The joint stronger than its beam
Assumes The moment that goes round the corner, Neither pinned nor rigid, which is every real connection and After the first yield, which is not the end.
A rigid knee carries the beam’s moment round the corner into the column; a real one does it through bolts and a plate that turn as they carry it. The joint that softens under its own load put bolted end plates at every beam end of a two-bay frame and let them follow EN 1993-1-8’s curve: straight up to two thirds of the joint’s resistance, then softening, until at its resistance the joint is a third as stiff as it began. Every joint there was weaker than its beam, so the joints were the frame’s fuses. The most loaded one softened first and reached its plateau, and the frame sent its share across the column to the joint on the other side.
That essay ended on the other kind of joint: one at least as strong as the beam it joins. A full-strength joint never reaches its plateau, because the beam beside it reaches its plastic moment first and hinges there. The question it left is whether the joint’s curve still matters. The joint softens on the way to the beam’s strength, and softening sheds moment. If it sheds enough, the beam’s first hinge comes later, and the joint’s curve is a question of strength. If the beam yields before the joint has done anything, the curve is only about stiffness, and a designer who chose a full-strength joint can forget it.
A frame whose beams are its fuses
The frame is the same two bays of 8 m and two storeys of 4 m, loaded by λ times 20 kN/m on its left bay and 20 kN at each floor from the left. Its beams have a plastic moment of 405 kN·m. Its columns are heavier than before, with a plastic moment of 538 kN·m, so that the beams are what yields — the order a designer wants, and the one that makes a beam’s own mechanism the frame’s.
That mechanism needs no analysis. The loaded beam fails when it has hinged at both ends and in its span, and a beam with the plastic moment at its two ends and its middle carries kN/m: λ = 5.06. No full-strength joint can change that number, because no full-strength joint can be the place a hinge forms. What a joint can change is the order in which the three hinges arrive, and the load at which the first of them does.
The first hinge matters. It is the load at which the frame stops being elastic, where a plastic analysis begins counting rotation and an elastic one has already stopped. It sets how far a frame designed elastically is from its limit, and how much rotation the beam’s hinges must find between the first and the last.
How much of the curve lies below the beam’s strength
EN 1993-1-8’s curve is straight up to two thirds of the joint’s resistance and softens above it. For a full-strength joint the part that matters is the part below the beam’s plastic moment, since the beam hinges there and the joint goes no further. A joint exactly as strong as its beam softens from 270 kN·m, two thirds of 405, and by the time the beam yields it has turned 6.4 mrad, three times what its initial stiffness would give. A joint 1.2 times as strong softens from 324 kN·m and has turned 3.9 mrad. A joint 1.5 times as strong begins to soften at exactly 405 kN·m, the moment at which its beam hinges, and so never softens at all.
So “full strength” is not one kind of joint. Every full-strength joint is protected by its beam, but a joint barely stronger than its beam is soft for its last third, and one half as strong again is straight to the end.
The softening holds the inner end back
The loaded beam’s inner end carries the most moment: the gravity load on that bay and the push from the left both hog it. With joints of 25 EI/L kept linear it reaches 405 kN·m at λ = 3.51. Let the joint soften and the inner end’s moment bends away from its straight line as it passes 324 kN·m, the joint’s two thirds, and reaches the plastic moment at λ = 3.78 instead. The moment it did not take has gone into the span, whose line rises a little more steeply, and into the outer end — the same emptying of a joint into its span that the panel a soft joint empties into the span found for joints soft from the start, arriving here only near the beam’s strength.
After the inner end has hinged, the two analyses are the same frame. The hinge carries 405 kN·m whatever the joint does, and the other joints are still on the straight parts of their curves, so the span reaches the plastic moment at λ = 4.78 in both. The softening buys the frame a later first hinge and nothing after it.
That 3.51 is itself later than rigid joints give. A rigid frame puts its first hinge at λ = 3.25; joints of 25 EI/L, the stiffness EN 1993-1-8 calls rigid in an unbraced frame, are still flexible enough to shed 8% of it. A rigid classification is a statement that the joint’s flexibility may be ignored in working, as neither pinned nor rigid put it, and not a statement that the frame yields where a rigid frame would.
Why the collapse cannot see the joint
That the collapse load does not move is not a property of this frame. It is the plastic collapse theorem, which after the first yield used for a single beam: a structure that can form enough hinges to become a mechanism collapses at the load that mechanism needs, and the elastic history on the way — every stiffness, every residual moment, every softened joint — decides only the order in which the hinges arrive. Nothing elastic appears in .
What the theorem asks in return is that every hinge can rotate for as long as the others take to form. A first hinge at λ = 3.25 has to keep turning at its plastic moment until λ = 5.06; a first hinge at λ = 4.52 has to keep turning only from there. So the softening that delays the first hinge does not raise the collapse load, but it shortens the stretch over which the first hinge must turn while carrying its full moment — the redistribution the moment that was moved on purpose did by design, done here by the joint’s curve without anyone choosing it. A frame whose first hinge comes at 89% of its collapse needs much less ductility from that hinge than one whose first hinge comes at 64%.
This is the sense in which the full-strength joint’s curve is a strength question after all. It cannot change what the frame carries, but it changes what the frame’s hinges must survive to carry it.
A joint half as strong again does not soften
The weaker the full-strength joint, the more of its curve lies below the beam’s strength and the more it sheds. A joint exactly as strong as its beam delays the first hinge to λ = 4.15, 18% later than the same joint kept linear. At 1.2 times the beam’s strength, 3.78, 8% later. From 1.5 times the beam’s strength on, the softening starts at the plastic moment and buys nothing.
That last number is worth knowing for a reason that has nothing to do with this frame. Seismic design asks a beam-to-column joint to be stronger than its beam by a margin for the steel being stronger than specified and for strain hardening, which comes to about 1.4 times the beam’s plastic moment. A joint designed to that rule is nearly straight up to the beam’s hinge: in this frame it delays the first hinge from 3.51 to 3.60. The rule exists to make the beam yield and the joint stay out of it, and its consequence is that the joint’s curve barely matters before the beam yields.
Too much shedding hands the first hinge to the span
A softening joint behaves, below the beam’s strength, like a joint of lower stiffness. So the question of how much softening helps becomes a question of how much flexibility helps, and flexibility does not help without limit.
As the joint’s initial stiffness falls from 100 EI/L, the first hinge comes later, because the beam’s end takes less of the load and the span more. That works until the span is carrying as much as the end. Below about 10 EI/L the span reaches the plastic moment first, and from there a still more flexible joint makes things worse: it pushes more moment into a span that is already the first to yield. At 3 EI/L the first hinge is in the span at λ = 3.91.
The first hinge comes latest at the stiffness where the beam’s end and its span yield together. For a joint 1.2 times as strong as its beam and softening, that is about 10 EI/L, where the first hinge arrives at λ = 4.52, 89% of the collapse load. Kept linear, the same balance is reached at about 5 EI/L and λ = 4.31. The softening moves the balance to a stiffer joint, because a joint that softens near the beam’s strength is stiffer in working and softer exactly when the beam’s end is approaching its limit.
That balance is the inelastic relative of the joint that was chosen, whose stiffness made a single beam’s end and span moments equal so that the beam could be sized for the smaller of two numbers. There the balance was elastic and set by stiffness alone. Here it is set by the stiffness and the curve together, in a frame being pushed sideways, and its reward is not a smaller beam but a first hinge that arrives near the collapse rather than at two thirds of it.
At working load the curve is invisible
At working load no full-strength joint in this frame has come anywhere near two thirds of its resistance. That is the opposite of the situation the redistribution nobody chose described, where a connection assumed to be a pin carried moment in service that no analysis had given it; here the joint behaves in service exactly as its initial stiffness says, and its surprises are saved for the approach to the hinge. The most loaded end carries about 115 kN·m at λ = 1, and a joint 1.2 times as strong as the beam does not soften until 324. So the drift a serviceability check reads is set by the joint’s initial stiffness alone — 5.4 mm with rigid joints, 5.8 with joints of 25 EI/L, 6.6 with joints of 8 — and a softening joint and the same joint kept linear give the same number to the tenth of a millimetre. They part only above λ = 2.8, where the inner end passes 324 kN·m.
That divides the joint’s two properties cleanly between the two checks that use them. Its initial stiffness is a working-load property, and its curve is a property of the approach to the first hinge. A full-strength joint chosen for its drift has had one of its two numbers chosen; the other decides when the beam starts to yield.
The rotation the joint spends first
The delay is not free. A joint that sheds moment does so by turning, and a joint exactly as strong as its beam has turned 6.4 mrad by the time the beam beside it hinges — three times what its initial stiffness would give, and all of it inside the bolts and the plate before the beam has done anything plastic. A joint 1.2 times as strong turns 3.9 mrad, and from 1.5 times the beam’s strength the joint turns only its elastic 2.1.
What comes after is the beam’s. Once the beam has hinged beside the joint, the joint’s moment stays at the beam’s plastic moment and the joint turns no further; the plastic rotation the frame needs between its first hinge and its collapse is supplied by the beam, which is what a full-strength joint was chosen to arrange. That is the difference from the joint that has to keep turning, a partial-strength joint that hinges first and must go on rotating at its full moment until the span catches up, and whose ductility therefore decides whether the collapse load is reached at all. A full-strength joint asks its own ductility for only the softening below the beam’s strength — a few milliradians, which a well-detailed end plate has — and hands the rest to a rolled section.
The first hinge, by hand
With rigid joints at λ = 1 the loaded beam’s inner end carries 124 kN·m, so the first hinge comes at . With linear joints of 25 EI/L it carries 115, and the hinge comes at .
A joint 1.2 times as strong as the beam has a resistance of 486 kN·m and softens from . At the beam’s 405 its stiffness modification is , so its secant stiffness there is EI/L. Every joint in the frame kept linear at that secant would put the first hinge at λ = 3.72, a little earlier than the softening joints’ 3.78. The two are not the same frame: the uniform secant makes every end that soft, while the softening joints are that soft only at the one end approaching the beam’s strength, and stay at their initial stiffness everywhere else. A single reduced stiffness is a fair stand-in for a full-strength joint’s curve, as it was not for the partial-strength joints that softened under their own load, because only one joint in the frame is on the soft part of its curve when it matters.
The collapse needs the plastic moment at both ends and in the span: , so kN/m, λ = 5.06.
Where the strong-column frame stops
The columns stay elastic. They are chosen heavier than the beams, and at the beam’s collapse the largest column moment is about 450 kN·m against a plastic moment of 538. A frame with weaker columns would hinge them first, and its mechanism would be a sway of the storey rather than the loaded beam’s.
The span has no hinge of its own. Every curve stops where the span reaches the plastic moment, which is the last state the model describes; the collapse is the beam’s mechanism, which needs no analysis. Between the span’s hinge and the outer end’s, which this model cannot follow, the frame is stiffer than a mechanism and softer than an elastic frame.
The joint’s curve is the standard’s. EN 1993-1-8’s curve is a design idealisation of tests: the exponent 2.7 is a bolted end plate’s, and a welded joint, whose curve is stiffer and straighter, would shed less. Strain hardening in the beam would raise its moment past 405 kN·m and drive a barely full-strength joint further up its curve, towards its own resistance — the case a seismic overstrength rule exists to prevent.
Every joint is the same. A designer can choose different joints at different ends. A softer joint at the inner end alone would delay the first hinge where it forms without sending moment into the outer end, which is where this leaves off.
Still open: the joint chosen end by end
Every joint here is the same, so the balance between end and span was reached by softening every joint at once. The loaded beam’s ends are not equal: the inner end is hogged by the gravity load and the push together, and the outer end by the gravity load against the push. A frame whose inner joints were made softer than its outer ones — or whose inner joints were made barely full strength while its outer ones were made strong — would shed moment only from the end that yields first, and could bring the inner end, the outer end and the span to the plastic moment almost together. Whether a frame tuned that way reaches its first hinge at nearly its collapse load, and whether a push from the other side, which reverses which end is the inner one, undoes the tuning, is the question the moment that was moved on purpose puts to a joint chosen to move it.
Named alongside this one
Essays reaching for the same objects. Nobody chose these; they are what the concept index makes visible.
- The base that sends the wind to the knees joint stiffness · mechanism · plastic hinge
- The roof that makes the wind worse every storm joint stiffness · mechanism · plastic hinge
- A determinate truss has no robustness at all mechanism · redistribution
- Any structure will carry the unit load mechanism · plastic hinge
- Four corners and a mechanism mechanism · plastic hinge
- How much of the plate is bending end plate · joint stiffness