Structural form

How a tall building stands still

A shear wall bends and a framed tube shears, and the two deflected shapes are the wrong way up for each other. Tie them together at every floor and the pair is stiffer than the sum of their stiffnesses — because near the base the wall holds the frame back and near the top the frame holds the wall.

Assumes The frame that leans, and what stops it, The deflection that arrives three years late and One support too many, and what it costs to know.

A tall building’s vertical structure is a solved problem: the columns get bigger toward the bottom and the arithmetic is a running total. Its lateral structure is not, and past about ten storeys it is the thing that decides the whole form of the building.

Two arrangements are available and they resist in completely different ways.

Two shapes that are the wrong way up for each other. Deflected shapes of a 20-storey building under a uniform wind, drawn to the same scale. The wall alone bends: its shape is flattest at the base and steepest at the top, reaching 146 mm. The frame alone shears: it is steepest at the base where the storey shear is largest, reaching 140 mm. Tied together at every floor they reach 58 mm — less than a quarter of either, and less than the 72 mm two springs in parallel would give, because each is stiff exactly where the other is not.
Fig. 1 Deflected shapes of a 20-storey building under a uniform wind, to the same scale. The wall alone bends: flattest at the base, steepest at the top, reaching 146.5 mm. The frame alone shears: steepest at the base where the storey shear is largest, reaching 140.0 mm. Tied together at every floor they reach 58.0 mm — less than half of either, and less than the 71.6 mm two springs in parallel would give.

The two shapes are the interesting part before any of the numbers. A wall is a vertical cantilever and its slope accumulates upward, so its worst storey drift — the relative movement between one floor and the next, which is what cracks partitions and jams lifts, and which stiffness rather than strength decides — is at the top. A frame racks storey by storey in proportion to the shear it carries, so its worst drift is at the bottom. They are the wrong way up for each other, and that is exactly why the combination works.

What each one is doing

A shear wall or a core is a cantilever with an enormous second moment of area, and its tip deflection under a uniform wind is the familiar qH4/8EIqH^4/8EI. The fourth power of the height is the reason walls run out: doubling the height of a building multiplies the wall’s deflection by sixteen while multiplying the wind load by four and the wall’s own stiffness by nothing at all.

A moment frame has no such expression, because it does not bend as a whole. Each storey racks by Vi/kiV_i/k_i where ViV_i is the shear above that storey, and the total sway is the sum of those racking movements. That makes a frame’s deflection go as the square of the height rather than the fourth power, which sounds better and is offset by kk being small — a frame is a much less efficient use of material for lateral stiffness, and it is used because it leaves the floor plan open.

Each storey of the framed building is a portal under a horizontal load, solved on its own: the columns bend in double curvature, the beams bend to restrain them, and the storey racks by an amount proportional to the shear passing through it. The racking of each storey is added to the ones below, which is why a frame’s sway accumulates from the bottom and its deflected shape has its greatest slope where the shear is largest.

The interaction reverses, and that is the whole trick

Tie the two systems together with floors that cannot stretch, and neither can take the shape it wanted.

Near the bottom the wall holds the frame. Near the top the frame holds the wall. Storey shear carried by each system, up the height of a 20-storey building. At the base the wall takes 3% of nothing and the frame the rest; by level 16 the wall's share has gone negative — it is being dragged forward by the frame rather than restraining it, and the frame is carrying more than the whole applied shear. Neither system does that alone, and it is why the pair is stiffer than either: the top drift is 58 mm against 146 for the wall alone and 140 for the frame alone.
Fig. 2 Storey shear carried by each system up the height of the building. At the base the wall carries almost all of it and the frame nearly nothing. Higher up the frame’s share rises; by level 16 the wall’s share has gone negative — it is being dragged forward by the frame rather than restraining it — and near the roof the frame carries more than the whole applied shear while the wall pulls back.

That sign change is the reason the pair beats springs in parallel. In the lower storeys the frame wants to rack a long way and the wall will not let it, so the wall takes the shear. In the upper storeys the wall wants to lean out and the frame will not let it, so the frame takes more than the applied shear and hands the excess back to the wall as a restraint.

Each system is stiff exactly where the other is weakest, and the interaction converts the wall’s surplus stiffness at the bottom and the frame’s at the top into a structure with neither system’s worst drift. The 24% bonus over the parallel-spring estimate is that conversion measured.

It also explains a detail that puzzles people looking at a frame analysis of a real building: the beams connecting a core to the surrounding frame carry substantial forces near the top of the building, in a direction that looks backwards. They are the interaction force, and near the roof it points the other way.

One number decides which building this is

Everything on this page — the shape, the reversal, the size of the bonus — is governed by a single dimensionless group, and it is worth extracting because it turns a family of drawings into one curve.

The wall contributes a flexural rigidity EIEI; the frame contributes a shear rigidity GA=khGA = k h, since a storey drift V/kV/k over a height hh is a shear strain V/khV/kh. Those two combine into a length

ℓs=EIGA\ell_s = \sqrt{\frac{EI}{GA}}

and the building’s behaviour depends on the height only through the ratio αH=H/ℓs\alpha H = H/\ell_s.

Both quantities can be read straight off the two single-system drifts printed above. The wall alone reaches 146.5 mm, and δ=qH4/8EI\delta = qH^4/8EI gives EI=8.19×108EI = 8.19\times10^8 kNm²; the frame alone reaches 140.0 mm, and δ=qH2/2GA\delta = qH^2/2GA gives GA=7.0×105GA = 7.0\times10^5 kN. So

ℓs=8.19×1087.0×105=34.2 m,αH=7034.2=2.05\ell_s = \sqrt{\frac{8.19\times10^8}{7.0\times10^5}} = 34.2\ \text{m}, \qquad \alpha H = \frac{70}{34.2} = 2.05

One drift, two motions, opposite curvatures. The sideways movement of a 70 m building under a uniform wind, drawn as the sum of the two mechanisms that produce it. The bending curve is a cantilever's: flat at the base, steepening upward, concave one way. The racking curve is a stack of parallelograms: steepest at the base and flattening, concave the other. They add to 287 mm at the roof, of which 51% is bending. The one group that decides the split is αH = H√(GA/EI) = 2.05: below one the racking dominates and the building behaves as a frame, above about six the bending does and it behaves as a cantilever, and everything interesting is in between.
Fig. 3 The same two mechanisms drawn as components of a single drift, at this building’s own numbers — the 8.19 × 10⁸ kNm² read off the wall’s 146.5 mm and the 7.0 × 10⁵ kN read off the frame’s 140.0. Put both flexibilities into one member instead of into two tied together and they simply add: 287 mm at the roof, 51 per cent of it bending, which is the 146.5 and the 140.0 back again. The group that fixes the split is αH = H√(GA/EI) = 2.05, and it is the same number for the interacting pair because it is built from the same two stiffnesses.

The two curvatures in that drawing are the whole of the shear length’s meaning. It is the height at which the two systems change places. Below it the wall’s flexural stiffness is the cheaper way to resist; above it the frame’s shear stiffness is. A building shorter than its own shear length behaves as a cantilever with a frame attached, and a building much taller than it behaves as a frame with a wall attached, and the interesting ones are within a factor of a few.

The bands are the design content:

αH\alpha H behaviour drift shape
below ~1 wall-dominated flexural — worst drift at the top
1.5 to 4 genuine interaction S-shaped, worst drift near mid-height
above ~6 frame-dominated shear — worst drift at the base

At 2.05 this building is squarely in the middle band, which is why it gets a 24 per cent bonus over the parallel-spring estimate: the bonus is the interaction, and it goes to zero at both ends of the table.

And it says exactly what happens on scaling. The forty-storey version has the same ℓs\ell_s and twice the height, so αH=4.09\alpha H = 4.09 — still interacting, but moving toward frame-dominated, which is why its reversal point slid from 80 per cent of the height to 70. Doubling a building’s height and keeping its behaviour would require four times the core stiffness at unchanged frame stiffness, since αH\alpha H carries EI\sqrt{EI} underneath. Nobody has ever quadrupled a core. That, rather than the fourth power on its own, is why the systems change at height.

The outrigger, and where it belongs

The next move, once a wall and a frame together are not enough, is to connect the wall to the perimeter columns with a deep truss or a storey-deep wall at one level — an outrigger. Its effect is not to add lateral stiffness directly but to apply a restraining moment to the wall, using the perimeter columns as a couple.

The best place for an outrigger is not the top. Top drift against the height at which a single outrigger is placed, for the same 20-storey building. The best level is 11 of 20 — 55% of the height — giving 17 mm against 58 mm with no outrigger at all and 35 mm with it at roof level. An outrigger works by applying a moment to the wall against the perimeter columns, and a moment applied at the very top has no height left to act over.
Fig. 4 Top drift against the height at which a single outrigger is placed. The best is level 11 of 20 — 55% of the height — giving 17.0 mm against 58.0 mm with no outrigger and 34.7 mm with it at roof level. An outrigger works by applying a moment to the wall against the perimeter columns, and a moment applied at the very top has no height left over which to act.

The shape of that curve is the design rule, and it is not obvious. The wall’s rotation is largest at the top, which suggests putting the outrigger there; the length over which the restraining moment reduces curvature is largest at the bottom, which suggests the opposite. The product of the two peaks somewhere near the middle, and every study of the problem since the 1960s has found the optimum between half and six-tenths of the height for a single outrigger.

Two consequences follow that are pure engineering economics. Putting an outrigger at 55% of the height means giving up a storey of lettable perimeter in the middle of the building, which is worse commercially than giving one up at the top — so real buildings often place them at plant levels, accepting a few per cent of stiffness to put the structure where the lifts and the air handling already are. And two outriggers at roughly a third and two thirds do better than one at the optimum, with diminishing returns after that.

Two thirds of a frame’s flexibility is in its beams

The frame was given one number, k=k = storey stiffness, and it is worth opening because what is inside it decides where money spent on a moment frame goes.

Rack one storey of a regular frame and both the columns and the beams bend. They are in series — the column’s rotation at a joint is only resisted to the extent the beam resists it — so the storey stiffness is

k=12Eh2[(∑Ich)−1+(∑IbL)−1]−1k = \frac{12E}{h^2}\left[\left(\sum \frac{I_c}{h}\right)^{-1} + \left(\sum \frac{I_b}{L}\right)^{-1}\right]^{-1}

which is the standard subassembly result and reads exactly like two springs in series, because it is.

Put ordinary members into one bay: a 3.5 m storey with two 305 × 305 × 137 columns (Ic=3.28×10−4I_c = 3.28\times10^{-4} m⁴) and one 533 × 210 × 92 beam over a 6 m span (Ib=5.52×10−4I_b = 5.52\times10^{-4} m⁴):

∑Ich=1.87×10−4,∑IbL=0.92×10−4 m3\sum \frac{I_c}{h} = 1.87\times10^{-4}, \qquad \sum \frac{I_b}{L} = 0.92\times10^{-4}\ \text{m}^3

The beam is the softer half by a factor of two, and it contributes 67 per cent of the storey’s sway flexibility — despite having the larger second moment, because its span is 6 m against the column’s 3.5. The pair gives k=12,700k = 12{,}700 kN/m, and the 7.0×1057.0\times10^5 kN of shear rigidity read off the drift above is about sixteen bays of this kind, which is what a perimeter frame on a plan of this size has.

So the instinct to answer a sway problem by enlarging the columns is mostly wasted. Doubling IcI_c here takes kk from 12,700 to 15,200 — 20 per cent — while doubling IbI_b takes it to 19,100, or 50 per cent, and doing both gives the full factor of two. It is I/LI/L rather than II that is being summed on each side, and the beams have the long LL.

That is also why a frame’s stiffness collapses when the bays get wider. Going from 6 m to 9 m bays with the same beam divides ∑Ib/L\sum I_b/L by 1.5 and takes kk down to 9,500 — a 25 per cent loss of lateral stiffness from a decision made entirely about the floor plan, before any lateral calculation was run.

Every wall is also a foundation problem

The lateral load a building resists has to leave it somewhere, and for a wall or core system it leaves through a footprint much smaller than the building.

A 20-storey building 70 m tall with a core 8 m across, under a wind resultant of 800 kN at mid-height, delivers 28,000 kNm of overturning moment into a foundation eight metres wide. Divide: the resultant lands 1.4 m from the core’s centre if the core carries 20,000 kN of gravity load, against a middle third of ±1.33 m — so the foundation is on the point of lifting on the windward side, from a wind the superstructure barely noticed.

Weight is the only thing holding it down. A body 12 m wide and 60 m tall weighing 60000 kN, under a wind pressure of 1.5 kN/m². The wind delivers 1080 kN and an overturning moment of 32400 kNm about the leeward toe; the weight restores 360000 kNm, a factor of 11.11. The resultant lands 0.54 m from the centre against a middle third of ±2.00 m, so the base is still wholly in bearing.
Fig. 5 The whole building as a rigid body: 60,000 kN on a 12 m base under 1.5 kN/m² of wind, giving a factor of 11.1 against overturning and a resultant 0.54 m from the centre against a middle third of ±2.0 m. The building itself is never close to blowing over; what is close is the individual core, whose base is a fraction of the plan.

The consequence is that a concentrated lateral system concentrates its foundation problem too, and the choice between a core and a distributed system is partly a choice about whether the overturning goes into a few piles in tension or into many columns in compression. A framed tube spreads it over the whole perimeter and the uplift per column is small; a single core takes all of it and needs tension piles, which are a different and more expensive thing than compression piles.

That is also why the systems that work at height are the ones with the largest plan dimension: they reduce the foundation forces in exactly the proportion they reduce the drift, and both improvements come from the same lever arm.

The drift limit is what all of this is for

None of these systems is close to failing. The wind moment on a 20-storey building is well within what any sensible core can carry, and the calculation above is not a strength calculation at all.

The limit that governs is drift: the top deflection against the height, and the storey drift against the storey height. The building above reaches 58.0 mm over 70 m, which is H/1208 — comfortably inside the H/500 that is the usual expectation. Take the frame away and it is H/478, which is not.

Two quite different things are being protected. The overall drift matters for occupant comfort and for the tolerance of anything spanning between the building and its neighbours. The storey drift matters for whatever is attached: a partition, a cladding panel or a lift guide rail is asked to absorb the difference between one floor’s movement and the next’s, and it usually fails at a fraction of a per cent of the storey height. That is why the shape of the deflection matters as much as its size, and why a system with a large top drift and even storey drifts can be preferable to one with a small top drift concentrated in three storeys.

The two mechanisms put their worst storey at opposite ends. Inter-storey drift, storey by storey, split into the two motions that make it. The racking component is largest at the bottom, where the storey shear is largest, and dies away at the top. The bending component is largest at the top, where the accumulated rotation is greatest, and is nothing at the base. Their sum has its worst storey at number 7 of 20 — neither where the shear puts it (storey 1) nor where the bending does (storey 20). This is why the roof drift is a poor guide: it is 1 in 244 of the height here, and the worst storey is 1 in 216 of its own.
Fig. 6 Inter-storey drift storey by storey, split into the two motions that make it, on the same 70 m building with the two flexibilities added rather than made to interact. The racking component is worst at storey 1 and dies away upward; the bending component is worst at storey 20 and is nothing at the base; their sum is worst at storey 7, which is neither. The roof drift is 1 in 244 of the height and the worst storey is 1 in 216 of its own — so the number a limit is usually written against is 13 per cent kinder than the number the cladding sees.

The same reasoning applies to the interacting pair with the numbers moved and the shape preserved: the worst storey is not at either end, and the total drift does not say where it is. A stiffening measure that improves the roof figure by taking the bending component down can leave the worst storey exactly where it was.

And the lateral system decides more than the static drift. The storey stiffnesses that resist wind are the ones that fix the building’s natural periods, so the same choice governs the response to an earthquake and to gusting — a matter this collection treats as a set of periods rather than one. A stiffening measure changes every one of those answers at once, and not all of them for the better.

Scale changes which system is possible

Everything above was a 20-storey building. The arithmetic does not survive being scaled without changing the answer.

Two shapes that are the wrong way up for each other. Deflected shapes of a 40-storey building under a uniform wind, drawn to the same scale. The wall alone bends: its shape is flattest at the base and steepest at the top, reaching 2269 mm. The frame alone shears: it is steepest at the base where the storey shear is largest, reaching 547 mm. Tied together at every floor they reach 343 mm — less than a quarter of either, and less than the 441 mm two springs in parallel would give, because each is stiff exactly where the other is not.
Fig. 7 The same wall and the same frame at forty storeys. The top drift is 343 mm over 140 m, which is H/408 — outside any ordinary limit, from a structure that was comfortable at half the height. The interaction reversal has moved to level 28, keeping its position at about 70% of the height, and the shapes are the same shapes at a different size.

The fourth power is doing that. A wall’s contribution falls away as the building grows, so the systems used at height are the ones whose stiffness comes from plan dimensions rather than from a core: the framed tube, the braced tube, the outrigger system, the bundled tube. Each is an attempt to use the full width of the building as the depth of a cantilever, which is the same statement about depth that governs a beam, applied to a building standing on end.

That is the sense in which a tall building is a different structure rather than a bigger one. The lateral system is chosen by the height, and the height is limited by the lateral system, and the vertical load-carrying arrangement has almost nothing to do with either. What the two arrangements share is that the forces in both follow stiffness rather than load, so every part of the answer depends on every other part.

Second-order effects arrive last and decide the argument

A leaning building carries its own weight eccentrically, and the moment that produces is a load nobody applied.

The load that makes itself worse. The amplification of a deflection against the ratio of applied load to buckling load. A structure at half its buckling load deflects twice as far as first-order analysis predicts, and the curve runs away well before the load is reached.
Fig. 8 The amplification of sway by gravity acting on the deflected shape: 1/(1 − P/P꜀ᵣ), which is 1.25 at a quarter of the critical load and 10 at nine tenths. For a tall building the relevant ratio is the total gravity load against the buckling load of the lateral system, and it converts a stiffness question into a stability one.

For most buildings the amplification is 5–15% and the design deals with it by amplifying the first-order answer. For a very tall or very flexible one it becomes the governing consideration, and the honest reading is that the lateral system’s stiffness has stopped being a serviceability matter and become a stability matter: a building whose sway amplification approaches two is a building approaching its own buckling load, and no amount of member strength addresses that.

The choice is made before any of this is calculated

One more thing is worth saying plainly, because everything above reads as an optimisation and none of it is one in practice.

The lateral system is chosen at the first sketch, from a very short list, and on grounds that are mostly not structural: a core is where the lifts and the stairs are, so a building with a central core has one because the lifts had to go somewhere. A perimeter frame keeps the plan open and puts columns where the facade wants them. An outrigger costs a plant floor. A braced bay blocks a window.

What the arithmetic then does is tell the designer whether the arrangement that the building wants is stiff enough, and by how much it misses. The calculation is a check on a decision made by a plan, and that is a different activity from choosing the stiffest system available — which would be a braced tube on every building over twenty storeys, and which nobody builds because nobody wants a facade of diagonals over their windows.

The one place the structure genuinely leads is at the top of the range. Past about sixty storeys the systems that are stiff enough are so few that the structural arrangement dictates the plan, the facade and the internal layout — which is why very tall buildings look like each other and moderately tall ones do not.

What the picture cannot show

The wall is a prismatic cantilever with no openings in it. A real core is perforated by doors at every level, so it behaves as a pair of coupled walls whose stiffness depends on the beams over the openings — and those coupling beams carry enormous shears and are the most heavily worked members in the building.

The floors are rigid in their own plane and the model has one lateral freedom per level. Where a floor is long, thin, or has large openings, the two systems do not move together, the diaphragm bends, and the sharing computed above is optimistic.

Nothing here is three-dimensional. A building with its core off centre twists in plan under a wind that pushes it sideways, and the torsional response is often the case that governs the corner columns. That requires a plan model rather than an elevation, and it is where the missing three equations bite hardest.

Where the ladder goes

The first rung is the coupled wall — two walls and the beams between them — which is the commonest real core and whose behaviour interpolates between two independent cantilevers and one big one, depending entirely on how stiff the coupling beams are.

The second is the tube, where the perimeter of the building becomes the structure and the interesting quantity is shear lag: the corner columns take more than their share and the middle of each face takes less, so the tube behaves as though it were narrower than it is — the same effect a bolted angle suffers, at a hundred times the scale.

The third is the one this essay has treated as static and is not. Wind is a fluctuating load and a tall building’s response to it is dynamic; what a designer is really controlling with all of this stiffness is an acceleration at the top floor, and the limit that governs is a matter of what makes people uneasy rather than anything about the structure.

What this makes readable

Essays that name this one as a prerequisite.

Named alongside this one

Essays reaching for the same objects. Nobody chose these; they are what the concept index makes visible.

What links here

The 8 essays that link to this one and share the most of its objects, of 20 that link here.

The objects this essay names

Each one links to every other essay that touches it.

IndeterminacyInteractionLateral systemOutriggerShear wallStiffnessStorey driftSway