Concept

Anchorage — where it appears

The provision that stops a force pulling out of the material it is delivered into, whether a bar's embedment, a hold-down bolt or a tension pile. Its size is the force divided by whatever stress the surrounding material can pass, and it is often the largest thing a small pressure produces.

Named by 11 essays across 6 fields — each of them below, with the objects they name alongside it.

The coefficient is a slope, and that is why it can exceed one. The crack magnified: two rough faces, drawn as a sawtooth at 54° to the plane. Sliding one over the other cannot happen without lifting it, so a shear displacement forces a separation in fixed proportion — the tangent of that angle, which is the number written down as a coefficient of friction and here is 1.40. The bars crossing the plane are stretched by the separation and clamp the faces back together; they are not carrying the shear, they are supplying the normal force that lets the roughness carry it. A bar that is not anchored on both sides supplies nothing.

Shear across a crack that is already there

Every shear calculation in this collection starts from an uncracked solid — a principal stress, a shear flow, a diagonal tension. This one starts after the crack, on a plane with no tensile strength at all, and the coefficient it uses is not a coefficient of friction. It is the slope of the roughness.

internal-forces · Shear friction
The bond stress is crowded against the loaded end. A 20 mm bar embedded 806 mm, with the force in it and the bond stress on it plotted along the embedment. Uniform bond — the assumption behind every development length ever tabulated — is a flat stress and a straight line of force. An elastic bond of the same peak strength is neither: the slip is largest where the bar is pulled and dies away over 1/α = 471 mm, so the far end of the bar is doing almost nothing. At the design rule's length of 40 diameters the elastic bond is 55 per cent used. The uniform answer is what the bond looks like after it has yielded along the whole length, which is a statement about ductility rather than about strength.

The force that arrives along a length

A bolt takes its force at a hole and a weld along a line. A reinforcing bar has no such place — it is a smooth cylinder in a hole of its own shape, and the only thing stopping it sliding out is a stress smeared over its surface. So the force in it is not a number, it is a function of position.

internal-forces · Bond
Held up by a pressure nobody can feel. An air-supported roof of 60 m span and 9 m rise. The membrane has no bending stiffness whatever, so the only thing that can hold it in tension is a pressure difference, and the pressure has to exceed the load per unit plan area and nothing else: 0.25 kN/m² of fabric plus 0.6 of snow is 0.85 kN/m², so 1.19 kN/m² does it — 1190 pascals, which is 1.17 per cent of an atmosphere and 121 millimetres of water. Ears do not notice it. A door does: at 2.1 kN on an ordinary leaf, the building needs an airlock rather than a handle. And the whole of it arrives at the foundation as 3365 kN of uplift — 17.9 kN on every metre of perimeter — which is the bill the pressure's smallness conceals.

Held up by the air inside

A membrane has no bending stiffness at all, so the only thing that can hold it in tension is a pressure difference. The pressure needed to hold up a roof is smaller than the pressure a closed door makes — and the same pressure arrives at the foundation as hundreds of tonnes of uplift.

structures · Pneumatic structure
Cover enters twice, and the strength of the concrete enters once. How long a 20 mm bar has before the cover over it splits, against the cover, split into the two halves it is always split into. Initiation is the time for the chloride front to reach the bar, which goes as the square of the cover — Fick's law and nothing else — and it is 9.1 years at 35 mm and 36.2 at 70. Propagation is the time from there to a split cover, which is short: 0.9 years, because the cover cracks at a section loss of 0.21% and no strength check in this collection would notice a loss that small. The pressure the cover can take grows with the cover too, so cover appears in both terms and the concrete's own tensile strength appears in one of them, linearly. That asymmetry is why every durability clause in every code is about cover and crack width, and hardly at all about strength.

The load that comes from inside

Every action in this collection has been applied from outside — a weight, a pressure, a movement, a temperature. Corrosion is not applied at all, and the reason it belongs to statics rather than to durability is that what does the damage is a load: rust occupies three times the volume of the steel it came from, and the only place to make room is by pushing the cover apart.

materials · Corrosion
A base plate, and when the bolts start working. A 500 × 500 mm plate carrying 600 kN and 180 kN·m, so the resultant sits 300 mm from the centre against a kern of 83.33 mm. The plate is in bolts engaged: bearing over 150.88 mm at a peak of 20 N/mm², with the holding-down bolts carrying 154.42 kN. The plate lifts at 50 kN·m and crushes at 126 kN·m, and the bolts are not needed until 150 kN·m.

The failure that is in the concrete

An anchor bolt is a steel component and its capacity is usually decided by something else entirely — a cone of concrete pulled out around it, failing in tension, in a material every other calculation on the project has assumed cannot take tension at all. The exponent in the capacity says so: it is not the square the geometry implies.

connections · Anchor breakout
The strength that does not keep pace. Concrete's mean tensile strength against its characteristic compressive strength, with the ratio of the two on the same axis, scaled. The tensile strength goes as f_ck^⅔, so it rises from 1.57 to 5.04 N/mm² over a sixfold rise in the compressive strength, and the ratio between them falls from 11.1% at C20 to 6.0% at C80 — a factor of 1.83. Nothing in a bending or a column calculation ever uses the lower curve, and everything that decides a transition does: when the section cracks, how much minimum steel it needs, how far a bar has to be lapped, what a member without links carries. So a stronger concrete needs more minimum reinforcement, longer laps and a bigger crack-control check, in a member whose ultimate capacity has barely moved. Its real scale is a length: E·G_F/f_ct² is 299 mm here, which is the size at which a member stops behaving plastically and starts behaving like a fracture problem.

The strength that is never used

Concrete's tensile strength appears in no bending calculation, no column calculation and no shear calculation with links in it. The whole design philosophy is that it cracks and the steel takes over. And it decides where nearly every transition in the subject sits — when a section cracks, how much minimum steel it needs, how far a bar has to be lapped, what a member without links can carry, and how wide a crack opens.

materials · Tensile strength
Where a bar may stop, and how far past there it goes anyway. The tension the bottom steel must carry along a 9 m beam, and the resistance of the bars actually present, drawn as a staircase. The demand is the moment diagram divided by the lever arm and then SHIFTED 270 mm toward midspan, because the truss inside the beam delivers its shear diagonally — the two constructions agree to 0.36 per cent, which is the second-order term and nothing else. Each curtailed layer then runs a further 1150 mm to develop, so the outer layer stops at 245 mm rather than the 1665 mm the moment diagram allows. The tail is 1420 mm at each end — 16 per cent of the span — and it is what turns a 20 per cent saving into 2.2.

Where a bar may stop

The moment diagram falls away from midspan, so the steel midspan needs is not needed everywhere, and curtailing it saves real money. Then two things get in the way, and between them they take nine tenths of what the moment diagram promised.

sections · Curtailment
A truss drawn inside a solid, and solved as one. A deep member 5000 mm between bearings and 2500 mm deep, carrying 2400 kN at mid-span. The model is two struts and one tie, on a lever arm of 2000 mm, and it is solved by the truss solver rather than by a formula: the tie comes back at 1500 kN and each strut at 1921 kN, at 38.7° to the horizontal. Spread over a strut width of 1031 mm the compression is 3.7 N/mm² against a limit of 18.1 for concrete cracked across its own strut, and the tie needs 3448 mm² of steel. A beam calculation on the same member would have asked the tie for 1404 kN, which is 7% less than the model does.

The node is the part that is checked

A strut-and-tie model is safe if every part of it can carry what the model asks. The struts are wide and lightly stressed, the ties are steel and easy, and the whole of the difficulty collects at the points where they meet — in a volume of concrete a few hundred millimetres across that no drawing shows.

internal-forces · Strut-and-tie
More steel across the crack, until the roughness runs out. Shear resistance of the interface against the reinforcement crossing it. The steel clamps rather than carries, so the resistance is the clamping stress times the interlock coefficient and rises in a straight line — until the asperities crush at 5.50 N/mm², which happens at a reinforcement ratio of 0.79%. Past that the line is flat and every further bar is decoration. The dashed line is what the clamping alone would give if the concrete were unbreakable.

Two models of one bracket

A corbel can be designed as a plane that has to be clamped or as a truss that has to be drawn, and the two are not approximations of each other. They describe different failures, they ask for steel in different places, and the honest answer is that both are checked because neither bounds the other.

internal-forces · Shear friction
A buckled panel is a truss that nobody drew. A 1500 × 2000 panel of 8 mm web, at d/t = 188. It buckles in shear at 41.0 N/mm², which is 492 kN — and it then carries 1187 kN, 2.41 times as much, because the tension diagonal takes over from the compression one that has gone. The band runs at 18.5° with a membrane stress of 348 N/mm² over a width of 788 mm, and it pulls on the flange at 280.2 N per millimetre of its length. A web that never buckled at all would have reached 2460 kN, so the panel ends at 48% of a stocky web's capacity on a fraction of its steel.

The tension has to pull on something

A buckled web carries its shear on a diagonal band of membrane tension, and the band pulls sideways on the flanges and stiffeners that bound it. That pull is the design output nobody plots — it runs from 72 to 603 newtons per millimetre across ordinary panel proportions, it is largest exactly where the panel is most efficient, and at the end of the girder there is nothing beyond to take it.

stability · Tension field
Two models of one buckled web. The shear resistance of a web 1500 mm deep and 8.0 mm thick in steel of 355 N/mm², as a share of its plastic shear 2,460 kN, against the spacing of its intermediate stiffeners as a multiple of the depth, by Basler's tension field, by the rotated stress field with a rigid end post and with a non-rigid one, and by buckling alone; the dots at the right-hand edge are the same web with no intermediate stiffeners. With stiffeners at the depth Basler gives 0.71 and the rotated field 0.50; at three depths 0.38 and 0.42; with none, 0.14 — buckling alone — and 0.41. The two cross at a spacing of about 2.6 depths. Basler's reserve is a band the stiffeners anchor and it narrows to nothing as they move apart; the rotated field's is spread over the whole web and anchored at its ends, and the spacing reaches it only through the buckling stress.

Two reserves for one buckled web

A slender web keeps carrying shear after it buckles, and design uses two models of how: Basler's band of tension anchored on the stiffeners, and the rotated stress field spread over the whole web and anchored at its ends. Given the same 1,500 × 8 mm panel they agree about the buckling and disagree about everything after it — and in particular about what an intermediate stiffener is for. One says stiffeners save 37 per cent of the steel; the other, 1 per cent.

stability · Tension field

Named alongside it

The objects these essays reach for when they reach for this one.

BondEquilibriumReinforcementStrut-and-tieCrack widthLoad pathShear frictionTensile strengthAggregate interlockCoverDevelopment lengthDuctility