives at mid-span multiplied by the member's force under a unit load there: two and a half for the middle chords of a truss ten times as long as it is deep, nothing at all for some verticals. Build only the chords to their dead-load strain and a quarter of the sag stays, the webs' share. Cut every member to a millimetre of scatter and the mid-span misses by six, an eighth of the camber.
Named alongside it
The objects these essays reach for when they reach for this one.
Bolt holeCamberCompatibilityDead loadErectionFabrication toleranceForce methodImposed deformationIndeterminacyPrestressRelaxationResidual stress