Concept

Influence line — where it appears

The value of one effect at one station, plotted as a unit load walks the whole structure. It answers where to put a load rather than what a load does, and its negative regions are where adding load reduces the effect.

Named by 17 essays across 6 fields — each of them below, with the objects they name alongside it.

Influence line for the bending moment at x = 3. The bending moment at one fixed station, plotted against the position of a unit load walking across the span. The beam was re-solved at 301 load positions. The worst position is x = 3.00, giving 2.100.

The worst place to stand

A bridge is not designed for a load. It is designed for a load that moves, and for every station along it there is a different position of that load that does the most damage.

internal-forces · Influence line
The worst position is not the obvious one. Three axles totalling 320 units, marched across a span of 20 in steps of 0.02. The envelope is the largest moment each station ever sees; its peak is 1160.2 at 9.88 along the span, which is 0.12 off midspan and occurs under the axle nearest the resultant rather than under the heaviest one. Barré's construction, which places midspan halfway between that axle and the resultant, independently gives 1160.3 at 9.88. The dashed curve is the envelope the same total weight would produce as one load rather than three: its peak is 1600.0, which is 38% more — spreading a load out is worth something.

The train that is worse than its heaviest axle

An influence line says where to stand one load. A vehicle is several loads at fixed spacings, and the worst arrangement never puts the heaviest one at the peak.

internal-forces · Influence line
Maxwell's reciprocal theorem. A load at one point and the deflection it causes at another, against the same load moved to the second point and the deflection read at the first. Both integrals return 93.3335, and neither calculation was told about the other. The two deflected shapes are entirely different; the two readings are identical.

The theorem that swaps the question round

Push here and measure there; push there and measure here. The two readings are identical, for every elastic structure, whatever its shape — and that fact turns an influence line into something a model can be asked for directly.

deflection · Reciprocity
The envelope is not a state of the structure. Every arrangement of the imposed load on three spans — 8 of them, since each span is loaded or not — drawn faintly, with the greatest sagging and greatest hogging at each station drawn over them. Each faint curve is a real state of equilibrium and satisfies the free-moment identity exactly: mid-span ordinate minus the mean of the end moments is wL²/8, to 3e-16 of it. The envelope satisfies it nowhere, missing by up to 23% — because it is assembled from different load cases at different stations and no arrangement of load produces it. seven of the 8 arrangements are needed to build it; the rest never govern anywhere.

The envelope is not a structure

A continuous beam whose imposed load may sit on any span has eight load cases, and every one of them is a genuine state of equilibrium. The curve the design is made against is not one of them — it is assembled from different cases at different stations, and it fails the identity all eight satisfy exactly.

equilibrium · Load arrangement
The worst speed is not the fastest one. Peak deck acceleration against train speed, for a 20 m span at 6.25 Hz under 10 axles 18 m apart. The spikes are not a numerical artefact and they are not about how heavy the axles are: a regularly spaced train is a forcing function with a frequency v/d, and where a multiple of it lands on the bridge's own frequency each coach arrives in step with the motion the last one left. The arithmetic is v = d·f₁/k, which puts peaks at 405, 203, 135, 101 km/h — all of them operating speeds. What fails first is the acceleration rather than any stress: ballast loses its interlock at about 3.5 m/s², and strength does not appear in the equation at all. Here the limit is first passed at 376 km/h.

The train that arrives in time with itself

A single load crossing a span is a mild problem. A train is not one load — its axles are regularly spaced, so the forcing has a frequency of its own, and where a multiple of it lands on the bridge's frequency each coach arrives exactly in step with the motion the last one left behind.

dynamics · Moving load resonance
Two answers added, and the answer to the two together, drawn on top of each other. A 8 m beam under a 60 kN point load at mid-span (152.38 mm), under 12 kN/m of uniform load (152.38 mm), and under both at once (304.76 mm). The sum of the first two is 304.76 mm, and the residual between it and the third is zero — not small, zero, to the last bit of the arithmetic. That exactness is not a numerical accident: the governing equation is linear in the load, so the response is a linear operator applied to it, and a linear operator distributes over addition by definition. Every calculation that adds one load case to another is standing on that one line.

The addition everything else rests on

Influence lines add, the unit-load method adds, moment distribution adds, load combinations add, and a stiffness matrix is linear by construction. All of it stands on one sentence with three hypotheses in it — and when they fail, two of the failures point in opposite directions.

deflection · Superposition
Influence line for the shear force at x = 10.5. The shear force at one fixed station, plotted against the position of a unit load walking across the span. The beam was re-solved at 301 load positions. The worst position is x = 10.56, giving 0.560.

Two diagonals, one of which is absent

A truss diagonal is sized for the shear in its panel, and near mid-span that shear changes sign depending on where the load stands. A member that can only pull cannot carry the reversed case, so the panel gets a second diagonal — and at any instant one of the pair is not there.

structures · Truss
Maxwell's reciprocal theorem. A load at one point and the deflection it causes at another, against the same load moved to the second point and the deflection read at the first. Both integrals return 307.5006, and neither calculation was told about the other. The two deflected shapes are entirely different; the two readings are identical.

An influence line is a deflected shape

Finding where a load has to stand to be worst means solving the structure once for every position it could stand in. Reciprocity says the answer is a single deflected shape — release the quantity being asked about, move it by a unit, and the shape the structure takes is the influence line.

deflection · Reciprocity
Two lines and a triangle: a three-hinged arch drawn. A three-hinged arch of 20.0 m span, springings at (0.0, 0.0) and (20.0, 0.0) m and the crown hinge at (10.0, 5.0), under 100.0 kN at 5.0 m. The right half carries no load, so it is a two-force member and its reaction lies along the line from its springing through the crown hinge. That line meets the load's line at K, 7.50 m up, and the left reaction must pass through K too. The triangle of the load and the two reaction directions gives the reactions as 90.1 kN at A and 55.9 kN at B, with a horizontal thrust of 50.0 kN — the values four equilibrium equations return, to 7e-15 kN. The shape of the rib entered nowhere.

The arch that is only its three hinges

A three-hinged arch's reactions come from three points and nothing else, so a parabola, a circle and a portal frame on the same hinges push on their abutments identically. Move a load across and the point where the reactions cross runs along two straight lines through the crown. That is the arch's influence line, drawn with a straightedge — and friction in the hinges it was built around blurs it.

equilibrium · Graphic statics
Putting a funicular through three points. Four loads — 40.0 kN at 3.0 m, 60.0 kN at 7.0 m, 30.0 kN at 12.0 m, 50.0 kN at 16.0 m — and three points the polygon must pass through: A and B at the springings and C, 5.0 m above their chord at 10.0 m. A trial pole, dashed, draws a polygon from A that ends 6.39 m below B. The ray through the trial pole parallel to its own closing line cuts the load line at Q, 95.0 kN from the top, which is the left reaction of a simple beam on A and B and does not depend on the pole at all. Every pole whose polygon passes through A and B lies on the line through Q parallel to A B; the one whose polygon also reaches C is 98.0 kN from the load line, which is the moment at C of that simple beam, 490.0 kN·m, divided by C's height above the chord. That is the three-hinged arch's thrust — the four equilibrium equations give 98.0 kN.

The polygon that runs out of freedom

A funicular polygon for given loads has exactly three freedoms, so it can be made to pass through three chosen points and no more. Three points is a three-hinged arch, and the drawing solves it. Take the crown hinge away and one freedom is left over. The drawing then offers a whole family of thrust lines and cannot say which one the arch uses — the rib's stiffness decides, and stiffness is not on the paper.

equilibrium · Graphic statics
The rib yields long before it would buckle. The largest combined stress, axial plus bending, anywhere in a 60 m two-pinned parabolic rib at a 12 m rise (EI 250,000 kN·m²) with a 12,000 mm² section 1,000 mm deep, against a factor on 15 kN/m of dead load over the span and 6 kN/m of live load over the left half together. Dashed: first order; solid: second order; dotted: the 355 N/mm² yield stress. First order, the rib reaches yield at a factor of 1.73; second order, at 1.18. The same load pattern, spread uniformly, would bifurcate the rib at a factor of 2.97, the right-hand edge — which is the number the eigenvalue reports and a number the rib never reaches.

The weight that bends a rib it cannot bend

A parabolic rib carries its own uniform dead load as pure thrust, with no bending in it at all. Put a live load on half the span and the rib bends in the shape of its own buckling mode from the first kilonewton, and the whole thrust, most of it from the dead load, multiplies that bending. The rib never reaches its buckling load. It yields well short of it, at a load its first-order check says it can carry.

stability · Arch buckling
A crossed hanger swings through nearly all of its force. The largest and smallest force in each crossed hanger of a tied arch of 100 m span and 17 m rise on 32 hangers, with 60 kN/m of dead load and a live load of 60 kN/m running on from either end, each bar running from the one to the other. The worst range is 678 kN, from 49 to 727, in hanger 11; the largest force anywhere is 756 kN. 6 of the 32 go slack at some stage, and the worst range is 90% of the largest force anywhere: the live load's shear passes through the crossed hangers as through a truss's web, and swings them from nearly nothing to nearly their most.

The hangers that carry the shear twice

Crossing a tied arch's hangers turns them into the web of a truss, which is why the tie stops bending. It also means a live load's shear passes through them, so as a load runs on from either end each crossed hanger swings from nearly nothing to nearly its most: on a 100 m arch the worst swings through 678 kN, 90% of the largest force in any hanger, where a vertical hanger swings through 194, half of its own. More dead load raises the force and leaves the range alone. The arrangement that is best for strength is the one that hands its hangers to fatigue.

structures · Network arch
A load between the posts racks the panel it stands in. Elevation of a Vierendeel girder of six 2 m panels, 1.5 m deep, its deck chord as stiff as its other chord and its posts, the load standing in the middle of its second panel; the racked shape exaggerated, the unloaded girder faint. The panel the load stands in carries most of its shear, and the deck chord there bends both as a Vierendeel chord and as a beam between its posts: 38 kN·m against 27 with the load at mid-span. The posts either side carry 56 and 11 kN·m, and the heaviest post 56.

The load that visits every panel

A Vierendeel girder checked for a load at mid-span is checked for one position of a load that, on a bridge, stands everywhere in turn. Crossing it, a 100 kN load puts 1.7 times the mid-span check's moment into the end panels' chords, loads the middle post that a central load leaves idle, and makes the deck chord a beam between its posts in every panel where its share of the shear is small. Equal chords stay the stiffest arrangement; a vehicle whose axles span a panel cannot stand in the middle of one.

structures · Vierendeel
A haunch moves the worst stress range to its toe. The stress range up the height of the first interior post of a Vierendeel girder of six 2 m panels, 1.5 m deep, every member of the same section (I = 117 × 10⁶ mm⁴, W = 780 × 10³ mm³), crossed by a 100 kN load, over one crossing: the plain post (dashed), and the post with 250 mm haunches 2.00 times as deep at both corners (solid); with the constant-amplitude limits 52.3 MPa for detail category 71 (dotted). Plain, the range is 78.3 MPa at the corner. Haunched, it is 43.3 at the corner and jumps to 61.2 at the toe, 250 mm along the post — the largest anywhere in it, 61.2.

The corner that counts its crossings

As a load crosses a Vierendeel girder, the moment at a post's corner changes sign when the load passes that post. A static check reads the peak, and the peak says the posts beside the supports work twice as hard as the middle one. Fatigue reads the range, and the range says every interior post works the same. A haunch at the corner lowers the corner's range and moves the worst of it to the haunch's toe — so a deeper haunch soon buys nothing, a longer one keeps paying, and a toe two detail categories worse than the corner cancels the haunch outright.

structures · Vierendeel
Whole spans miss the shear inside a span. The shear along three spans of 8.0, 8.0, 8.0 m, under 20 kN/m of dead load everywhere and 15 kN/m imposed: the largest and least when the imposed load stands wherever it raises or lowers the shear at each section (solid), and when it may only cover whole spans (dashed). At the supports the two agree. At the middle of the second span the exact envelope reaches 23.8 kN either way and the whole spans 10.0 kN; at a tenth of the way along it, 122.4 against 122.0.

The shear whole spans cannot find

A continuous beam is designed by loading its spans in patterns, whole spans at a time, and for the bending moment that is very nearly exact: the moment's influence line keeps one sign over each span, so a span is either worth loading or not. The shear's influence line changes sign at the section itself, inside the span, and no pattern of whole spans can load one side of a section and not the other. At the middle of the inner span of three equal spans the imposed shear is 0.198 qL; whole spans find 0.083 qL, and the straight line to qL/8 that is safe on a simple span finds 0.125.

internal-forces · Influence line
Lightened where it reverses, and the range follows. The stress range each post's corner sweeps over one crossing of a Vierendeel girder of six 2 m panels, 1.5 m deep, its chords all of one section (I = 117 × 10⁶ mm⁴, W = 780 × 10³ mm³), crossed by a 100 kN load: uniform posts, posts sized to their peaks, and posts sized to both their peaks and their ranges. Uniform, every interior corner ranges 76.1 to 78.3 MPa. Sized to peaks, the middle post's range is 150.8 MPa and its neighbours' 101.6, against the uniform girder's worst of 78.3. Sized to both, no corner exceeds 78.3 MPa.

The post sized by what it must survive

A Vierendeel girder's posts are usually all one section, and a crossing load gives them peaks that differ by a factor of two and ranges that barely differ at all. Size each post to its peak and the steel falls by a quarter — and the middle post, lightened to two-fifths of the chords, sweeps twice the stress range the whole girder used to, and lasts a seventh as long. Size each post to its range instead and the girder needs less steel than the uniform one, not more, because the posts that can be lightened are the ones at the ends.

structures · Vierendeel
Every member's stress range as the load crosses the uniform girder. The stress range in each post (at its worse corner) and in each panel's chords (at the worst of their four ends, axial force and moment together) of a Vierendeel girder of six 2 m panels, 1.5 m deep, every member at first of one section (I = 117 × 10⁶ mm⁴), crossed by a 100 kN load, along the span. The posts range 50, 78, 76, 76, 76, 78, 50 N/mm² from end to end; the chords 71, 92, 103, 103, 92, 71. The worst member is a middle chord at 102.8, the worst post 78.3.

The girder sized member by member

A Vierendeel girder's posts can be sized to the stress ranges a crossing load gives them, and the earlier essay found that this keeps the girder's fatigue life for a tenth less steel. With the chords counted too — their axial force and their bending together — the girder's worst member is not a post but a middle chord. Sizing every member to that one range takes a quarter of the steel out and keeps the life; the posts barely move when the chords are resized, and sizing the two in turn settles in four passes. Sized for strength instead, the same girder uses more steel and lives a third as long, and sized to a range a fifth below the worst it is lighter than the uniform girder and lives twice as long.

structures · Vierendeel

Named alongside it

The objects these essays reach for when they reach for this one.

Pattern loadingLoad arrangementMoving loadFatigueStiffnessSuperpositionVierendeelArchBending momentFree bodyIndeterminacyMoment envelope

All concepts