Stability

The column made of two columns

A solid column buckles when its bending stiffness runs out. A laced one has a second way to go — the lattice shears, the chords stay straight — and the two flexibilities add rather than the two stiffnesses. A battened column reaches 23% of its own Euler load and behaves as though its slenderness were twice what it is.

Assumes Strong enough and still falls over, The ends decide the length that matters and Which member moved the roof.

A solid column has one way to bend, and Euler counted it. A column made of two chords joined by a lattice has two: it can bend, as a solid column does, and the lattice can shear while the chords stay straight. The second mode is not available to a solid member at all, and it is what makes a built-up column a different object rather than a lighter one.

A built-up column has a second way to bendA 12 m column of two chords 300 mm apart, joined by double lacing. On the left it buckles the way a solid column does, by bending; on the right the chords stay straight and the lattice racks, which a solid column cannot do at all. Neither happens alone, and the two flexibilities add rather than the two stiffnesses — so the critical load is 1287 kN against an Euler load of 1341 kN, which is 96% of it, and the column behaves as though its slenderness were 80 rather than 79.bending, as a solid column doesP_E = 1341 kNracking, which a solid column cannotS_v = 31500 kN1/P꜀ᵣ = 1/P_E + 1/S_v → 1287 kNthe smaller of the two governs, and here it is the bending
Fig. 1 A 12 m column of two chords 300 mm apart with double lacing. On the left it buckles by bending, as a solid column does; on the right the chords stay straight and the lattice racks. Neither happens alone, and the two flexibilities add rather than the two stiffnesses.

The two stiffnesses are in series

Engesser’s result is one line, and everything on this page is a reading of it:

1Pcr=1PE+1Sv\frac{1}{P_{cr}} = \frac{1}{P_E} + \frac{1}{S_v}

where PE=π2EI/L2P_E = \pi^2 EI/L^2 uses the second moment of the whole built-up section, and SvS_v is the shear stiffness of the lattice — the transverse force per unit of shear strain, which for a lacing system is a truss-deflection problem and for battens is a frame one.

That is a harmonic sum, so the smaller term governs and the larger one is nearly irrelevant. Two flexibilities in series, exactly as a beam and its supports are in series and for the same reason: the two mechanisms happen one after the other along the same load path, so their displacements add.

For the column drawn, PE=1,341P_E = 1{,}341 kN and Sv=31,500S_v = 31{,}500 kN, so Pcr=1,287P_{cr} = 1{,}287 kN — 96% of Euler. A four per cent penalty, which is why laced columns are used at all.

Battens, and a factor of four

Three ways of joining two chords, and a factor of four between themThe same two chords at the same spacing, joined three ways. Double lacing puts two diagonals in every panel and is very nearly as stiff in shear as a solid web; single lacing has half of that; battens have no diagonal at all and work by bending the chords between them, which is why their shear stiffness is smaller by more than an order of magnitude. The worst of the three keeps 23% of its own Euler load and behaves as a column of slenderness 163 rather than 79.double lacingS_v = 31500 kN96% of Eulerλ 79 → 80single lacingS_v = 15750 kN92% of Eulerλ 79 → 82battensS_v = 406 kN23% of Eulerλ 79 → 163
Fig. 2 The same two chords at the same spacing, joined three ways. Double lacing gives a shear stiffness of 31,500 kN, single lacing half of that, and battens 406 — because a batten has no diagonal and works by bending the chords between them, which is a very much softer arrangement.
A built-up column has a second way to bendA 12 m column of two chords 300 mm apart, joined by battens. On the left it buckles the way a solid column does, by bending; on the right the chords stay straight and the lattice racks, which a solid column cannot do at all. Neither happens alone, and the two flexibilities add rather than the two stiffnesses — so the critical load is 312 kN against an Euler load of 1341 kN, which is 23% of it, and the column behaves as though its slenderness were 163 rather than 79.bending, as a solid column doesP_E = 1341 kNracking, which a solid column cannotS_v = 406 kN1/P꜀ᵣ = 1/P_E + 1/S_v → 312 kNthe smaller of the two governs, and here it is the lattice
Fig. 3 The battened version of the same column, with its racking mode drawn. Every chord segment between battens bends in double curvature and every batten bends with it — a Vierendeel frame, standing on end, and about as stiff in shear as one.
lattice SvS_v PcrP_{cr} as a fraction of PEP_E effective λ\lambda
double lacing 31,500 kN 1,287 kN 96% 80
single lacing 15,750 1,236 92% 82
battens at 1.2 m 406 312 23% 163

The battened column is the finding. Its nominal slenderness is 79 — a perfectly ordinary column — and it behaves like one of slenderness 163, which is at the far end of what any code permits. The chords have not changed, the spacing has not changed, and the whole of the difference is that a batten resists racking by bending while a diagonal resists it by stretching — which is the deflection that is not bending arriving in a place nobody expected it.

A diagonal is an order of magnitude stiffer than a bent member of the same size, which is the argument for triangulating anything and is exactly why a Vierendeel girder is expensive. A battened column is a Vierendeel girder stood on end and asked to be a column.

Which free body produced the shear stiffness

The lacing’s shear stiffness is a truss deflection, computed the way this collection computes truss deflections.

Take one panel of the lattice, of length aa, with the chords at spacing hh. Apply a transverse shear VV across it. In a double-laced panel each diagonal of length dd carries Vd/(2h)V d/(2h) — resolved from the shear — and stretches by Vd2/(2hEAd)Vd^2/(2hEA_d). That extension lets the panel rack by an angle, and assembling the geometry gives

Sv=nEAdah2d3S_v = \frac{n E A_d\, a\, h^2}{d^3}

with nn the number of lacing planes. Every term is a length or an area of the lattice, and not one of them is a property of the chords.

Every member's share of the movement, and they are not the members expectedA Pratt truss of six panels at a depth of 0.85, carrying 10 kN at each top node, with the movement of the bottom chord at mid-span attributed member by member. The unit-load sum δ = ΣF·f·L/EA gives 631.06 at EA = 1: 47.2% from four top chords, 28.5% from six bottom chords, 22.3% from six diagonals, 2.0% from five verticals. The single worst member is a top chord at mid-span at 14.8% of the whole. Each member is drawn at the width of its own share. The same deflection from a stiffness solution that shares none of this arithmetic is 631.06, a relative residual of 3.6e-15.δ = 631.06 read here10 kN at every top node — each member drawn at the width of its own sharetop chord (four members)47.2%bottom chord (six members)28.5%diagonal (six members)22.3%vertical (five members)2.0%the members that moved the roof, ranked — a symmetric pair is two members and appears twicetop chord, at mid-span14.80%F -52.9 × f -1.765top chord, at mid-span14.80%F -52.9 × f -1.765bottom chord, at mid-span8.77%F 47.1 × f 1.176top chord, near the left support8.77%F -47.1 × f -1.176bottom chord, at mid-span8.77%F 47.1 × f 1.176top chord, near the right support8.77%F -47.1 × f -1.176diagonal, near the left support6.20%F -38.6 × f -0.772diagonal, near the right support6.20%F -38.6 × f -0.772virtual work and a stiffness solution agree to 3.6e-15 — two methods sharing no arithmetic
Fig. 4 Which member moved the roof — the unit-load method attributing a truss’s deflection member by member. A lattice’s shear stiffness is that calculation applied to one panel and read as a stiffness, and the diagonals dominate it for the same reason they dominate a truss’s deflection.

For battens the same panel is a portal frame: the chords bend in double curvature between battens and the battens bend with them, giving

Sv=24EIcha2(1+2IchanIbh)    2π2EIcha2S_v = \frac{24 E I_{ch}}{a^2\left(1 + \dfrac{2 I_{ch} a}{n I_b h}\right)} \;\le\; \frac{2\pi^2 E I_{ch}}{a^2}

The batten spacing aa appears squared in the denominator, so halving the batten spacing quadruples the shear stiffness — which is the only handle a battened column really has, and the reason batten spacings look absurdly close on old drawings.

Moving the chords apart, twice

Here is the result that makes the subject worth an essay.

The chords can be moved apart for ever and the answer stops movingCritical load against the spacing of the two chords, with the lacing at a constant 60°. The Euler load rises with the square of the spacing because the chords are lever arms; the shear stiffness of the lattice does not rise at all, because at a fixed angle every length in the lacing scales together and the stiffness is scale-free. Their harmonic sum therefore runs into a ceiling at 31500 kN, and the spacing at which the column has spent half of what it will ever get is 1478 mm.50010001500200025003000020000400006000080000100000120000spacing of the chords (mm)critical load (kN)Euler, P_Elattice, S_vthe columnceiling 31500 kN
Fig. 5 Critical load against the spacing of the chords, with the lacing angle held at 60°. The Euler load rises with the square of the spacing; the shear stiffness of the lattice does not rise at all; and their harmonic sum runs into a ceiling at 31,500 kN.

PEP_E grows as h2h^2, because the radius of gyration is essentially half the spacing and the Euler load goes as its square. So far so obvious.

SvS_v does not grow at all. At a fixed lacing angle every length in the lattice scales together — aha \propto h and dhd \propto h — so Svhh2/h3S_v \propto h \cdot h^2 / h^3, which is a constant. The shear stiffness of a lacing system at a fixed angle is scale-free.

The harmonic sum of a term rising without limit and a term that does not move is a curve that approaches the fixed one. So:

PcrSvashP_{cr} \to S_v \quad\text{as}\quad h \to \infty

A built-up column cannot be made stronger than the shear stiffness of its own lattice, however far apart its chords are put. At 300 mm the column is at 96% of Euler; at 900 mm it is at 73%; at 3 m it is at 20% and has spent almost all of what widening will ever buy. The spacing at which the two stiffnesses are equal — the knee — is 1,478 mm.

Hold the panel length instead, and the ceiling becomes a maximumThe same column with the panel length held at 173 mm rather than the lacing angle. Now the diagonals get longer and flatter as the chords move apart, the shear stiffness falls away, and the critical load has a maximum: 7472 kN at a spacing of 1400 mm, past which a wider column is a weaker one. Which of the two sweeps applies is decided by whether the panel is set by the lacing or by something else — a connection, a floor level, a plate size.50010001500200025003000020000400006000080000100000120000spacing of the chords (mm)critical load (kN)Euler, P_Elattice, S_vthe columnbest at 1400 mm
Fig. 6 The same sweep with the panel length held at 173 mm instead of the lacing angle. Now the diagonals get longer and flatter as the chords move apart, the shear stiffness falls away, and the critical load has a genuine maximum: 7,472 kN at a spacing of 1,400 mm, past which a wider column is a weaker one.

Which of the two sweeps applies is decided by what fixes the panel. If the lacing angle is held — the usual detailing rule, 45° to 60° — the ceiling applies. If the panel length is set by something else, a connection spacing, a plate size, a floor level, then the second curve applies and there is an optimum spacing to be found.

Both curves say the same thing in different words: past some spacing, the lattice is the column.

What buys the shear stiffness

SvAdS_v \propto A_d, so the lattice’s own area is the direct handle:

AdA_d Pcr/PEP_{cr}/P_E
25 mm² 74.6%
50 85.4%
100 92.2%
200 95.9%
400 97.9%
800 98.9%

The curve is the familiar shape of a series combination — most of the benefit early, and a long expensive tail. Going from 25 to 100 mm² of lacing buys 18 points; going from 400 to 800 buys one. Lacing is sized generously because it is cheap and because the first hundred square millimetres do nearly all the work.

A brace is a stiffness requirement, not a strength oneCritical load against brace stiffness for a pinned column braced at mid-height. The curve climbs from the unbraced Euler load of 9.87EI/L² and flattens at 39.48EI/L², which is the Euler load of the braced segment — past that the column buckles in a shape the brace does not obstruct, and further stiffness buys nothing. A stiffness of 16EI/L³ is marked, reaching 13.09EI/L².010203040506001020304050brace stiffness (units of EI/L³)critical load (units of EI/L²)13.139.5 — braced9.87 — unbraced
Fig. 7 The same shape in the bracing problem: a brace needs a threshold stiffness and nothing beyond it. Lacing is bracing distributed along a member instead of applied at a point, and both curves flatten for the same reason — once the secondary system is much stiffer than the primary one, the primary one is what is left.

The ends still decide the length

The ends decide the length that mattersFour columns of identical height and section, buckling under four sets of end conditions. The effective length factor is the fraction of the column that behaves like a pin-ended one, and the buckling load goes as its inverse square.K = 0.5both ends fixedK = 0.7one fixed, one pinnedK = 1both ends pinnedK = 2fixed at the base, free at the topsame column, same section, four ways of holding the endsthe load at which each buckles goes as 1 ÷ K² — a factor of sixteen across this row
Fig. 8 And nothing here displaces the older argument. PEP_E in Engesser’s expression is the Euler load at the member’s effective length, so a built-up column with poor end restraint suffers the usual factor of up to sixteen before any of the lattice arithmetic begins.
The column curveFailure load against slenderness, as a fraction of the squash load. A stocky column crushes; a slender one buckles at the Euler load; the crossover is where the two curves meet, and real columns fall below both near it.5010015020000.20.40.60.811.2slenderness (effective length ÷ radius of gyration)they cross at λ = 76squashingEuler bucklingreal columns, which are neither
Fig. 9 The column curve the effective slenderness is read on. A built-up column is placed on it at λeff\lambda_{eff} rather than at λ\lambda, which is the whole practical content of the subject: the lattice’s flexibility is converted into an equivalent slenderness and the ordinary machinery takes over.

That conversion is how codes handle it. Rather than carrying a shear stiffness through every subsequent calculation, the loss is expressed as an increased slenderness — 79 becomes 163 for the battened column — and everything downstream is the column curve as usual.

Length costs more than it looksThe same column section at four lengths, with the buckling capacity of each drawn as a bar. Capacity falls as the inverse square of the length, so a column three times as long carries a ninth as much.1× the length100% of the capacity1.5× the length44% of the capacity2× the length25% of the capacity3× the length11% of the capacityidentical section, identical material, identical end conditions
Fig. 10 What that costs, in the currency this collection has used since the beginning. Capacity goes as the inverse square of the effective length, so doubling an effective slenderness quarters the capacity — which is the same arithmetic as making the column twice as long, and it has been bought with a batten detail.

Why anybody builds one

The whole of the above is a catalogue of penalties, and built-up columns are nevertheless everywhere. The reason is in the numerator of the ratio rather than in the fraction.

The one length a section carries into a columnFive profiles of equal area, with the radius of gyration r = √(I/A) drawn as the distance it is — a pair of lines either side of the centroid, at the depth the whole area would have to sit at to give the section the second moment it has. As a 4 m pin-ended column the same 3000 mm² of material carries between 7 and 3146 kN, in the ratio of the squares of those radii and of nothing else.the same, laid flatr = 4.3 mmλ = 9247 kNsquarer = 15.8 mmλ = 25397 kNtall rectangler = 57.7 mmλ = 691295 kNteer = 61.2 mmλ = 651454 kNI-sectionr = 90.0 mmλ = 443146 kNthe dashed pair is ±r about the centroidthe bar is the Euler load at 4 m, to scale
Fig. 11 The one length a section takes into a column: the radius of gyration, and the factor of 432 in Euler load it produces across five arrangements of the same steel. A built-up column is that argument continued past the point where the section stops being one piece.

A rolled section’s radius of gyration is bounded by its own depth, and its depth is bounded by what a mill will roll. The largest universal column has a radius of gyration of about 100 mm about its weak axis. Two of those chords put a metre apart have a radius of gyration of 500 mm — five times as much, and twenty-five times the Euler load, for the same weight of steel plus a lattice.

Set against a 4% penalty from double lacing, that is not a close contest. The three places it is taken up:

Where the length is very long. A transmission tower leg, a mast, a crane boom, a falsework tower. At slendernesses where a solid section would be hopeless, the lattice buys an order of magnitude and its own penalty is a rounding error.

Where the load is very large. A mill building’s crane column, a heavy industrial frame. Two or four chords carry the axial load between them and the lattice holds them apart, which is cheaper than rolling or fabricating a single section of the required area.

Where the member must be transported and assembled. A lattice is a kit of small pieces; a plate girder column is a single object needing a low loader and a large crane. That is why lattice masts and towers are laced and welded box columns are not.

And one place it is not taken up at all: where the connection cost dominates. A laced column at a 60° angle over 12 m has 69 panels and 138 diagonal ends, which is 138 welds or 276 bolts for a member with two ends. That is the real price of the four per cent, and it is why battens — with an eighth as many pieces and a shear stiffness eighty times worse — persist despite everything on this page.

Where the model stops

Engesser’s is not the only expression. Haringx’s alternative, Pcr=Sv(1+4PE/Sv1)/2P_{cr} = S_v\left(\sqrt{1 + 4P_E/S_v} - 1\right)/2, differs in what it assumes about how the shear force follows the deformed member, and it gives a higher answer. The difference matters only when SvS_v and PEP_E are comparable, which is exactly the battened case — so the one column where the answer matters most is the one where the two formulations disagree by most.

The chords have their own buckling problem. Between two lacing points a chord is a column of its own, of length aa and its own radius of gyration, and it can buckle locally before the whole member does. That check is why lacing panels are short and why it is not enough to make the lattice stiff.

The lacing carries a real force. A built-up column bows, the bow generates a transverse shear, and the lattice carries it — so lacing is designed for a shear that no applied load contains, usually taken as a percentage of the axial force. It is an imperfection-driven force, and it exists because the column is not straight.

And nothing here is inelastic. All of the above uses the elastic modulus, and a stocky built-up column yields before any of it applies.

The same arithmetic, three places on this site

The harmonic sum is worth recognising as a shape rather than as a formula, because it turns up wherever two mechanisms act in series along one load path.

Rankine’s column formula, 1/P=1/Py+1/Pcr1/P = 1/P_y + 1/P_{cr}, combines squashing and buckling the same way, and it was the practical column formula for the best part of a century for exactly the reason Engesser’s works: the smaller capacity governs smoothly and the transition is automatic.

A beam and its supports, where the two flexibilities add and the softer one decides how much of the movement belongs to which.

And a composite beam’s two limits, where a partial shear connection puts the interface stiffness in series with the section’s own.

In all four the useful reading is the same and it is about what to improve. A series combination is dominated by its weakest term, so effort spent on the stronger term is largely wasted — and the arithmetic says how largely. On the battened column above, doubling the chord spacing to 600 mm quadruples the Euler load, from 1,341 to 5,228 kN, and takes the critical load only from 312 to 661: a factor of four in the strong term bought a factor of 2.1 overall. Halving the batten spacing instead multiplies the shear stiffness by 7.5, from 406 to 3,027 kN, and takes the critical load to 930 — a factor of 3.0, from the term that was governing.

The question a series combination asks is never “how much” but “which one”.

What the pictures cannot show

The two modes in the hero figure are drawn separately, and they never occur separately. The real deformed shape is a single curve containing both, in a proportion set by the ratio of the two stiffnesses, and drawing that would show one curve where the argument needs two.

The lattice figures draw a panel count chosen for legibility. A real laced column at a 60° angle and 300 mm spacing has a panel of 173 mm over a 12 m length, which is 69 panels — too many to draw and exactly the number that makes the shear stiffness what it is.

And the sweeps run the chord spacing to three metres, at which point the object is not a column any more but a small tower with two legs. The curve is continuous and the engineering is not.

The ladder from here

Later rungs on this anchor: the local buckling of a chord between lacing points, and the interaction between it and the overall mode. Haringx against Engesser, and the elastomeric bearing where the disagreement is largest. The shear force in the lacing, and why it is specified as a fraction of the axial load rather than computed. Four-chord towers and masts, where the same arithmetic is applied about two axes at once and the lacing planes interact. Built-up columns in timber, where the connection is nails and the slip modulus does the work of the lacing area. And the historical case: laced and battened columns were the standard form for a century of iron and steel construction, and Engesser’s correction was published in 1891 after built-up columns kept failing at loads their second moment of area said were safe.

Named alongside this one

Essays reaching for the same objects. Nobody chose these; they are what the concept index makes visible.

What links here

Every essay whose body links to this one.

The objects this essay names

Each one links to every other essay that touches it.

BattenBucklingBuilt up columnChordEffective slendernessEngesserEuler loadLacingRadius of gyrationSeries combinationShear deflectionShear stiffness