Secondary system — where it appears
Named by 2 essays across one field — each of them below, with the objects they name alongside it.
The spectrum a floor hands on
Most of what breaks in an earthquake is not the structure. It is a transformer, a chiller, a rack, a ceiling, a pipe — and every one of them is bolted to a floor rather than to the ground. The motion it feels has already been through a filter with one very sharp tooth in it.
The pipe held at every floor
A riser runs the height of a building and is fixed at every floor, so each of its supports moves with a different floor. The floor spectrum prices the pipe's inertia, and for a pipe anchored at every floor the inertia is nearly irrelevant: the drift puts 131 N/mm² into a 100 mm riser at two thirds of a per cent, thirty times its inertia, and passes yield at 200 mm. Guide the same pipe instead of anchoring it and the drift almost vanishes — the pipe then feels only how much the drift changes from one storey to the next.
Named alongside it
The objects these essays reach for when they reach for this one.
Response spectrumAmplificationDampingFloor accelerationImposed deformationModal participationMode shapeResonanceRestraintSoft storeyStorey driftTransfer function