Dynamics
Twice the deflection, for the same load
A weight placed gently on a beam deflects it by one amount. The same weight let go from rest, a millimetre above the same beam, deflects it by twice as much — and the factor of two is exact, for every structure ever built.
The period nobody chose
Every structure has a natural period, it decides the answer to every question in this field, and no drawing anywhere records it. It is a consequence of a mass picked for one reason and a stiffness picked for another — and it has already been computed, by the serviceability check.
The only thing that stops it
Drive a structure at its own frequency and the amplitude grows without limit unless something takes energy out. What takes it out is damping, and damping is the one structural property that is never designed, never drawn, and never known until the thing is built.
A structure has more than one period
One mass on one spring has one period. A building with eight floors has eight, each with a shape of its own, and the second one bends the building into a curve nobody drew. They are not harmonics, they do not interfere, and each behaves as though the others were not there.
Most of the mass moves together
A sixteen-storey frame has sixteen modes, and the first one carries eighty-four per cent of the mass. That is why a hand calculation on one mode gets the base shear right to within a tenth — and why the same calculation gets the acceleration at roof level wrong by a factor of two.
The floor that is strong and unusable
A floor can satisfy every strength check, deflect less than the limit, and still be rejected by the people who work on it — because somebody walking across it at two steps a second happens to be exciting it at exactly the rate it likes to move.
The spectrum is not a load
A response spectrum looks like a load curve and is not one. Every point on it is the peak of a complete time integration of one particular structure, and the curve is what you get by doing that again for every structure there could be.
The earthquake asks for a displacement
A structure a quarter as strong as the elastic demand does not deflect four times as far. It deflects almost exactly as far, yields on the way, and survives — which is why no ordinary building is designed for the force an earthquake would apply if it stayed elastic.
The wind is a spectrum
A wind load is quoted as a pressure, which suggests something steady. It is not — the energy is spread across four decades of frequency, almost all of it in gusts lasting minutes, and a tall building takes ninety per cent of its response from the sliver of that energy sitting at its own frequency.
The wind that brings its own frequency
Every other load in this subject arrives at whatever rate it happens to arrive at. Vortex shedding arrives at a rate set by the wind speed — so for any chimney, mast or cable there is always a wind speed at which the shedding matches the structure exactly, and it is a breeze rather than a storm.
The bridge that was pushed by its own sway
A crowd walking on a bridge that moves sideways adjusts its footing to stay balanced, and the adjustment pushes the bridge the way it is already going. The crowd is a damper with the sign reversed, and past a certain number of people the total damping is negative.
The mass that helps by being late
Hang three per cent of a building's mass from a spring in its roof, tune the spring so the mass arrives a quarter-cycle behind the motion, and the peak response falls by a factor of seven. Nothing was strengthened and nothing was stiffened.
The weight that was dropped
A half-tonne load lowered onto a beam produces 5 kN. The same load dropped one metre onto the same beam produces 160 kN — and onto a beam ten times softer, 54 kN. The stiff structure is the one that suffers, which is the opposite of nearly every other rule about structures.
The machine that shakes the building
Put a machine on springs to keep its vibration out of the floor, and below a frequency ratio of root two the springs make things worse. Every transmissibility curve ever drawn passes through exactly one at that ratio, whatever the damping — so a soft mount either works well or fails badly, with nothing in between.
The motion that feeds itself
A steady wind contains no frequency at all, and it can destroy a bridge. The force that does it is manufactured by the structure's own movement, so there is no excitation to resonate with — there is a wind speed above which the equilibrium is unstable, and below which nothing happens.
The train that arrives in time with itself
A single load crossing a span is a mild problem. A train is not one load — its axles are regularly spaced, so the forcing has a frequency of its own, and where a multiple of it lands on the bridge's frequency each coach arrives exactly in step with the motion the last one left behind.
Made weaker on purpose
Everything else in this collection resists a load by being stiff or strong enough for it. A base-isolated building resists an earthquake by refusing to hear it — a layer of bearings under the whole structure with a lateral stiffness a twentieth of the frame's, bought with almost no strength at all.
The ground is a spring
Every dynamic result in this collection has assumed a structure rising from something that does not move. Nothing does. A foundation can slide and it can rock, both are flexibilities in series with the structure's own, and the rocking one carries a square of the height — so the period lengthens, the force falls, the drift rises, and the damping goes the wrong way.
The load that is over before it has moved
A blast delivers an enormous pressure for a few milliseconds. Everything else in this field asks what force a structure can carry; a load that has come and gone before the structure has travelled any distance is not asking that question, and the answer turns out to depend on the mass and the ductility with the strength barely in it.
The liquid has a period of its own
Shake a tank and its contents do not all go with it. Part of the liquid moves as though it were bolted to the wall and part sloshes at a period fixed by gravity and the radius, which the tank's stiffness has no influence over whatever. The split is decided by one proportion, and the two parts then take entirely different amounts of the earthquake.
The block that is safer for being bigger
A block resting on the ground lifts off at an acceleration that depends only on its shape and not at all on its size, and then falls over at one that depends strongly on its size. Two objects of identical proportion begin rocking at the same instant and only the smaller one topples — which is why the slender water towers stood in Chile and the squat tanks beside them did not.
The ground has a period of its own
An earthquake is measured on rock and felt on soil, and between the two is a layer that behaves exactly like a structure — a column fixed at bedrock, free at the surface, with a fundamental period of four times its depth over its shear wave velocity and a set of odd harmonics above it. The motion a building receives is the rock motion through that filter, and the filter is sharp.
The resonance that ran out of time
A resonance amplifies by one over twice the damping, which for a lightly damped structure is fifty or a hundred. That is a steady-state answer and it takes time to arrive — with a time constant containing the same small damping — so nothing that sweeps through a resonance ever collects all of it, and past a certain rate the peak reached stops depending on the damping at all.
The gap between two buildings
Two towers side by side in an earthquake need a gap. The obvious answer is the sum of what each can move, and it is wrong — because the two peaks do not happen at the same instant. What decides the answer is the ratio of the two periods, and buildings that sway alike need almost no gap at all.
The force read off a frequency
Nothing can measure the tension in a stay cable directly — there is no gauge, no accessible end and no place to put a load cell. What there is, is a member whose frequencies are an arithmetic progression whose spacing is the square root of its own tension, so a phone taped to it for thirty seconds returns the force.
Pushed over until it will not stand
A structure in an earthquake is asked for a displacement rather than a force. A pushover answers a different question cheaply — how much base shear the frame has against how far its roof moves — and the whole art is in what happens when the two are laid over each other.
The brace that yields both ways
An ordinary diagonal yields in tension at its full strength and buckles in compression at half of it, and the buckle leaves a hinge that does not straighten. Stop it buckling with a sleeve that carries no load at all and the loop becomes symmetric.
The spectrum a floor hands on
Most of what breaks in an earthquake is not the structure. It is a transformer, a chiller, a rack, a ceiling, a pipe — and every one of them is bolted to a floor rather than to the ground. The motion it feels has already been through a filter with one very sharp tooth in it.
Weaker in one place, and better on every average
Take an eight-storey frame and make its ground storey half as stiff and half as strong. Its ductility demand falls, its first mode carries more of the mass, and its period lengthens into a gentler part of the spectrum. Three global numbers all improve, and the building is the one that collapses.
The only damping is the landing
A rocking block has no dashpot in it. The only energy it ever loses is lost at the instant it lands on its other corner, and how much is a property of the block's proportions — 14 per cent for a slender one and 38 for a stocky one. That single number decides whether it settles or goes over, and a real base does not deliver the value the theory computes.
The damper that is too near the end
A stay cable has almost no damping of its own, so it is given a damper — and the damper cannot go where the motion is, because the middle of a two-hundred-metre stay is a hundred metres above the road. What it can supply is then decided by one length, and no amount of damper changes it.
The damping that is radiated
Every response in this field is quoted with a damping assumption attached, because damping is measured rather than designed and the measurement has a factor of two in it. A machine block on the ground is the exception: its damping is not dissipation at all, and it can be computed from three numbers none of which is a material property of anything that dissipates.
The floor that arrives at a column
The gap between two buildings is computed from their roof displacements, which is where each of them moves most. It is not where they touch, and it is not what is there when they do — a slab edge meeting a column part way up its height is a different event from two slabs meeting, and it is the one that appears in the photographs.
The modes that were left out
Nobody runs every mode a model has, and the rule for how many is a mass count — enough to account for ninety per cent of the structure. The rule is written in the one quantity that converges fastest. On a twenty-storey frame two modes give the base shear to within one per cent and the force in the top storey to within twenty.
The pattern that stopped describing the building
A pushover analysis pushes with a load pattern chosen to resemble the first mode, and by the time the structure has done anything worth analysing it no longer has that mode. Recomputing the pattern as the frame softens changes the base shear by nine per cent and the drift at the fourth floor by a factor of four.
A wall that is allowed to lift
A block that rocks inherits everything that decides whether it survives — a restoring moment set by its weight and shape that falls as it leans, and a loss of energy set by its proportions at each landing. Put a tendon through a wall and yielding bars across its base and both become design quantities, and the ratio between them decides whether the wall comes home.
The frequency below both checks
A machine block is checked for sway and for rocking as if they were two oscillators, each with its own spring, its own radiation damping and its own natural frequency. A block whose mass sits above its base is one oscillator with two modes, and neither of them is a sway or a rocking — one sits below both checks, one above both, and the lower one is where the machine resonates.
The line of ties that stops short
Cross-ties are the one intervention on a stay cable that changes its frequencies rather than damping them, and the usual account says they lift the stays out of the range that excites them. A line of ties that is not anchored to anything cannot lift the first frequency above the shortest stay's own, however stiff the ties are made. What lifts it is carrying the line to the deck.
The force that belongs to the model
When two buildings meet, momentum decides what each of them feels, and no contact law can change it. What the contact law decides is the force, and the force it reports is the contact stiffness somebody assumed, raised to a power. Four laws and a hundredfold change of stiffness move the buildings by a few per cent and the force by a factor of eight.
The crowd that is also the structure
A crowd jumping to music loads a grandstand with harmonics several times those of walking, and nothing about their size is measured: they follow from a pulse that has to average one body weight. But the people who jump arrive with the people who sit, and the seated crowd is mass, stiffness and damping bolted to the stand. It lowers the worst case by a factor of five and makes the most common jumping rates worse.
The stay shaken along its own length
A deck that moves at a stay's anchorage pushes nothing across the stay. It stretches the stay along its own line and lets it go again, so the tension swings, and at twice the stay's frequency that swing drives the stay with no sideways force at all. Whether the swing grows is one comparison — a quarter of the tension swing against the damping ratio — and it is a comparison the capped damper wins.
The damper that ends up as a joint
A damper across the gap between two buildings acts on exactly the motion the gap is sized for, and it can be sized for two different things. The size that takes the most energy out of the pair still lets the buildings collide. The size that keeps them apart has nearly stopped moving: it has joined them into one building, and the stiffer of the two pays for it in drift.
The force a filler can promise
A crushable filler in the gap between two buildings replaces a contact stiffness nobody knows with a crush strength somebody chose, and the force of a collision becomes that strength — for as long as the filler has thickness left to crush. Energy decides how much thickness that has to be, and in a gap sized for buildings that were never meant to meet it is not much.
The tendon that forgets its prestress
A rocking wall comes home because a tendon pulls it, and the tendon must not yield — yet the rotations that test the wall are exactly the ones that stretch it. Past its yield, the force a tendon keeps is its yield force less its stiffness times the stretch, whatever it was prestressed to, so the guarantee a design needs is a limit on rotation, and more prestress only reaches that limit sooner.
The damping that comes through the sides
A machine block set into the ground is held at its sides as well as its base, and the side soil does two things at once. It lifts the height at which the ground's resistance acts toward the block's centre of mass, which weakens the coupling between sway and rocking without ever removing it. And it radiates, which is what actually flattens the resonance — so the quiet an embedded block promises rests on the stiffness of backfill nobody measured.
The twist the combination rule invents
Two modes close together respond together, and the square root of the sum of squares assumes they do not. The error has the sign of the two modal contributions: where they agree, as they do in base shear, the rule comes up short, and where they oppose, as they always do in torque, it comes up long — by a factor of five for a floor whose stiffness sits twenty centimetres off its mass, a torque the building does not have.
The damping that belongs to no mode
Give every mode its own damping ratio and throw the rest of the damping matrix away, and an isolated building's periods and damping come out right to within a fifth of a per cent. Its storey drift at the superstructure's frequency comes out six times too small. The bearings' dashpot pushes on both modes at once, and the more of it there is the less extra damping buys: the classical analysis promises the drift keeps falling, and it stops.
The top floor the bearings shake
On a building of several storeys, the damping at the isolation bearings is tied less tightly to each higher structural mode than to the one below. It still does more harm in each, because the ground barely reaches those modes on its own. The error the usual analysis throws away gathers in the upper storeys, and past about a third of critical damping at the bearings the roof shakes harder while the analysis says it is still helping. How much damping is best depends on how tall the building is.
Two modes that are really a plane
A building equally stiff in both directions has two translational modes with one period, and they are not a pair of shapes but a whole plane of them. The pair an analysis returns is chosen by asymmetries of a millionth, so any result that depends on the pair — a square-root combination, a comparison with measured modes — inherits a choice the building never made. Damping then decides whether the difference can be seen at all.
What a mode shape notices that a frequency does not
Take a tenth of the stiffness out of one storey of a ten-storey building and its first frequency falls by a per cent at most, and by almost nothing if the storey is near the top. The mode shape looks unchanged, its match to the old one 0.99997. But the mode's storey drift — its curvature — rises by about a tenth in the damaged storey and hardly anywhere else, wherever that storey is. The instrument that sees the damage is the one almost nobody installs.
The modes at zero frequency
A structure held by nothing — a span being launched, a segment on a crane, a pontoon — has a mode in which it moves as one body and stretches nothing, at a frequency of exactly zero. That is a real mode, not a glitch in the stiffness matrix. It carries every kilogram of the structure under a uniform acceleration and leaves the flexible modes none at all. A load that is not uniform is a different matter: pushed suddenly from one end, the structure has no static answer to give, only an acceleration with a vibration riding on it.
The rock that sends the waves back
A machine block on the ground is damped by the waves it launches, and a half-space lets them all escape. Put rock four and a half metres down and none of them can: below the soil layer's own lowest frequency there is no wave that travels, and a vertical mode damped at 47 per cent of critical keeps the soil's own 5. Its resonance grows fivefold, and the heavy block the textbook rule recommends is the one that loses its damping on the deepest ground.
The blow that has no frequency
A forge hammer does not shake its foundation; it strikes it. The transmissibility curve every isolation design is drawn on has nothing to say about a blow, and the rules it teaches mislead. The force a struck block passes to the ground is least at a quarter of critical damping, not the most; five per cent and forty-seven pass almost the same; and the springs that soften every blow can bring the block down to the hammer's own rate and make a train of blows ring four times as high as one.
The pad that makes the blow worse
A forge hammer's anvil sits on a pad on its foundation block, and the pad looks like isolation: a spring between the blow and everything below it. For the block it is the opposite. Every pad an anvil can sit on makes the block move more than a rigid seat would, by half again when the pad is tuned near the foundation, and what the pad buys instead is a smaller force under the anvil. The hope that a tuned pad could act as a tuned mass works only against a train of blows, and only at a softness the anvil cannot live with.
The actuator that arrives late
A tuned mass damps a structure because its force arrives a quarter of a cycle behind the motion. Replace the mass with an actuator told to push against the structure's velocity, and the same quarter-cycle is fatal: the push that was damping becomes stiffness, the stiffness becomes a source of energy, and a gain that would have cut the response tenfold makes the structure vibrate by itself. The delay is a few hundredths of a second, which is nothing to a tower and everything to a floor.
The pipe held at every floor
A riser runs the height of a building and is fixed at every floor, so each of its supports moves with a different floor. The floor spectrum prices the pipe's inertia, and for a pipe anchored at every floor the inertia is nearly irrelevant: the drift puts 131 N/mm² into a 100 mm riser at two thirds of a per cent, thirty times its inertia, and passes yield at 200 mm. Guide the same pipe instead of anchoring it and the drift almost vanishes — the pipe then feels only how much the drift changes from one storey to the next.
The actuator that pushes against the mass
An actuator that damps a structure by feeding back its velocity has to push against something. Against the ground, it is stable up to large gains until a delay of a quarter period removes its damping. Against a tuned mass — the arrangement meant to keep a passive damper underneath — the same feedback goes unstable at a gain of a per cent and a half with no delay at all, makes the structure worse than the passive mass at every gain below that, and drives the mass three or four times as far. What limits it is not when it acts but what it pushes against.
The breeze that uses up a chimney
A chimney that locks in to vortex shedding at a breeze is usually told to accept the motion and check its fatigue. Counting the cycles a real wind climate delivers turns that into arithmetic, and the arithmetic has two surprises. The chimney that collects the most cycles is not the one tuned to the commonest wind but to one a fifth stronger than the climate's scale, so stiffening a chimney can shorten its life. And damping does not lengthen the life in proportion: it ends the count, all at once, at the damping that puts the largest stress range under the detail's cut-off.
The same weight, dropped again
A structure allowed to yield under a falling weight needs only a fraction of the strength an elastic one needs — half of it for a ductility of two and a half — because the energy goes into bending the steel rather than into force. That is the whole saving, and it is spent on the first drop. Drop the same weight again and the structure yields again: a perfectly plastic one adds the same permanent set every time and never stops, and a hardening one stops only when it has stiffened itself back up to nearly the elastic force it was made weaker to avoid, after moving more than half a metre.
The filler that cannot be gentle twice
A crushable filler in the gap between two buildings caps a collision at its crush force, but a filler soft enough to make the everyday contacts gentle runs out on the hardest one. Grade it — soft at the face, strong behind — and the soft layer takes the small contacts while the strong layer stops the large. The energy says otherwise. Every kilojoule the soft layer does not absorb, the strong layer must, in less depth: in a 40 mm filler, an outer half at 1.5 MPa needs an inner half at 56 MN, far above the 35 MN of the bare concrete it was meant to improve on.
The fuse that protects the strand and not the wall
A rocking wall's tendon loses its prestress when it yields, so give it a fuse: a short link in series that yields first and is replaced afterwards. The strand then never passes 1,000 kN and stays elastic. But the fuse caps the restoring moment lower, so under the same 1.5 g pulse the wall rocks to 110 mrad instead of 89, and the line loses all its prestress just as the strand did. A new fuse gives the prestress back; the bars' stretch stays, and the next pulse takes the wall to 134 mrad.
The law that throws the tuning away
An actuator that pushes against a tuned mass and listens only to the structure pumps the mass's own mode. A law that also listens to the mass can be made safe in one move — cancel the mass's spring, so that it has no mode to pump — and every such law is stable. But cancelling the spring throws away the tuning that made the mass useful, and the actuator has to earn it back: below a third of the force on the structure, the law is worse than the passive mass it replaced. What it buys above that, it buys mostly by letting the mass travel further.
The deck that forgets its own rhythm
A deck at twice a stay's frequency grows the stay whenever a quarter of the tension swing beats the damping. But a deck pushed by gusts is not a sine: its amplitude comes and goes and its phase drifts, and it holds a rhythm for seconds where the stay needs minutes to answer one. Against that deck the requirement is not a quarter of the swing but its square over sixteen times the deck's own damping — a sixth of the sine's at service, and a number set by how much the deck remembers rather than by how far it moves.
Half a spring is neither tuning nor freedom
An actuator pushing on a tuned mass is safe if its law cancels the mass's spring, and it then needs half the applied force to do much better than the passive mass. The obvious compromise is to cancel only part of the spring, keeping some of the tuning in case the law is not enough. Search every law in the family and the compromise turns out to be the worst choice available: each share of spring kept costs performance and makes more of the laws unstable, and from about 85 per cent kept upward no stable law under the same limits does as well as the mass with no law at all.
The filler that knows how fast it is hit
A filler graded through its depth meets the small collisions softly and the hard one with a strong layer that has to be very strong, because every kilojoule the soft layer misses must be absorbed in less depth. A filler whose strength rises with the speed it is crushed at ranks collisions by speed instead, with no layers at all, and treats the middling collisions better than grading does. But it meets every collision hardest at its first instant, when the crushing speed is greatest, and a force that falls as the collision proceeds needs a higher peak to absorb the same energy in the same depth. A purely viscous filler that stops the hardest collision in 24 mm hits it with exactly twice the force of a uniform one.
The tank that sloshes the tower
On the ground a tank's liquid splits into a part that moves with the wall and a part that sloshes at its own long period, and the two answers can be added afterwards because they are orders apart. Lift the tank onto a tower and the tower's period moves up towards the sloshing period, the two masses stop being separate, and the system has two modes that belong to neither. Adding the ground answers then overstates the base shear by a third, treating the water as solid by as much again, the wave grows by half, and a flexible tower is worst with the tank about five-sixths full.
The damper is only as good as its brace
A viscous damper added to a frame is held by a brace, and the brace is a spring in series with it. That pair has a ceiling: the most damping it can add is (√(1+κ) − 1)/2, κ being the brace's stiffness over the frame's, reached at one damper size and lost on either side of it. A brace as stiff as the frame allows 20.7%; a quarter as stiff, 5.9%. A damper larger than the best one is not better — it strokes less, locks, and turns the brace into a strut that moves the resonance instead of flattening it.
The water tower that could damp itself
A full water tower's sloshing water is a second mass on a spring, hung from the container at very nearly the tuning a designed tuned-mass damper would be given, and it weighs two-fifths as much as what it hangs from. Plain water has half a per cent of damping, so it splits the tower's resonance into two sharp peaks and helps nothing. A screen across the tank that gives it a tenth makes the water a damper: the tower's rms base shear falls to four-tenths of what it would be with the water frozen, and the same screen keeps working as the town empties the tank.
The branch that holds the riser to a floor
A riser guided at every floor leans with each storey's drift and is barely bent by it. Take a branch off it and brace the branch to a slab, and the branch becomes a strut that holds the riser to that slab partway up the storey. The riser, which was carrying 3 N/mm², carries 71 at the tee. Let the branch slide at its brace and the riser is spared, but the branch is then bent by the riser's lean. The lean has to go somewhere, and the brace decides where.
The switch that hands the mass back
An actuated tuned mass that cancels its own spring does far better than the passive mass, and the passive mass is always underneath it, so the obvious safeguard is a switch: when the stroke nears its limit or the controller fails, let go and leave the mass on its spring. The switch does not land on the passive mass. For several periods after it, the structure moves more than it would with the law or with the passive mass alone — up to the passive mass's own worst peak, at frequencies where the passive mass would have been comfortable. Letting go gradually is worse still, and a switch that is slow lets a growing storm through.
The damper sized for the earthquake
A fluid damper whose force goes as its velocity to the power 0.3 is chosen because it caps the force a large earthquake can push through its brace. The same exponent makes its effective size depend on how far it strokes. Sized to its brace's best at the earthquake's amplitude, it adds 20.7% of critical damping there, 5.4% at three-tenths of it, and nothing at all at a tenth — where the brace has locked, the building is stiffer, and the motion its occupants feel meets a resonance that is as sharp as an undamped frame's. Giving half the brace to a linear damper keeps 9.3% under the wind for 1.2 points at the earthquake.
The elbow that takes the strut away
A branch braced to a slab is a strut that holds a guided riser to that slab, and the riser, carrying 3 N/mm² alone, carries 71 at the tee. Turn the branch through an elbow before its brace and the strut is gone with 300 mm of second leg: the riser falls to 4. The storey's lean does not vanish. It bends the first leg and the elbow instead. With the stress intensification the piping rules give each fitting, the elbow carries 146 N/mm² with a 100 mm leg and matches the tee's 82 at 300 mm. Past that the tee governs again. An elbow can rescue the riser, but it cannot rescue a brace on the farther slab, where it reaches 347 N/mm².
The lever that moves the damper and not the band
A damper whose force goes as a low power of its speed is sized for the earthquake and locks in the wind. A toggle or scissor linkage multiplies its stroke, and it seemed it might move the band of amplitudes the damper serves down towards the wind. It cannot. Behind a lever of ratio f the same damper acts on the storey as one f to the power 1 + α larger, so its band moves up, not down; re-sized to the design amplitude, it gives the storey exactly the curve it had without the lever, and what has changed is the damper — a quarter of the size, a third of the force, three times the stroke. What would widen the band is a ratio that grows with the motion, and a toggle has one — until its links lie straight and it locks.
The tank that is its own tower
A standpipe holds its water in its own shaft, so the water fills a height several times its width. Only a lens of it near the surface sloshes — 0.455ρπR³, 178 t of the 2,199 t in a steel standpipe 10 m across and 30 m tall — and that lens stops growing once the water is deeper than a radius, so its period is set by the width alone: 3.3 s, against the shaft's 0.38. The lens is 8% of the water but a quarter of the shaft's moving mass, because it sits where the shaft moves most. It is far too slow to be tuned as a damper, and a screen can do little with it; what it does instead is stay still while the shaft sways, which takes nearly a fifth off the drift a frozen-water calculation predicts.
The tank that must be shallow to be slow
A deep tank's sloshing period is set by its width alone, so a tank in a tall building's core ought to be tuned by choosing how wide to make it. It cannot be. A deep tank fast enough to fit is too fast for the building: 3.6 s for a core 10 m across, where a 5 s building would need a tank 19.5 m long and an 8 s one 50 m. The depth has to tune it, and only shallow water is slow — 1.73 m for 5 s, 0.63 m for 8. Shallow water is the efficient kind, with four fifths of it sloshing. But at the accelerations the tank exists to reduce, the wave it makes is a quarter of its depth on a 5 s building and seven tenths on an 8 s one, and the linear tuning it was designed by has stopped describing it.
The forging that cushions the blow
A forge hammer's foundation is usually designed for a blow treated as a fixed impulse: the tup's momentum, multiplied by a factor for its rebound. The blow is not fixed. Between the tup and the anvil lies a hot forging, a plastic body that flows under the tup, stretches the blow to 48 milliseconds and absorbs nearly all of its 49 kJ, so that the anvil's pad feels 0.46 MN. As the part cools it flows less, the blow shortens, the tup rebounds, and the pad force climbs to 5.86 MN when the dies meet with nothing between them. The foundation is designed by the blow that does no work.
The tank that follows the building
A sloshing damper is tuned to a period computed before the building exists, and the building that is built has another one — stiffer at handover, with its partitions and cladding working, softer once its concrete has cracked. A tank whose plan is fixed and whose period is set by its depth can be brought back by opening a valve. Ten per cent off tune, the tank left alone lets the building's peak response more than double; pumped back to the right depth, it holds within a tenth of the design value, and the water it gains or loses barely matters. What does matter is that a slower building needs shallower water, and in shallow water the wave the damper is made of grows towards the depth it is sloshing in.
The filler that is used up before the worst
A crushable filler between two buildings is sized for the hardest collision it might meet, meeting it new. An earthquake does not oblige: the hardest contact arrives after a dozen middling ones, and each has taken some of the depth. Through a record of six cycles, a filler half of whose strength follows its crushing speed is dense before the worst contact arrives, and a uniform one has five millimetres left. A graded filler still has twelve. Yet the graded filler meets the worst contact at 56 MN and the spent rate-sensitive one at 39. Keeping depth is not the same as being gentle, and the order of the contacts barely matters.
The convoy that keeps the deck's time
A deck shaken by traffic is shaken by vehicles, and vehicles arrive with a rhythm of their own. The same lorries that, arriving at random, move a stay's deck by 7 mm rms and ask the stay for six hundredths of a per cent of damping, move it by 20 mm and ask for a whole per cent if they arrive every four deck periods exactly. But the rhythm is fragile in a precise way: scatter the headways by two per cent and half the danger has gone, and the timing that has to be kept is a tenth of the deck's period whatever the headway and however damped the deck. Ordinary traffic is counted by a stay, not timed; a convoy driven by a machine might not be.
The weight that lands somewhere else
A beam that yields under a falling weight takes a permanent set from every drop, and if the weight always lands in the same place the set grows by the same amount every time. Let the weight land somewhere different each time — rocks on a canopy, crates on a deck — and the set still grows: the weight's energy fixes how much plastic work every drop does, wherever it lands. What the landing point decides is where the work goes. Half of every drop's hinge rotation goes under the weight and half to the supports, so wandering drops spread the first half along the span and leave the second half where it always was: the worst hinge turns half as fast, and it is at a support.
Taking hold is harder than letting go
A tuned mass driven by a law that cancels its spring is safe to let go of: the transient is the same whenever the switch falls, and the passive mass takes over. Switching the law back on is the reverse operation and behaves nothing like it. The mass the spring was holding is thrown up to three times past its stroke limit, by an amount that depends on the instant, and a switch that is allowed to come back in a storm near its threshold comes back hundreds of times.
The fuse that makes the span work harder
A rock-fall canopy's beams hang on connections weaker than themselves, so it seems natural to let those connections be fuses: let them take the blows, replace them after a bad winter, and keep the beam clean. A falling weight is an energy, though, and a mechanism fixes how far its hinges turn relative to each other. Weaken the ends and each drop's energy has less moment to spend itself against, so every hinge turns further, and the one under the weight turns furthest. Under a big rock the fuse is the part of the beam that does less of the work, and it takes the span a third sooner to its limit. It keeps its promise only for the rocks too small to bend the span at all.
The bearing that does not know what it carries
A friction pendulum's stiffness is the weight on it divided by the radius of its dish, and from that one line three things follow. Its period has no mass in it. A heavy bearing is a stiff bearing, so the centre of stiffness stands exactly under the centre of mass wherever the mass is put, and an off-centre building does not twist. And when the building rocks and the load shifts across the bearings, the shift is along the very force that caused it, which gives that force no lever arm either. What can bring the twist back is the friction, if it differs from one bearing to the next.
The tuned mass that sits out the earthquake
A tuned mass sized for a tall building's wind sway has a stroke of half a metre and bumpers at each end. In an earthquake it would need three. The fear is that the stopped mass becomes a hammer inside the building. It does not: the building's peak never rises by more than a per cent. What the stops take away is a benefit the mass gives the tail of the shaking and never gave its peak, and what they add is a force on the mass's own supports, set by how soft the bumpers are.
The stroke the wind has already spent
A tuned mass built for a tower's comfort in wind is given a stroke and a pair of stops, and an earthquake that drives it into them costs the building almost nothing. That was found for a mass at rest when the ground began to move. A mass in a breeze is not at rest. Swinging through 0.4 m of its 0.5, it meets its stops sixteen times in an earthquake that would barely have touched them, and what pays is not the building but the stops: a small earthquake on a windy day loads them as a large one on a calm day would.
The bearings changed in opposite pairs
A building on friction pendulums does not twist because every bearing's friction is its load times one coefficient, so the friction's resultant passes through the mass. Replace one bearing with a new one and that stops being exactly true. One bearing does almost nothing: about one per cent at a corner. The order of a whole programme does more. Worked from one end of the plan to the other, the halfway state moves the friction's centre 2.5 m and the corner bearings travel 8 per cent further than the mass; worked in pairs opposite each other through the centre, the plan never twists by more than two per cent and is straight again after every second bearing.
The ring the mass swings inside
A tall building's tuned mass is usually swung by the wind across one line, and an earthquake can arrive from any direction. If the mass runs on two tracks with stops on each, an earthquake at right angles to the wind's swing finds its whole stroke free: the wind costs nothing. If it hangs inside a ring of stops, the two strokes add as a vector and the ring is nearer than it looks. In a moderate earthquake across a wind that already swings the mass ±0.40 m of its ±0.50, the ring is struck 2.6 times a record against 0.5 between pairs and 8.0 along the wind's line. In a strong one the ring is struck more often across the wind than along it.