The gap is a sum of five things and only one of them is computed. What a 30 mm movement joint is asked to accommodate, by three combination rules. The top bar is every term at its extreme, added: 33.2 mm, which assumes the hottest day, the fullest floor, the whole of the shrinkage and the worst-placed wall arrive together. The chance of that is about 1.5%. The bottom bar treats them as independent and asks for 16.0 mm. The middle bar is the rule used for actions and almost never for movements — one term at its full value and the rest at their coincidence factors — and gives 25.5 mm. The segments across the top bar are the terms themselves, and the ordering is the finding: the largest is tolerance at 10.0 mm, which is not a structural quantity at all, and the smallest is deflection at 3.2 mm — the only one anybody computes carefully, and 10% of the total. Deflection

The gap nobody computed

A movement joint is sized by adding up everything the structure will do to it, and the deflection calculation — the only term anybody computes carefully — is usually the smallest one in the list. The largest is a construction tolerance, which is not a structural quantity at all, and the sum of the extremes is nearly twice what treating them as independent would ask for.

Every reason a building is stiffer than its model, added up. The computed natural frequency of a floor, and the same frequency after each source of stiffness that was deliberately left out is put back. Not one of them is a modelling error. Cladding and partitions are stiffness nobody is allowed to rely on for strength; a nominally pinned connection is never pinned; a slab acts with its beam whether or not shear connectors were provided; and concrete between the cracks is stiffer than a cracked section assumes. Together they multiply the stiffness by 1.83 and the frequency by 1.35, because a frequency is the square root of a stiffness, and every factor is halved on the way through. The asymmetry is the finding: leaving stiffness out makes a deflection conservative and a vibration check unconservative in the direction that matters, since a stiffer floor has a higher frequency and sits further from the footfall range. The model here reads 4.40 Hz against a 5.2 Hz criterion and fails it; the floor reads 5.95 Hz and passes. The correction that would have got it right is exactly the stiffness nobody is willing to count on. Deflection

Stiffer than the model said

Measured natural frequencies of finished buildings come out between ten and sixty per cent above the values computed for them, consistently and in one direction only. Nothing on the list of reasons is a modelling error: every one is a real source of stiffness deliberately left out — and leaving stiffness out is conservative for deflection and unconservative for vibration.

Ten decades of time for forty per cent of the strength. Strength as a fraction of the five-minute test value, against the length of time the load is held, over 12 decades of seconds. The relation is a straight line on this axis, which is the reason a single duration factor works at all: every decade of time costs about the same amount of strength. A load held for 60 years leaves 59% of the short-term strength, and the member need not have moved — this is not creep, and it is not fatigue, because nothing about the load varies. It is that a static stress slowly breaks fibres. The curve has an asymptote at 18% that nobody quotes: below about a fifth of its short-term strength a member has no time to failure at all, so there is a stress under which duration stops being a question rather than merely becoming a small one. Materials

The load that was left on too long

A timber beam that carries a load for fifty years fails at about fifty-nine per cent of the stress the same beam carries for five minutes in a testing machine. Nothing about the load varies, the member need not have deflected, and the relation between the two is a straight line on a logarithmic time axis over ten decades.

The strength was bought in a furnace and the welder gives it back. Proof stress as delivered and beside a weld, for four aluminium alloys. The heat-treated alloys lose half of it: the strength of a 6xxx extrusion is in precipitates formed by an ageing treatment, and the arc dissolves them for 32 mm either side of the weld, permanently. The work-hardened tempers lose nearly as much, because the heat undoes exactly the work. The annealed ones lose nothing at all, because there is nothing left in them to anneal. The consequence is the crossover: 5083-H22 is 1.04 times 6061-T6 as delivered and 0.92 times it once welded, so the stronger alloy is the weaker member. The 240 mm member drawn, with two longitudinal welds, keeps 87% of its parent capacity — a weld along a member softens a strip and leaves a section, and the same weld across it softens the whole of one. Materials

The strength the welder gives back

A 6082-T6 extrusion is twice as strong as a 5083-H111 plate and, welded across, the two are within a few per cent of each other. The heat of the arc anneals the metal for thirty millimetres either side, permanently, and the strength that was bought in a furnace is given back at the first joint.

The bearing that is drawn as a roller. The horizontal force a sliding bearing delivers, against the vertical load it is carrying, with its coefficient of friction on the same picture. The coefficient is not a constant: PTFE's falls as the contact pressure rises, and the standard fit is μ = 1.2/(10 + σ), so the bearing drawn is at 30.0 N/mm² and μ = 0.030 while the same bearing at a fifth of the load is at 0.075 — 2.5 times as much. The force curve is therefore strongly non-linear: a fifth of the load gives 50% of the force. Two readings follow and only one of them is usually taken. The largest force is at full load, 108 kN, and that is what the pier is designed for. The largest nuisance is at light load, where 54 kN of friction is 39% of the 140 kN of wind the bearing was put there to release the structure from. Cold makes it worse again: below about −5 °C the same bearing delivers 216 kN. A roller symbol on a drawing means this, and it is a pair of load cases rather than one, because friction opposes whichever way the deck happens to be going. Connections

The roller that is not a roller

A sliding bearing is drawn as a roller and detailed as a sheet of PTFE, and it delivers a horizontal force of a few per cent of whatever it is carrying. The coefficient everybody quotes is the one at full design pressure, and PTFE's coefficient rises as the pressure falls — so the bearing is at its freest exactly where nobody checks it.

Four details, and no material anywhere on the plot. Stress range against cycles to failure for four detail categorys — 160, 112, 71, 36 N/mm² at two million cycles. The lines are parallel because they share a slope of three, and the spread between them is a factor of 4.4 in stress and therefore 88 in life. Nothing on this plot depends on the strength of the steel: the same detail in a grade twice as strong lies on the same line. At a stress range of 62 N/mm² the lives are 160: unlimited, 112: 2.1e+7, 71: 3.0e+6, 36: 3.9e+5 cycles. The knee in each line is the constant-amplitude limit, past which the slope becomes five. Connections

The detail decides and the steel does not

A fatigue check contains no material strength anywhere. The same detail in a steel twice as strong lies on exactly the same line, because a fatigue life is decided by the geometry of a weld and by the stress range it sees — and two per cent of the traffic does most of the damage, because life goes as the inverse cube of the range.