Concept

Panel zone — where it appears

The rectangle of column web between the flanges of the beams framing into a rigid joint. It carries the difference between the beams' flange couples and part of the columns' shear, usually more than either member's own shear, and is stiffened with doubler plates when it cannot.

Named by 4 essays across one field — each of them below, with the objects they name alongside it.

The moment does not stop at the end of the beam. A portal frame of 8 m by 4 m with fixed bases, carrying 20 kN/m on the beam. The bending moment is drawn on the tension side of every member, and it runs round the corner without a break: 65.2 kNm arrives at the end of the beam and 65.2 kNm leaves down the column, which is the same number, since joint rotational equilibrium is one of the equations the frame solve satisfied. Midspan carries 94.8 kNm, and the two add to 160.0 — the 160.0 kNm of a simply supported span, to 0.0e+0 kNm. The corner takes 61% of the wL²/12 a fully built-in beam would have carried, because the columns are springs rather than walls: the beam-to-column stiffness ratio is 1.27. The beam's moment crosses zero 0.92 m from the corner and the column's 1.33 m above its base.

The moment that goes round the corner

At a rigid knee the bending moment does not stop at the end of the beam. It turns and runs down the column, and in the same instant the beam's shear becomes the column's axial force — while the block of steel that has to carry the turn appears on no member diagram anywhere.

internal-forces · Corner moment
The interior panel is designed by the case that designs nothing else. The shear across the column-web panel at each kind of joint of a frame of two 8 m bays and two 4 m storeys with fixed bases, 457 mm beams and 254 mm columns with 8.6 mm webs, under five load cases, the worse direction of sway taken where there is one. Full gravity: roof corner 106, roof interior 0, floor exterior 143, floor interior 0 kN; One bay loaded: roof corner 115, roof interior 117, floor exterior 150, floor interior 154 kN; Sway: roof corner 25, roof interior 40, floor exterior 53, floor interior 89 kN; Gravity + sway: roof corner 131, roof interior 40, floor exterior 196, floor interior 89 kN; Pattern + sway: roof corner 141, roof interior 157, floor exterior 203, floor interior 242 kN. The floor interior panel is empty under full gravity and carries 89 kN under gravity with sway, the case that governs the members; under one bay loaded with sway it carries 242 kN — 2.7 times as much, more than any exterior panel's 203 kN, and 70 per cent of the web's shear resistance.

The panel that gravity leaves empty

A corner joint's panel carries the difference between a beam's flange couple and half a column's shear, and full gravity load is what makes that large. An interior joint has a beam on each side, and under full gravity their two couples cancel: the panel between them carries nothing at all, in the load case that sizes every member around it. It fills under the two loads that are not symmetric. A pattern load hands it one beam's moment, and sway hands it two beams' moments turning the same way. Together they put more shear through it than through any exterior joint, in a combination that governs no member.

internal-forces · Corner moment
What leaves the interior panel lands in the span. A frame of two 8 m bays and two 4 m storeys with fixed bases, 457 mm beams and 254 mm columns, with 20 kN/m on the left bay's beams only, against the stiffness of every beam-to-column joint as a multiple of the beam's EI/L, on a logarithmic scale. The shear across the floor interior joint's column-web panel (solid): 154 kN with rigid joints, 146 at EN 1993-1-8's rigid limit of 25 EI/L, 104 at 3.0 EI/L, 23 MN·m/rad, 63 at EI/L. The loaded beam's largest sagging moment (dashed), in kN·m: 71, 76, 102 and 126, against 160 for a simply supported span. The faint lines are EN 1993-1-8's boundaries for a frame that sways: nominally pinned below 0.5 EI/L, rigid above 25.

The panel a soft joint empties into the span

Under a load on one bay, an interior column's web panel carries the difference between the two beams' moments. Make the beam-to-column joints semi-rigid and the panel is relieved — by 5 per cent at the stiffness EN 1993-1-8 still calls rigid, by a third at three times the beam's EI/L — because a softer joint takes less moment. The moment it does not take lands at mid-span, where the beam was not designed for it, and in sway it lands in the columns. And soften only some of a frame's joints, and the sway goes looking for the ones still stiff: their panels carry up to a quarter more than they would in an all-rigid frame.

internal-forces · Corner moment
The loaded end stops; the unloaded one takes over. The moments at the four floor beam ends of the frame of two 8 m bays and two 4 m storeys, its beam ends joined to the columns by end plates of 3.0 EI/L initial stiffness and 120 kN·m resistance, under λ times 20 kN/m on the left bay and 20 kN at each floor, against λ: on the softening joints (solid) and on joints that keep their initial stiffness (dashed). At λ = 1 the loaded beam's inner end carries 78 kN·m and the unloaded beam's inner end, across the same column, 13. The loaded end reaches its resistance at λ = 2.69; at λ = 3 the four ends carry 89, 120, 81, 88 kN·m, against 97, 235, 39, 68 on stiff joints. The unloaded inner end has gone from 13 to 81, 6.2 times as much for three times the load.

The joint that softens under its own load

A bolted end plate is stiff until its moment passes two thirds of its resistance and then softens until, at its resistance, it is a third as stiff. Put such joints at every beam end of a frame under a pattern load and a push, and the most loaded joint softens first and hands its share across the column to the joint on the other side, which carries six times as much for three times the load. The redistribution grows as the frame approaches its strength. Every joint ends at its own stiffness, so the single secant stiffness an elastic analysis is allowed asks the loaded joint for half as much again as it can carry, and gives the exterior panel three quarters of what it gets.

internal-forces · Corner moment

Named alongside it

The objects these essays reach for when they reach for this one.

Pattern loadingPortal frameSwayJoint equilibriumRigid jointContinuityContraflexureEnd plateFlange coupleFree body diagramHaunchJoint stiffness

All concepts