Structural form

The slab that spans both ways

A panel supported on four sides sends its load in two directions at once, and the share is decided by a fourth power — so a panel a third longer than it is wide has already stopped being a two-way slab in any useful sense. What it does at collapse is a different calculation with a different answer.

Assumes The load a beam is given is a decision, After the first yield, which is not the end and Span to the fourth, which is why spans are short.

A floor slab supported on all four sides has a choice about where to send its load, and the usual account is that it makes both — spanning one way and the other, sharing the work. That is true for a square panel and it stops being true remarkably quickly.

A two-way slab is a one-way slab as soon as it is not square. The share of the load carried by the strips spanning the short way, against the ratio of the sides. The two families of strips cross at the centre and must deflect equally there, and a strip's deflection goes as the fourth power of its span — so at a ratio of 1.33 the short strips already take 76% and at 2 they take 94%. The panel drawn here is 6 × 8 m, a ratio of 1.33, and its short strips take 76.0%. Two-way action is worth having at a ratio of one and worth almost nothing by two.
Fig. 1 The share of the load carried by the strips spanning the short way, against the ratio of the sides. Strips in the two directions cross at the centre and must deflect equally there, and a strip’s deflection goes as the fourth power of its span — so the short strips take Ly⁴/(Lx⁴ + Ly⁴). At 1 : 1 the share is half; at the 6 × 8 m panel drawn here it is 76.0%; and by 2 : 1 it is 94%.

The whole of that curve comes from one equation with one unknown, and the equation is a compatibility statement rather than an equilibrium one.

One equation, and the fourth power does the rest

Cut the panel into two families of strips at right angles. Every strip in one family crosses every strip in the other, and at the centre both pass through the same point — which must therefore deflect the same amount whichever family is asked.

A simply supported strip of span LL under ww deflects 5wL4/384EI5wL^4/384EI at its middle. Setting the two families equal:

wxLx4=wyLy4withwx+wy=ww_x L_x^4 = w_y L_y^4 \qquad\text{with}\qquad w_x + w_y = w

and the share follows immediately. Nothing about the slab’s thickness, its material or its reinforcement enters, because both sides carry the same EIEI and it cancels.

The consequence is the one this collection keeps meeting from other directions: span enters deflection as a fourth power, and a fourth power is a violent thing. A panel only 33% longer than it is wide sends three-quarters of its load the short way; the second direction is doing a quarter of the work for the same reinforcement.

The fourth power on its own is the familiar one: doubling a span multiplies a beam’s deflection by sixteen. What the two-way share does is use that curve as a lever rather than as a warning. Two strips have to deflect equally where they cross, so their loads must be in the inverse ratio of their fourth powers, and a modest difference in span therefore produces an extreme difference in load. A 1.33 : 1 ratio is nothing as a length and is 3.16 as a fourth power, which is where the 76 per cent comes from.

Two-way action is worth having at a ratio of one and worth almost nothing by two, which is the practical rule the curve encodes and the reason panel proportions are a structural decision rather than an architectural one.

The tributary rule says something different

An earlier essay divided the same panel with lines at 45° and handed the load to the beams around it. That division gives the short direction 62.5% of the load where the elastic calculation gives 76.0%, and the discrepancy is worth being precise about because the two rules are answering different questions.

Where a beam's load comes from. A 8 × 6 m panel carrying 5 kN/m², divided at 45° from the corners. The long beams take a trapezoid of 15.0 m² each and the short beams a triangle of 9.0 m²; the four areas sum to 48.0 m², which is the panel, so no load has been invented or lost. The line loads quoted are the uniform equivalents; the real distributions peak at 15.00 kN/m at midspan.
Fig. 2 The tributary division of the same proportions: two trapezoids and two triangles, summing exactly to the panel. It is a division of area, and area does not go as the fourth power of anything — so it under-states how much the short direction really takes and over-states the long one, by about a fifth at these proportions.

Neither is wrong. The tributary rule is a statement about what the supporting beams should be designed for, and it is deliberately blunt: it has the property that the loads add up, it is drawable in ten seconds, and its errors are of a size the beams’ own margins absorb. The elastic share is a statement about what the slab does, and it is what decides the reinforcement in each direction.

The pattern is one worth naming, because it recurs. A rule that conserves the total can be badly wrong about the division and still produce a safe structure, provided every member designed from it has some margin — which is what makes crude load paths workable, and what makes them dangerous when the margins are trimmed.

At collapse, none of that arithmetic applies

Everything above is elastic, and a slab does not fail elastically. Once the reinforcement yields along a line, that line becomes a hinge of constant moment, and the panel goes on carrying load until enough lines have formed to make a mechanism.

The pattern it breaks in. The yield-line mechanism of a 6 × 8 m panel simply supported on all four edges: lines from each corner meeting a ridge along the middle, 3.41 m in from each short edge. The panel folds into four flat plates, all the rotation happens along the lines, and the collapse load is 20.611 kN/m² for a capacity of 40 kNm/m. The pattern is assumed and the position searched, so the answer is an upper bound — the lowest one the mechanism can produce.
Fig. 3 The yield-line mechanism of the 6 × 8 m panel: lines from each corner meeting a ridge along the middle, 3.413 m in from each short edge. The panel folds into four flat plates, all the rotation happens along the lines, and the collapse load is 20.611 kN/m² for a moment capacity of 40 kNm/m.

The calculation is a work equation and it takes three lines. Give the ridge a unit deflection; the external work is the load times the volume under the resulting shape; the internal work is the moment capacity times each region’s rotation times the projection of the yield lines it turns about. Equate, and the load falls out.

What makes it an upper bound is that the pattern was assumed. Any mechanism gives a load at which the slab could collapse, and the true collapse load is the lowest over all of them — so the position of the lines has to be searched rather than chosen.

The mechanism is searched for, not quoted. Collapse load against the position of the yield lines, for a 6 × 8 m panel with a moment capacity of 40 kNm/m. Every position gives an upper bound and the true collapse load is the lowest of them: 20.611 kN/m² at 3.41 m from the short edge. The handbook formula, 24m/(a²(√(3+α²) − α)²), gives 20.611 — a difference of 0.000%, which is the search resolution rather than a disagreement.
Fig. 4 Collapse load against the position of the yield lines, over six hundred positions. Every position is a legitimate mechanism and gives an upper bound; the lowest is 20.611 kN/m² at 3.413 m from the short edge. The handbook closed form, 24m/(a²(√(3+α²) − α)²), agrees to five decimal places — which is the search finding the same minimum the algebra does, by a route that shares nothing with it.

The lines are not at 45° and the square panel is why everybody thinks they are

The minimum in that search sits at 3.413 m from the short edge, and a 45° line from the corner of a 6 m-wide panel would reach the centreline at 3.000 m. The real angle is 41.3°, and the 45° mechanism gives 20.741 kN/m² against the true 20.611 — 0.63% high, which is what an upper bound being slightly too high looks like.

For a square panel the search returns 2.995 m on a 6 m panel — 45° to within the search resolution — and that is the case everybody meets first. The 45° rule is therefore another symmetry result mistaken for a geometric one, exactly as the tributary rule is, and both are exact for a square and approximate for everything else.

The pattern it breaks in. The yield-line mechanism of a 6 × 6 m panel simply supported on all four edges: lines from each corner meeting a ridge along the middle, 3.00 m in from each short edge. The panel folds into four flat plates, all the rotation happens along the lines, and the collapse load is 26.667 kN/m² for a capacity of 40 kNm/m. The pattern is assumed and the position searched, so the answer is an upper bound — the lowest one the mechanism can produce.
Fig. 5 The square case: the ridge has shrunk to a point, the four lines are diagonals, and the mechanism is a shallow pyramid. The collapse load is 26.667 kN/m² for the same 40 kNm/m of capacity — 29% more than the 6 × 8 panel, from a change of proportion alone with no change of thickness, reinforcement or span in the short direction.

That last comparison is the argument for square panels stated in one number. The short span is 6 m in both cases and the short-direction reinforcement is the same; making the panel square rather than 3 : 4 buys 29% more capacity for nothing.

The corners are trying to lift, and holding them down is worth something

There is a part of a two-way slab’s behaviour that no strip argument contains at all, and it is visible on any slab that has been loaded hard: the corners try to rise.

The reason is torsion. Near a corner where two supported edges meet, the slab is being bent in two directions at once and the twisting curvature between them is at its largest — so the corner region carries torsional moment rather than bending, and the equilibrium of that region requires a downward force at the corner. Where the corner is held down, that force is supplied and the panel is stiffer and stronger than the strip calculation says. Where it is free — a slab simply resting on walls, a precast unit — the corner lifts off, the torsional restraint is lost, and the capacity falls.

The corner is where the plate twists, and it has to be held down. The twisting moment M_xy over a 6 × 8 m simply-supported panel under 10 kN/m², from Navier's double series. It is zero along both centrelines and largest at the corners, which is the opposite of the bending moments and is why no strip reading contains it: 29% of the load crosses this panel in twist, and a strip can only bend. At a free corner the twisting moment is statically equivalent to a downward point force of 2M_xy — 33.4 kN here, 7.0% of the whole load on the panel, applied at a point — so the corner has to be held down. A panel whose corners are free lifts there, deflects more, and cracks diagonally across them. The deflection at the centre is 4.12 mm, against 6.15 mm for the strip that ignores all this — 49% more, which is the size of what the twist is carrying.
Fig. 6 The twisting moment over the same 6 × 8 m panel under 10 kN/m², from Navier’s double series. It is zero along both centrelines and largest at the corners — the opposite of the bending moments, and the reason no strip reading contains it, since a strip can only bend. 29 per cent of the load crosses this panel in twist. At a free corner the twisting moment is statically equivalent to a downward point force of 2M_xy, which is 33.4 kN here — 7.0 per cent of the whole load on the panel, applied at a point. The centre deflects 4.12 mm against the 6.15 mm the strip calculation gives, which is 49 per cent more and is the size of what the twist is carrying.

Two practical rules come out of it and both look arbitrary until the mechanism is understood. Corner reinforcement — top and bottom steel in both directions over a region about a fifth of the short span — exists to carry the torsional moments the corner is being asked for. And holding the corners down, rather than letting them lift, is worth a few per cent of capacity and considerably more stiffness.

It also makes a connection this collection has been building toward. Torsion is the internal force with no diagram, and here it is doing structural work in the least likely place — the flat corner of a floor slab, where nothing appears to be twisting at all.

What two-way action is actually worth

The cleanest way to value it is to ask what moment capacity a slab needs for a stated load, and to compare that with the same slab spanning one way.

A 6 m one-way strip under 10 kN/m² needs wL2/8=45.0wL^2/8 = 45.0 kNm per metre. The 6 × 8 m panel spanning both ways needs 19.4 kNm/m by the yield-line calculation above — 57% less, for the same span and the same load, because the corners are helping and the long direction is taking a share.

Stretching the panel is what spends that saving, and the yield-line calculation is the place to watch it go.

The pattern it breaks in. The yield-line mechanism of a 6 × 12 m panel simply supported on all four edges: lines from each corner meeting a ridge along the middle, 3.91 m in from each short edge. The panel folds into four flat plates, all the rotation happens along the lines, and the collapse load is 15.712 kN/m² for a capacity of 40 kNm/m. The pattern is assumed and the position searched, so the answer is an upper bound — the lowest one the mechanism can produce.
Fig. 7 The same mechanism on a 1 : 2 panel. The ridge has grown to occupy most of the length and the yield lines have been pushed out to 3.910 m from each short edge, against 3.413 on the 6 × 8 and a point on the square. The collapse load is 15.712 kN/m² for the same 40 kNm/m of capacity, against the square panel’s 26.667 — the two ends now contribute almost nothing and the middle behaves as a one-way strip, which is what the elastic share of 94% already said.

Three panels, one mechanism, one capacity: 26.667, 20.611 and 15.712 kN/m², from nothing but the second dimension. The short span is 6 m in all three and the short-direction reinforcement is identical, and the collapse load has fallen by 41 per cent across the range.

That saving is why two-way slabs exist, and the shape of it explains where they are used. It is largest for square panels and falls away with the aspect ratio; it needs support on all four sides, which means beams or walls in both directions; and it needs the reinforcement to run both ways, which is a detailing cost rather than a material one. Flat slabs on columns are a different structure again — supported at points rather than on lines — and their yield-line patterns are correspondingly stranger. Whichever is used, the depth available is doing most of the work: depth is the cheapest strength in a slab as much as in a beam, and a 25 mm change in thickness moves more than any amount of re-proportioning.

The collapse mechanism of a fixed-ended beam. A collapse mechanism, with the hinge position found by searching rather than quoted. Every position gives an upper bound on the collapse load; the lowest is 10.00, at a hinge 50.0 per cent along, which is a coefficient of 16.000 times Mp over the square of the span.
Fig. 8 The beam version of the same method: a mechanism assumed, the work equation written, and the hinge position searched over eight hundred candidates rather than quoted. Yield-line analysis is this argument in two dimensions, and it inherits both its power and its one weakness — the answer is an upper bound, so a mechanism nobody thought of gives a lower load.

Two-way action is worth far less in stiffness than in strength

The 57 per cent quoted above is a saving in moment capacity, and a slab is very seldom governed by moment capacity. Run the same three panels through a deflection comparison and the number collapses.

Deflection is decided entirely by the short-direction share, since the two families deflect the same amount by construction and the short one carries wxw_x of the total:

δtwo−wayδone−way=wxw\frac{\delta_{two-way}}{\delta_{one-way}} = \frac{w_x}{w}

which is the share itself, read as a fraction rather than as a percentage. Put it beside the collapse saving:

panel short share stiffness saving strength saving
6 × 6 50.0% 50% 67%
6 × 8 76.0% 24% 57%
6 × 12 94.1% 6% 43%

At 3 : 4 the panel is 57 per cent stronger and 24 per cent stiffer, and at 1 : 2 it is 43 per cent stronger and six per cent stiffer. The gap between the two columns is not small and it is not an artefact.

It has a cause, and the cause is the whole of what the elastic strip model leaves out. The strip share is an elastic statement about two families of beams that pass through each other and do nothing else. The collapse load is a plastic statement about a folded plate whose corners are carrying torsion, whose reinforcement has redistributed, and in which every yield line does work. The corners appear in the second column and not in the first, which is why the 1 : 2 panel — where the elastic share says two-way action has all but gone — still collapses at 43 per cent less capacity than a one-way strip.

The design reading is uncomfortable and worth stating. A two-way slab is usually sized by deflection; the argument that sells it is a strength argument; and the two differ by a factor of more than two at ordinary proportions. So a panel chosen for its collapse economy and then thickened until it passes a span/depth check has bought most of what it paid for in a currency it is not spending. That is the same mismatch a floor that is strong and unusable is built on, arriving here through the plan rather than through the section.

Continuity beats aspect ratio, and reverses it

The fourth-power rule was derived for two simply supported strips, and the coefficient 5/3845/384 cancelled because both families had it. In a real floor they do not.

An interior panel is continuous with its neighbours, and continuity in one direction changes that coefficient by a factor of five — a strip fixed at both ends deflects wL4/384EIwL^4/384EI against a simply supported one’s 5wL4/384EI5wL^4/384EI. So the compatibility statement is really

kx wxLx4=ky wyLy4k_x\,w_x L_x^4 = k_y\,w_y L_y^4

and the share is set by the product of the coefficient and the fourth power, not by the fourth power alone.

Take the 6 × 8 panel and make it continuous along its long direction — an edge panel of a floor whose beams run one way — while the short direction stays simply supported on the perimeter:

5 wx(1,296)=1 wy(4,096)⇒wxwy=0.6325\,w_x(1{,}296) = 1\,w_y(4{,}096) \quad\Rightarrow\quad \frac{w_x}{w_y} = 0.632

The short direction now takes 39 per cent and the long direction 61. The panel that sent three-quarters of its load the short way sends the majority of it the long way instead, from nothing but the support conditions at its two ends.

The break-even is where the aspect ratio’s fourth power equals the continuity factor:

(LyLx)4=5⇒LyLx=1.50\left(\frac{L_y}{L_x}\right)^4 = 5 \quad\Rightarrow\quad \frac{L_y}{L_x} = 1.50

so a panel continuous the long way sends most of its load that way until it is half as long again as it is wide. That is a large range of ordinary panels, and it is the reason an interior panel and an edge panel of the same dimensions carry their load in different directions and crack in different patterns — the plan is identical and the boundary is not.

An upper bound is the wrong side to be on

The weakness deserves stating plainly, because it is the opposite of the usual engineering position. A yield-line answer is a load at which the slab can collapse by the mechanism assumed, so a missed mechanism makes the answer unsafe rather than conservative — and this collection’s other plastic method, the thrust line and the safe theorem, errs the other way.

Two mechanisms are commonly missed and both are worth knowing. Corner levers: near a corner where two simply supported edges meet, the slab lifts and the yield line forks, giving a load a few per cent below the simple pattern. And fans around a concentrated load or a column head, where the lines radiate rather than run straight, which is the governing pattern for punching.

The professional response is a two-part one: search over the mechanisms that are known, and add a margin for the ones that are not — the yield-line method is conventionally used with a lower moment capacity than a strip-based elastic method would allow, and the difference is the price of being on the wrong side of a bound.

The reinforcement does not have to follow the share

The elastic share says how much load each direction carries in a slab whose two directions are equally stiff. It does not say how the slab must be reinforced, and that distinction is the most useful thing in this essay for anybody detailing one.

A slab reinforced more heavily in one direction is stiffer in that direction, so it attracts more load, so it needs more reinforcement — a feedback that sounds unstable and is not, because the stiffness in each direction changes far less than the reinforcement does once the slab has cracked. What actually happens is that the designer chooses the load path and then provides for it, within limits set by what the slab can redistribute.

That freedom is exactly the lower-bound theorem at work. Any distribution of load between the two directions that is in equilibrium with the applied load, and for which the reinforcement is sufficient everywhere, is a safe design — regardless of what an elastic analysis says the slab would do if left alone. Hillerborg’s strip method is that observation turned into a design procedure: divide the load between the directions however is convenient, design each family of strips as a one-way slab, and the result is safe by theorem rather than by calculation.

The practical consequence is that the elastic share is a guide rather than an instruction. A designer who sends 100% of the load the short way and reinforces accordingly has designed a safe slab that will behave like a two-way slab and will crack a little more where the reality and the assumption disagree. A designer who assumes an equal share on a 1 : 2 panel and reinforces for it has done something else entirely, because the long direction will never take 50% no matter how much steel is in it — the load follows stiffness, and stiffness is not what the drawing says the steel is for.

What the picture cannot show

The slab is isotropic in every figure. A real slab has different reinforcement in the two directions, so the moment capacity is a function of the yield line’s direction, and the search has to be over patterns and over orientations. The arithmetic is the same with an extra factor; the pictures are much less tidy.

Nothing here has a deflection in it. Yield-line analysis reports a collapse load and says nothing about serviceability, and slabs are almost always governed by deflection rather than by strength — so the method answers the question that does not decide the thickness.

The elastic share and the collapse mechanism describe different states of the same slab and neither is the whole story. A slab in service is somewhere between: cracked, partly redistributed, with a stiffness in each direction that depends on how much it has already been loaded. The two calculations bracket it, which is the usual arrangement, and the bracket is wide.

Where the ladder goes

The first rung is the flat slab: no beams, columns only, and a structure whose yield-line pattern is a set of fans around the column heads. Punching shear is the failure that governs it and it is a local three-dimensional problem that none of the arithmetic above touches.

The second is the strip method, which is yield-line’s opposite number: instead of assuming a mechanism and getting an upper bound, it assumes a distribution of load into strips and gets a lower one, so the two together bracket the answer in the same way an arch’s thrust line and its collapse mechanism do.

The third is the one the fourth power implies. If two-way action is worth so much and disappears so fast with aspect ratio, the layout of a floor grid is a structural decision of the first order — and it is usually made by somebody drawing a column grid to suit a car park.

What this makes readable

Essays that name this one as a prerequisite.

Named alongside this one

Essays reaching for the same objects. Nobody chose these; they are what the concept index makes visible.

What links here

The 8 essays that link to this one and share the most of its objects, of 12 that link here.

The objects this essay names

Each one links to every other essay that touches it.

Collapse mechanismLoad pathPlastic hingeSpan scalingTributary areaTwo-way spanningUpper boundYield-line