Dynamics

The mass that helps by being late

Hang three per cent of a building's mass from a spring in its roof, tune the spring so the mass arrives a quarter-cycle behind the motion, and the peak response falls by a factor of seven. Nothing was strengthened and nothing was stiffened.

Assumes The only thing that stops it and A structure has more than one period.

The response at resonance is one over twice the damping ratio, and a structure’s damping is a property nobody designed. That leaves two ways out: make the structure so stiff that nothing can excite it, or give it damping it did not have.

The second is far cheaper, and the standard way of doing it is strange enough to be worth the whole essay: hang another mass on another spring, and tune it.

3% of the mass, hung on a spring, against the peak it removesThe magnification of a structure with 1.0% damping, with and without a tuned mass damper of 3.0% of its mass, tuned to 0.9709 of its frequency with 10.5% damping of its own. The bare peak is 50; with the absorber the single peak becomes two of 7.34, a reduction to 15% — a factor of 6.8. The marked points at frequency ratios 0.923 and 1.044 are the fixed points: the response there is the same whatever damping the absorber is given, which is what makes the optimum a question with an answer. The absorber's own stroke at the worse of the two peaks is 29.57 times the structure's static deflection, and that stroke is what decides whether it fits.0.60.70.80.911.11.21.31.41.501020304050forcing frequency ÷ the structure's ownamplitude ÷ static deflectionno absorber — peak 503.0% absorber — peak 7.34a factor of 6.8, for 3.0% of the mass
Fig. 1 A structure with 1% damping and a peak magnification of 50, with and without an absorber weighing 3% of it. The single sharp peak becomes two blunt ones of 7.34 — a factor of 6.8, for 3% of the mass. The two marked points are where every possible absorber damping gives the same answer, and they are what makes the optimum well defined.

Why an added mass does anything

The absorber does not absorb. The name is misleading and it is worth dismantling before the arithmetic.

A tuned mass damper is a second mass on a spring, hung from the structure and free to move relative to it. When the structure moves, the absorber moves too — but not in step. Tuned so that its own natural frequency is near the structure’s, at the frequency that matters it lags by about a quarter of a cycle, and its inertia force acts against the structure’s motion.

So the structure feels a force opposing its movement, supplied by something that is merely hanging there. That force is what reduces the response. The energy then has to go somewhere, and it goes into the absorber’s own dashpot, which is stretching and compressing at the difference between the two motions.

Two consequences follow and both are counter-intuitive.

The absorber has to move a great deal. On the 3% absorber above, the relative stroke at the worse of the two peaks is 29.6 times the structure’s static deflection. The absorber travels much further than the structure does, because it is the relative motion that does the work.

The absorber’s own damping must be moderate. With none at all, the absorber is a perfect vibration neutraliser at exactly one frequency and useless at every other — the two-degree-of-freedom system has two undamped resonances of its own, and the response peaks at 55. With too much, the absorber is effectively clamped to the structure and simply adds to its mass. Between them there is an optimum.

3% of the mass, hung on a spring, against the peak it removesThe magnification of a structure with 1.0% damping, with and without a tuned mass damper of 3.0% of its mass, tuned to 0.9709 of its frequency with 2.0% damping of its own. The bare peak is 50; with the absorber the single peak becomes two of 17.32, a reduction to 35% — a factor of 2.9. The marked points at frequency ratios 0.923 and 1.044 are the fixed points: the response there is the same whatever damping the absorber is given, which is what makes the optimum a question with an answer. The absorber's own stroke at the worse of the two peaks is 92.22 times the structure's static deflection, and that stroke is what decides whether it fits.0.60.70.80.911.11.21.31.41.501020304050forcing frequency ÷ the structure's ownamplitude ÷ static deflectionno absorber — peak 503.0% absorber — peak 17.32a factor of 2.9, for 3.0% of the mass
Fig. 2 The same absorber with 2% damping instead of the optimum 10.5%. Two tall peaks appear where the single one was, at 17.3 — better than the bare structure’s 50 and much worse than the optimum’s 7.3. The absorber is doing its inertia job and not its dissipation job.

The fixed points, which make the problem solvable

Here is the elegant part, and it is why the optimum can be written down rather than searched for.

Sweep the absorber’s damping from zero to enormous and watch the response curve move. Almost everywhere it changes — but there are two frequencies at which it does not. At those two points every possible absorber damping gives exactly the same response, and their positions depend only on the mass ratio and the tuning.

That is Den Hartog’s observation, and it converts the design into a two-step argument.

First, choose the tuning so that the two fixed points are at equal height — which happens at

fopt=11+μf_{\text{opt}} = \frac{1}{1+\mu}

so a 3% absorber is tuned 2.9% below the structure’s own frequency rather than to it.

Second, choose the damping so that the curve peaks at those points rather than between or beyond them:

ζopt=3μ8(1+μ)\zeta_{\text{opt}} = \sqrt{\frac{3\mu}{8(1+\mu)}}

which for 3% is 10.5%. The resulting peak is 1+2/μ\sqrt{1+2/\mu} — 8.23 for a 3% absorber, against the measured 7.34 for a structure that also has 1% damping of its own.

The reason this is worth admiring is that no calculation of the optimum could have been formulated without the fixed points. They are a property of the system that nothing in the design brief mentions, and finding them made a two-parameter optimisation into two one-line formulae.

What the mass ratio buys

1% of the mass, hung on a spring, against the peak it removesThe magnification of a structure with 1.0% damping, with and without a tuned mass damper of 1.0% of its mass, tuned to 0.9901 of its frequency with 6.1% damping of its own. The bare peak is 50; with the absorber the single peak becomes two of 11.56, a reduction to 23% — a factor of 4.3. The marked points at frequency ratios 0.959 and 1.030 are the fixed points: the response there is the same whatever damping the absorber is given, which is what makes the optimum a question with an answer. The absorber's own stroke at the worse of the two peaks is 78.69 times the structure's static deflection, and that stroke is what decides whether it fits.0.60.70.80.911.11.21.31.41.501020304050forcing frequency ÷ the structure's ownamplitude ÷ static deflectionno absorber — peak 501.0% absorber — peak 11.56a factor of 4.3, for 1.0% of the mass
Fig. 3 A 1% absorber: the peak falls from 50 to 11.6, a factor of 4.3. The two peaks are closer together and taller, and the absorber’s stroke is 79 times the structure’s static deflection — nearly three times the stroke of the 3% version, because a lighter absorber has to move further to supply the same inertia force.
10% of the mass, hung on a spring, against the peak it removesThe magnification of a structure with 1.0% damping, with and without a tuned mass damper of 10.0% of its mass, tuned to 0.9091 of its frequency with 18.5% damping of its own. The bare peak is 50; with the absorber the single peak becomes two of 4.34, a reduction to 9% — a factor of 11.5. The marked points at frequency ratios 0.843 and 1.052 are the fixed points: the response there is the same whatever damping the absorber is given, which is what makes the optimum a question with an answer. The absorber's own stroke at the worse of the two peaks is 10.07 times the structure's static deflection, and that stroke is what decides whether it fits.0.60.70.80.911.11.21.31.41.501020304050forcing frequency ÷ the structure's ownamplitude ÷ static deflectionno absorber — peak 5010.0% absorber — peak 4.34a factor of 11.5, for 10.0% of the mass
Fig. 4 A 10% absorber: the peak falls to 4.34, a factor of 11.5. Three times the mass of the 3% version for less than twice the benefit, and it needs a tenth of the building’s mass hanging in the roof.
mass ratio peak response factor gained absorber stroke
none 50.0 1.0
0.5% 15.1 3.3 143
1% 11.6 4.3 79
3% 7.3 6.8 30
5% 5.9 8.5 19
10% 4.3 11.5 10

The returns diminish as 1/μ1/\sqrt{\mu}, which is why real installations cluster between 0.5% and 2% of the modal mass — and why the stroke column matters as much as the response column. A 0.5% absorber gives a factor of 3.3 and needs to travel 143 times the structure’s static deflection, which on a tall building is metres. The mass ratio is chosen by the space available for the absorber to move in, at least as often as by the response required.

Mistuning is the failure mode

What mistuning costs: three absorbers, three tuningsThe same 3.0% absorber on the same structure, tuned to -10%, 0%, 10% either side of the optimum. The peaks are 13.73, 7.34, 14.13. A tenth off tuning gives back a large part of what the absorber bought, which is why a tuned mass damper is commissioned on the finished structure rather than designed from a model — the frequency it has to match is not known accurately enough in advance.0.70.80.911.11.21.31.41.50246810121416forcing frequency ÷ the structure's ownamplitude ÷ static deflection-10% mistuned — peak 13.73tuned exactly — peak 7.3410% mistuned — peak 14.13
Fig. 5 The same 3% absorber tuned 10% low, exactly, and 10% high. The peaks are 13.7, 7.3 and 14.1 — a tenth off tuning gives back more than half of what the absorber bought. The curve is sharp on both sides, which is what “tuned” means and what makes it a liability.

That sensitivity is the reason a tuned mass damper is commissioned rather than designed. The frequency it has to match is the structure’s, and that frequency is not known in advance to better than ten or twenty per cent — the mass depends on occupancy, the stiffness on cracking and on non-structural components, and the end conditions on details nobody drew.

So the practice is: build the structure, measure its frequency, and then tune the absorber to what was measured. Most installations have adjustable stiffness for exactly this, and several have been retuned years later after refurbishment changed the mass.

There is a second consequence, less often stated. A tuned mass damper protects one mode. A structure with two modes close in frequency, or with modes in two directions, needs either a device per mode or an absorber deliberately detuned to cover a band at lower efficiency — which is why a structure’s mode list is the first thing consulted when one is specified.

3% of the mass, hung on a spring, against the peak it removesThe magnification of a structure with 1.0% damping, with and without a tuned mass damper of 3.0% of its mass, tuned to 0.9709 of its frequency with 50.0% damping of its own. The bare peak is 50; with the absorber the single peak becomes two of 20.31, a reduction to 41% — a factor of 2.5. The marked points at frequency ratios 0.923 and 1.044 are the fixed points: the response there is the same whatever damping the absorber is given, which is what makes the optimum a question with an answer. The absorber's own stroke at the worse of the two peaks is 20.6 times the structure's static deflection, and that stroke is what decides whether it fits.0.60.70.80.911.11.21.31.41.501020304050forcing frequency ÷ the structure's ownamplitude ÷ static deflectionno absorber — peak 503.0% absorber — peak 20.31a factor of 2.5, for 3.0% of the mass
Fig. 6 The other side of the optimum: the same 3% absorber with 50% damping. The peak is 20.3, worse than at 2% and four times worse than at the optimum, and the two peaks have merged back into one. An absorber this heavily damped barely moves relative to the structure, so its spring never stretches and its dashpot never dissipates — it has become 3% more building.
How much a harmonic force is magnified, at three damping ratiosDisplacement amplitude divided by the deflection the same force would produce if it were applied slowly, against the ratio of the forcing frequency to the structure's own, at 1%, 2%, 5% of critical damping. At the natural frequency the magnification is 50, 25, 10 respectively — one over twice the damping ratio, and nothing else in the problem enters it.00.20.40.60.811.21.41.61.820510152025forcing frequency ÷ natural frequencyamplitude ÷ static deflection1% damping — 50× at the peak2% damping — 25.01× at the peak5% damping — 10.01× at the peak
Fig. 7 What the same reduction would have cost in structural damping alone. Going from 1% to 5% takes the peak from 50 to 10, which is roughly what a 3% absorber achieves — and there is no way to give a finished building four points of damping by any means other than a device. That equivalence is how absorbers are specified — not as a mass, but as the additional damping ratio they are worth.

What it is used for, and what it is not

The applications are where damping is scarce and the consequence of resonance is discomfort rather than collapse:

Tall buildings under wind, where the resonant part of the response is the part that makes people at the top feel unwell, and where it is inversely proportional to the damping. This is the largest market for the device and the one that produced the enormous pendulums now installed in several very tall towers, hung through four or five storeys and visible to visitors.

Footbridges, both for the vertical bouncing and for the lateral instability — where raising the total damping raises the critical crowd in proportion.

Chimneys and masts, against vortex shedding, where the Scruton number contains the damping linearly and a device weighing a fraction of a per cent can move a structure across the threshold below which the response is negligible.

Long-span floors, where a device of a few hundred kilograms in a ceiling void can fix a response factor that would otherwise need the whole floor redesigned — and where the modal mass is small enough that a useful mass ratio weighs less than the furniture.

What they are not used for is earthquake resistance, and the reason is instructive. An absorber needs several cycles at a steady frequency to develop its relative motion, and a strong-motion record does not offer that: the largest demands arrive in the first few cycles, before the absorber has begun to move. Devices for seismic use are therefore ones that work instantly — dissipating through yielding, friction, or viscous fluid — rather than by tuning.

Where the idea came from

The device is Hermann Frahm’s, patented in 1909 for reducing the rolling of ships — a tank of water arranged so that its own sloshing opposed the roll — and it arrived in structures much later. Den Hartog’s analysis, in Mechanical Vibrations in the 1930s and 40s, is what turned it from a trick into a design procedure by finding the fixed points and the optimum that follows from them.

The route it took is worth a sentence, because it is a common one in this subject. The problem was solved first in a field where the excitation is regular and known — ships, engines, machine tools — and imported into structures once structures became light enough to need it. The same is true of the response spectrum, which came from seismology, and of the gust factor, which came from communications theory.

The variants, and one that has no spring

The physical realisations vary more than the theory does.

A pendulum rather than a spring — a mass hung on cables, whose frequency is set by the length. Simple, adjustable by changing the length, and the standard for very tall buildings, where a pendulum of the required period is naturally several storeys tall.

A liquid column in a U-shaped tank, where the mass is water and the tuning is set by the tank’s geometry. It needs no bearings and cannot seize.

A sloshing tank, where the water’s own surface wave is the tuned mode. The tuning is fixed by the tank’s length and the water depth, and the damping by baffles. A building that needed a water tank anyway can have one that is also a damper, which is the cheapest version of this idea there is.

The last two are worth noticing because they have no moving mechanical parts at all: the absorber is water in a box, tuned by the shape of the box.

40 kN at 1.00 times the natural frequency, on a structure of 5.00 s periodDisplacement against time for a single-degree-of-freedom structure of natural period 5.00 s and 1.0% damping, under 40 kN at 1.00 times the natural frequency. The static deflection under the same peak force is 63.33 mm and the peak response is 3093.25 mm — a factor of 48.85.050100150200250300-3000-2000-1000100020003000time (s)displacement (mm)40 kN at 1.00 times the natural frequencysteady amplitude 3166.29 mmstatic, 63.33 mmpeak 3093.25 mm at 300 s
Fig. 8 Why a transient is a poor customer for an absorber. The bare structure takes about fifty cycles to reach its steady resonant amplitude, and an absorber’s benefit develops over a comparable number — so for a load that lasts three cycles, neither the resonance nor its remedy has begun. Wind and machinery give an absorber the time it needs; a blast, an impact and an earthquake do not.

What the picture cannot show

The curves are steady state. They assume a harmonic force applied indefinitely, which is right for a machine and approximately right for wind. Under a transient — a gust, a bang, an earthquake — the absorber’s benefit is much smaller, because it has not started moving.

The absorber is drawn as free. It has end stops, and a device that hits them stops being tuned and becomes an impact. Sizing the stroke for the design event, and deciding what happens beyond it, is most of the engineering.

Nothing here draws the structure. The absorber’s mass is applied at one point — the roof, usually — and its effectiveness depends on the mode shape at that point. A device at a node of the mode it was meant to damp does nothing at all, which has happened.

The mass ratio is modal, not total. The 3% is three per cent of the effective modal mass of the mode being damped, which for a first mode is around 85% of the building’s mass and for a second mode is a tenth of it. An absorber sized as a percentage of the whole building is oversized for the first mode and hopelessly undersized for the second, and the participation table is where the right denominator is found.

Measured as added damping

The last figure suggests the way absorbers are actually specified, and it is worth making explicit because it connects this rung to every other one in the field.

An absorber’s effect on the peak response can be quoted as the equivalent damping ratio the structure would need to achieve the same peak without one. A 3% absorber that takes the peak from 50 to 7.3 is worth about 5.8 points of damping — a structure at 1% behaving like a structure at 6.8%.

That is a convenient number for two reasons. It goes straight into every other calculation in this field: the resonant part of a wind response, the critical crowd on a footbridge, the Scruton number for a chimney, the response factor for a floor. And it is measurable on the finished structure by exactly the test that measures anything else — displace it, release it, and watch the decay.

The catch is that the equivalence holds at one frequency. A structure with an absorber has a shape of response quite unlike a structure with more damping — two peaks rather than one, and a much narrower band of benefit — so quoting an equivalent damping is a summary rather than a substitution, and it is a summary that is only accurate near the tuning.

Where the ladder goes

Two directions, and they run in opposite senses.

Upward in sophistication: an active system replaces the tuned spring and dashpot with an actuator that pushes the mass wherever a controller says. It is not limited by tuning, can protect several modes, and introduces a failure mode no passive device has — a control system that adds energy at the wrong moment.

Downward in ambition, and closer to home: a tuned mass damper is a second degree of freedom added on purpose, and everything the field says about two-degree-of-freedom systems applies to it. The absorber and the structure are two coupled oscillators, and the two peaks in every figure above are the two modes of the combined system. Nothing new is happening — the system has been given a second mode, arranged so that both of them are worse at resonating than the one it replaced.

That reading is worth keeping, because it is the honest one. A tuned mass damper is not a mysterious device that removes vibration; it is a deliberate second degree of freedom, whose coupling to the first is arranged so that neither can respond strongly on its own. Everything else in this field has been about accepting the modes a structure happens to have. This is the one rung where they are chosen.

What links here

Every essay whose body links to this one.

The objects this essay names

Each one links to every other essay that touches it.

DampingDetuningFixed pointsMass ratioMode shapeResonanceTuned mass damperVibration control