Concept

Mode shape — where it appears

The pattern of relative movement a structure takes when vibrating at one of its natural frequencies, fixed in ratio and arbitrary in size. Modes are orthogonal, so a load that resembles one excites the others hardly at all — which is why where a load is applied decides which mode answers it.

Named by 30 essays across 4 fields — each of them below, with the objects they name alongside it.

Rayleigh's method: the frequency read off the deflection that was computed anyway. A simply supported beam of 8 m, sagging 13.08 mm under its own weight, sampled at 21 stations. Rayleigh's quotient over those deflections gives 4.91 Hz against the exact 4.91 Hz — 0.119% high, and high rather than low because an assumed shape is a constraint and a constraint stiffens. The rule of thumb, 18 divided by the square root of the deflection in millimetres, gives 4.98 Hz.

The period nobody chose

Every structure has a natural period, it decides the answer to every question in this field, and no drawing anywhere records it. It is a consequence of a mass picked for one reason and a stiffness picked for another — and it has already been computed, by the serviceability check.

dynamics · Natural period
Three modes of a five-storey frame. The first three mode shapes of a five-storey shear frame, from the eigenvalue problem rather than sketched. Mode 1 has a period of 0.6 s, no node and carries 88.0% of the mass; Mode 2 has a period of 0.21 s, one node and carries 8.7% of the mass; Mode 3 has a period of 0.13 s, two nodes and carries 2.4% of the mass. The nth mode crosses the axis n−1 times, which is a theorem rather than a drawing convention.

A structure has more than one period

One mass on one spring has one period. A building with eight floors has eight, each with a shape of its own, and the second one bends the building into a curve nobody drew. They are not harmonics, they do not interfere, and each behaves as though the others were not there.

dynamics · Mode shapes
How much of the mass each mode carries, over eight modes. The effective modal mass of each of the eight modes of a frame of eight storeys, as a percentage of the total. Mode 1 carries 85.6% and mode 2 9.1%; two modes are needed to reach 90% of the mass. The masses sum to exactly the total, which is a property of the eigenvectors rather than a normalisation applied afterwards.

Most of the mass moves together

A sixteen-storey frame has sixteen modes, and the first one carries eighty-four per cent of the mass. That is why a hand calculation on one mode gets the base shear right to within a tenth — and why the same calculation gets the acceleration at roof level wrong by a factor of two.

dynamics · Modal mass
3% of the mass, hung on a spring, against the peak it removes. The magnification of a structure with 1.0% damping, with and without a tuned mass damper of 3.0% of its mass, tuned to 0.9709 of its frequency with 10.5% damping of its own. The bare peak is 50; with the absorber the single peak becomes two of 7.34, a reduction to 15% — a factor of 6.8. The marked points at frequency ratios 0.923 and 1.044 are the fixed points: the response there is the same whatever damping the absorber is given, which is what makes the optimum a question with an answer. The absorber's own stroke at the worse of the two peaks is 29.57 times the structure's static deflection, and that stroke is what decides whether it fits.

The mass that helps by being late

Hang three per cent of a building's mass from a spring in its roof, tune the spring so the mass arrives a quarter-cycle behind the motion, and the peak response falls by a factor of seven. Nothing was strengthened and nothing was stiffened.

dynamics · Tuned mass damper
The restraint chooses the buckling length, and it is not the member's. A compression flange 12 m long held sideways not at points but everywhere, by a restraint of 0.35 N/mm per mm of length. Unrestrained it would buckle at 173 kN in a single half-wave, drawn faintly. Restrained it buckles at 1968 kN — 11.4 times as much — in two half-waves, because the sum n²π²EI/L² + kL²/n²π² has its minimum there and every other n is worse. The effective length that answer implies is 3555 mm, which is 0.30 of the member and is a property of the restraint rather than of the span.

Held everywhere, and it forgets its length

A brace at a point divides a member's buckling length. A restraint spread along the whole member does something else — the member chooses its own number of half-waves, and past a few of them the critical load stops depending on the length at all.

stability · Continuous restraint
The worst speed is not the fastest one. Peak deck acceleration against train speed, for a 20 m span at 6.25 Hz under 10 axles 18 m apart. The spikes are not a numerical artefact and they are not about how heavy the axles are: a regularly spaced train is a forcing function with a frequency v/d, and where a multiple of it lands on the bridge's own frequency each coach arrives in step with the motion the last one left. The arithmetic is v = d·f₁/k, which puts peaks at 405, 203, 135, 101 km/h — all of them operating speeds. What fails first is the acceleration rather than any stress: ballast loses its interlock at about 3.5 m/s², and strength does not appear in the equation at all. Here the limit is first passed at 376 km/h.

The train that arrives in time with itself

A single load crossing a span is a mild problem. A train is not one load — its axles are regularly spaced, so the forcing has a frequency of its own, and where a multiple of it lands on the bridge's frequency each coach arrives exactly in step with the motion the last one left behind.

dynamics · Moving load resonance
The demand falls and the movement rises, by the same factor. One elastic spectrum read twice: as an acceleration on the left and as the displacement that goes with it on the right. A fixed-base building at 0.5 s sits on the plateau and is asked for 1.05 g. Put it on bearings soft enough to make its period 2.54 s and the demand falls to 0.103 g — a base shear 10.2 times smaller, bought with no strength whatever. The same shift on the right-hand plot goes the other way: displacement is S_a T²/4π², so the demand rises from 65 mm to 165. That number is the design. It is a gap all the way round the building, a moat every service has to cross, and a detail that a later contractor will fill in unless somebody says what it is for.

Made weaker on purpose

Everything else in this collection resists a load by being stiff or strong enough for it. A base-isolated building resists an earthquake by refusing to hear it — a layer of bearings under the whole structure with a lateral stiffness a twentieth of the frame's, bought with almost no strength at all.

dynamics · Base isolation
The check that everything adds up, and the error it cannot see. Four versions of the same 2-bay, 3-storey frame, with the global equilibrium residual each one produces — the sum of the reactions against the sum of the applied loads, as a fraction of the applied total. It is the first thing every analysis prints and it is worth having: a lost restraint and a load entered in the wrong unit both show up immediately, at 6% and 24%, because both change what the structure is carrying. The fourth bar is the point. A member whose stiffness is wrong by a factor of ten redistributes the internal forces completely — the second bar shows the change in the member forces, 18% — and the global residual is exactly zero, because the wrong answer is still in equilibrium with the same loads. Equilibrium is one equation per degree of freedom of the whole body, and a stiffness error lives entirely in the many equations underneath it. A model can satisfy every equilibrium check ever devised and be a model of a different structure.

The stiffness the load takes away

Buckling is usually taught as an event — a critical load, a bifurcation, a mode. Written as a matrix it stops being an event at all. A compressive load subtracts a stiffness from the structure, the subtraction grows with the load, and the critical load is simply where what is left reaches zero.

stability · Geometric stiffness
A broad tank sloshes and a tall one does not. The liquid's division into the part that moves with the wall and the part that sloshes, against the tank's proportion. The convective masses come from the potential-flow solution and the impulsive mass is whatever is left, so the two sum to the liquid's mass exactly at every proportion rather than approximately over part of the range. A tall tank at H/R = 3 is 84% impulsive and behaves almost like a solid; a shallow one at H/R = 0.5 is 72% convective and most of its contents never notice the earthquake. This tank sits at H/R = 1.33, which is 65% impulsive.

The liquid has a period of its own

Shake a tank and its contents do not all go with it. Part of the liquid moves as though it were bolted to the wall and part sloshes at a period fixed by gravity and the radius, which the tank's stiffness has no influence over whatever. The split is decided by one proportion, and the two parts then take entirely different amounts of the earthquake.

dynamics · Sloshing
Every reason a building is stiffer than its model, added up. The computed natural frequency of a floor, and the same frequency after each source of stiffness that was deliberately left out is put back. Not one of them is a modelling error. Cladding and partitions are stiffness nobody is allowed to rely on for strength; a nominally pinned connection is never pinned; a slab acts with its beam whether or not shear connectors were provided; and concrete between the cracks is stiffer than a cracked section assumes. Together they multiply the stiffness by 1.83 and the frequency by 1.35, because a frequency is the square root of a stiffness, and every factor is halved on the way through. The asymmetry is the finding: leaving stiffness out makes a deflection conservative and a vibration check unconservative in the direction that matters, since a stiffer floor has a higher frequency and sits further from the footfall range. The model here reads 4.40 Hz against a 5.2 Hz criterion and fails it; the floor reads 5.95 Hz and passes. The correction that would have got it right is exactly the stiffness nobody is willing to count on.

Stiffer than the model said

Measured natural frequencies of finished buildings come out between ten and sixty per cent above the values computed for them, consistently and in one direction only. Nothing on the list of reasons is a modelling error: every one is a real source of stiffness deliberately left out — and leaving stiffness out is conservative for deflection and unconservative for vibration.

deflection · Measured stiffness
The average is not the answer, and it is unsafe. Critical load of a pinned column whose middle third has been given a different stiffness, against the whole-column Euler load, with the two numbers a hand check reaches for beside it. The eigenvalue is taken from K − P·Kg over 24 elements, so nothing here is a formula for a stepped column — it is the same computation the uniform case gets. At a middle third of 0.50 times the rest the true load is 0.612 of Euler's, the arithmetic average says 0.832 and the weakest segment says 0.496. The average is high by 36% and it is high on the unsafe side, because the third of the column it is averaging over is the third where the mode has all its curvature. The weakest-segment answer is safe everywhere and wasteful by about as much.

An average stiffness is not a safe stiffness

Euler's load belongs to a column of one EI. Give the same column two, and the temptation is to average them — which is wrong, and wrong in the unsafe direction by a quarter. Buckling weights stiffness by the square of the curvature of the mode, so the middle of a pinned column decides everything and the ends decide almost nothing.

stability · Stepped column
The ground is a structure, and it has a period. The transfer function of 38 m of soil at 75 m/s over bedrock at 800 m/s: how much the surface moves for a given motion in the rock, at every frequency. It is a column fixed at the bottom and free at the top, so its resonances are the odd harmonics — the peaks stand at 1, 3, 5, 7 times the first, which is a fixed-free column and nothing else. The fundamental is at 0.493 Hz, a period of 2.03 s, and it is 4H/v_s exactly. The peak amplification is 7.5 against the bound 1/(α + πξ/2) = 7.5, which agrees to 0.2% — and the α in it is the impedance ratio, 0.0554 here. That is the term that keeps the answer finite: assume rigid bedrock and α is zero, the bound becomes 13 and the model is predicting an amplification set by damping alone. What limits the surface motion is that the energy can leave downward.

The ground has a period of its own

An earthquake is measured on rock and felt on soil, and between the two is a layer that behaves exactly like a structure — a column fixed at bedrock, free at the surface, with a fundamental period of four times its depth over its shear wave velocity and a set of odd harmonics above it. The motion a building receives is the rock motion through that filter, and the filter is sharp.

dynamics · Site response
Evenly spaced modes, so one of them is always where the feet are. The first 6 modes of a 120 m stay under 3.50 MN. A taut string's frequencies are an arithmetic progression — every one of them 1.006 Hz above the last — where a beam's go as the square of the mode number and spread out. That difference is the whole of why a cable is a lively member and a beam is not: a beam has a first mode and then a gap, and a cable has a mode every 1.01 Hz for ever. The shaded band is ordinary walking, 1.6 to 2.4 Hz, and mode 2 sits inside it. Nothing about the tension can move a mode out of the band without moving another one in.

The force read off a frequency

Nothing can measure the tension in a stay cable directly — there is no gauge, no accessible end and no place to put a load cell. What there is, is a member whose frequencies are an arithmetic progression whose spacing is the square root of its own tension, so a phone taped to it for thirty seconds returns the force.

dynamics · Cable dynamics
Where the drift went. Storey drift at the target displacement, for the same frame with and without a soft ground storey at 50 per cent of the others' stiffness and strength. The regular frame spreads 219 mm over every storey; the soft one reaches 266 mm and puts 5.58 per cent of it into the ground storey against 0.53 next to it — a concentration of 5.9 against 1.7. The roof goes 22 per cent further, and where that extra displacement lands is the whole of the difference between the two buildings.

Weaker in one place, and better on every average

Take an eight-storey frame and make its ground storey half as stiff and half as strong. Its ductility demand falls, its first mode carries more of the mass, and its period lengthens into a gentler part of the spectrum. Three global numbers all improve, and the building is the one that collapses.

dynamics · Pushover
The same chord, buckling under a constant force and under a varying one. Two buckled shapes of the same 40 m compression chord on the same continuous restraint of 0.35 N/mm per mm, at the same scale. Under a constant force the buckle fills the member — 8 half-waves over 98 per cent of the length — and the critical force is 1881 kN, which is the length-free answer the closed form gives. Under the parabolic force a uniformly loaded deck delivers to it, the buckle LOCALISES: 5 half-waves over 56 per cent of it, gathered where the force is largest, and the peak force at buckling is 2113 kN. The shaded curve is the force distribution the second shape is buckling under.

The buckle that will not spread out

A compression chord on a continuous restraint chooses its own number of half-waves and forgets how long it is. Give it the force it actually carries — a parabola, largest at midspan — and the number barely moves while the shape changes completely, which is the half that decides where the restraint has to be.

stability · Continuous restraint
What a damper at the anchorage can do, and the ceiling it cannot pass. Modal damping against damper size for a 200 m stay at 4500 kN, with the damper 4 m from the anchorage — 2.0 per cent of the length. Each curve is a mode, found as a complex root of the taut string with a viscous damper in it rather than from a formula. Every one of them peaks at 1.00 per cent of critical, which is x/2L exactly, and the peaks are at different damper sizes — a higher mode wants a smaller damper, because it moves faster at the same amplitude. The curves are flat near their peaks: half the optimum coefficient gives 80 per cent of the ceiling, and so does twice it.

The damper that is too near the end

A stay cable has almost no damping of its own, so it is given a damper — and the damper cannot go where the motion is, because the middle of a two-hundred-metre stay is a hundred metres above the road. What it can supply is then decided by one length, and no amount of damper changes it.

dynamics · Cable dynamics
Where two buildings touch, and what is there when they do. Closure between an 8-storey building 24 m tall and a 4-storey one 15 m tall, drawn against height, with the 50 mm gap between them. The two swaying out of phase close on each other more the higher up they are, so they first touch at 7.6 m and are in contact above it. The dots are the taller building's floors: its storeys are 3.00 m and the other's are 3.75, so two of them arrive part way up a column rather than at a slab. A blow at mid-height of a column asks it for a shear of half the impact and an end moment of Fh/8, neither of which is a demand any part of the design contains.

The floor that arrives at a column

The gap between two buildings is computed from their roof displacements, which is where each of them moves most. It is not where they touch, and it is not what is there when they do — a slab edge meeting a column part way up its height is a different event from two slabs meeting, and it is the one that appears in the photographs.

dynamics · Pounding
Three quantities converging at three different rates. How much of the exact answer a truncated modal analysis of a ten-storey building reaches, against how many modes it keeps. The mass count is the rule — ninety per cent, reached at two modes. The base shear is ahead of it: one mode carries 85 per cent of the mass and 98 per cent of the base shear. The force in the top storey is behind it, at 80 per cent on one mode and 94 on two. The rule is written in the quantity that converges fastest, and it is checked against a quantity nobody plots.

The modes that were left out

Nobody runs every mode a model has, and the rule for how many is a mass count — enough to account for ninety per cent of the structure. The rule is written in the one quantity that converges fastest. On a twenty-storey frame two modes give the base shear to within one per cent and the force in the top storey to within twenty.

dynamics · Mode shapes

The pattern that stopped describing the building

A pushover analysis pushes with a load pattern chosen to resemble the first mode, and by the time the structure has done anything worth analysing it no longer has that mode. Recomputing the pattern as the frame softens changes the base shear by nine per cent and the drift at the fourth floor by a factor of four.

dynamics · Pushover

The line of ties that stops short

Cross-ties are the one intervention on a stay cable that changes its frequencies rather than damping them, and the usual account says they lift the stays out of the range that excites them. A line of ties that is not anchored to anything cannot lift the first frequency above the shortest stay's own, however stiff the ties are made. What lifts it is carrying the line to the deck.

dynamics · Cable dynamics

The damper that ends up as a joint

A damper across the gap between two buildings acts on exactly the motion the gap is sized for, and it can be sized for two different things. The size that takes the most energy out of the pair still lets the buildings collide. The size that keeps them apart has nearly stopped moving: it has joined them into one building, and the stiffer of the two pays for it in drift.

dynamics · Pounding

The twist the combination rule invents

Two modes close together respond together, and the square root of the sum of squares assumes they do not. The error has the sign of the two modal contributions: where they agree, as they do in base shear, the rule comes up short, and where they oppose, as they always do in torque, it comes up long — by a factor of five for a floor whose stiffness sits twenty centimetres off its mass, a torque the building does not have.

dynamics · Mode shapes

The damping that belongs to no mode

Give every mode its own damping ratio and throw the rest of the damping matrix away, and an isolated building's periods and damping come out right to within a fifth of a per cent. Its storey drift at the superstructure's frequency comes out six times too small. The bearings' dashpot pushes on both modes at once, and the more of it there is the less extra damping buys: the classical analysis promises the drift keeps falling, and it stops.

dynamics · Mode shapes

The top floor the bearings shake

On a building of several storeys, the damping at the isolation bearings is tied less tightly to each higher structural mode than to the one below. It still does more harm in each, because the ground barely reaches those modes on its own. The error the usual analysis throws away gathers in the upper storeys, and past about a third of critical damping at the bearings the roof shakes harder while the analysis says it is still helping. How much damping is best depends on how tall the building is.

dynamics · Mode shapes

Two modes that are really a plane

A building equally stiff in both directions has two translational modes with one period, and they are not a pair of shapes but a whole plane of them. The pair an analysis returns is chosen by asymmetries of a millionth, so any result that depends on the pair — a square-root combination, a comparison with measured modes — inherits a choice the building never made. Damping then decides whether the difference can be seen at all.

dynamics · Mode shapes

What a mode shape notices that a frequency does not

Take a tenth of the stiffness out of one storey of a ten-storey building and its first frequency falls by a per cent at most, and by almost nothing if the storey is near the top. The mode shape looks unchanged, its match to the old one 0.99997. But the mode's storey drift — its curvature — rises by about a tenth in the damaged storey and hardly anywhere else, wherever that storey is. The instrument that sees the damage is the one almost nobody installs.

dynamics · Mode shapes

The modes at zero frequency

A structure held by nothing — a span being launched, a segment on a crane, a pontoon — has a mode in which it moves as one body and stretches nothing, at a frequency of exactly zero. That is a real mode, not a glitch in the stiffness matrix. It carries every kilogram of the structure under a uniform acceleration and leaves the flexible modes none at all. A load that is not uniform is a different matter: pushed suddenly from one end, the structure has no static answer to give, only an acceleration with a vibration riding on it.

dynamics · Mode shapes

The pad that makes the blow worse

A forge hammer's anvil sits on a pad on its foundation block, and the pad looks like isolation: a spring between the blow and everything below it. For the block it is the opposite. Every pad an anvil can sit on makes the block move more than a rigid seat would, by half again when the pad is tuned near the foundation, and what the pad buys instead is a smaller force under the anvil. The hope that a tuned pad could act as a tuned mass works only against a train of blows, and only at a softness the anvil cannot live with.

dynamics · Vibration isolation

The pipe held at every floor

A riser runs the height of a building and is fixed at every floor, so each of its supports moves with a different floor. The floor spectrum prices the pipe's inertia, and for a pipe anchored at every floor the inertia is nearly irrelevant: the drift puts 131 N/mm² into a 100 mm riser at two thirds of a per cent, thirty times its inertia, and passes yield at 200 mm. Guide the same pipe instead of anchoring it and the drift almost vanishes — the pipe then feels only how much the drift changes from one storey to the next.

dynamics · Floor spectrum

The factor of two belongs to one mode

A member that fails suddenly hands its force to the structure around it all at once, and the convention is to double the static answer: a load applied suddenly to a spring overshoots to twice its static deflection. A truss is not one spring. Take a diagonal out of a counter-braced truss in an instant and some members swing to three times their change of force, one swings the wrong way first, and a bottom chord whose force does not change at all passes through half as much again as it carries — because every mode overshoots by two, at its own time, and a member is a sum of modes.

structures · Robustness

Named alongside it

The objects these essays reach for when they reach for this one.

DampingEigenvalueNatural periodModal analysisModal massResonanceResponse spectrumDegrees of freedomOrthogonalityServiceabilitySoft storeyBase isolation

All concepts