The column the unit load walks past
Assumes One deflection, without solving everything, The load that makes itself worse and The column that leans on its neighbours.
The check that cannot see the beams carried a unit load from the roof of a four-bay, ten-storey concrete frame down one line of its columns, as a cantilever with every beam cut away — the trick one column is enough to find the sway had found in a single portal — and found that the roof sway is that line’s real column moments integrated against the unit load’s, forty numbers by hand. The check was exact for any beams and any joints. That was its virtue and its limit: the unit load never enters a beam, so the check confirms the analysis’s arithmetic and says nothing about the stiffness it assumed.
Every column in that frame was part of the moment frame. Most buildings are not like that. A few lines of columns, rigidly joined to their beams, carry the wind; many more carry only gravity, pinned at every floor, leaning on the frame as a prop leans on a wall. A leaning column has no moment anywhere, so it can have no share in any column line’s integral. But its load acts through the sway, and in a second-order analysis it adds to the moments in the frame. The essay ended by asking whether a one-line check of a second-order analysis needs a term for the leaning columns, and whether, given one, it could see what a first-order analysis misses.
The answer is in two halves, and they are the two halves of the principle of virtual work.
Four times the frame’s own gravity, leaning on it
The frame is the same: four bays of 8 m, ten storeys of 3.5 m, 600 mm square columns, 400 by 700 mm beams carrying 40 kN/m, and 40 kN of wind at every floor, half at the roof. The beams are taken at 0.35 of their gross stiffness, the allowance usually made for cracking in a second-order analysis of concrete. The frame’s own gravity is 1,280 kN a floor.
Beside it stands a line of gravity columns, pinned top and bottom in every storey, tied to the frame at each floor by a link as stiff as a beam. They carry four times the frame’s own gravity, 5,120 kN a floor — a building whose gravity columns hold four fifths of its weight, which is an ordinary proportion. To first order they do nothing to the sway, because a pinned column carries vertical load straight down and offers no lateral resistance. To second order they push: a column carrying a load P, leaning by a drift δ over a storey of height h, needs a horizontal force of P·δ/h at its top to stay where it is, and the frame provides it.
The frame’s own gravity adds 4 per cent to its sway, from 33.3 mm to 34.7; the leaning columns add another 21 per cent, to 42.0. The ratio of 42.0 to 33.3 is 1.26. A designer working to the usual rule — that second-order effects may be neglected when they add less than a tenth — would find them necessary here only because of the gravity columns, which the frame’s own analysis model may not contain.
The integral needs no extra term
Now carry the unit load down the windward line exactly as before, and integrate the second-order analysis’s own column moments against it, storey by storey. The integral gives 42.0 mm at the roof, and at every floor below the roof the same integral, stopped at that floor, gives that floor’s second-order sway. There is no term for the gravity, the leaning columns or the geometric stiffness. The dots in the figure are on the lines.
That seems to contradict the usual way second-order analysis is taught, in which the principle of virtual work grows a term for the axial forces acting through the rotations. It does not, because that term belongs to the other reading of the principle. The unit-load method is the reading in which the forces are imaginary and the displacements real. The virtual system — a unit load at the top of the line, a unit reaction and a moment at its base — is in equilibrium in the undeformed geometry, and any structure will carry the unit load that is statically admissible. The real system enters only through its curvatures, and the real curvature of a column is its real moment over its stiffness, whatever produced that moment.
Put more plainly, the integral is a statement about the shape of one line of columns. The top of a column line fixed at its base has moved sideways by the integral of its curvature times the lever arm to the top, because that is what a bent line is. If the second-order analysis’s moments are right, the curvatures are right, and the line’s top is where the analysis says. Counted, not checked said of the leaning column that a member with no lateral stiffness still decides a storey’s critical load; here a member with no moment is simply not on the path the unit load takes. The gravity is in the column moments already, which is the only place the check looks.
The check that passes the analysis that forgot them
That is the property that makes the column-line check cheap for a second-order analysis, and it is also what makes it blind to the commonest omission in one.
The analysis that models only the frame — its own beams’ loads, nothing for the gravity columns — sways 34.7 mm. Its column moments are smaller, and integrated against the unit load they give 34.7 mm. The analysis that includes the leaning columns sways 42.0, and its column moments give 42.0. At eight times the frame’s own gravity, a building whose gravity columns hold eight ninths of its weight, the complete analysis sways 53.6 mm and its check agrees; the forgetful one still says 34.7, and its check still agrees with it.
A compatibility check cannot see a load that was never applied. Every analysis is a structure that is compatible with itself: its moments bend its columns into a shape, and its sways are that shape’s. The leaning columns are a load, not a stiffness, and an analysis that leaves out a load is a different structure under a different loading, entirely consistent with itself. This is the earlier essay’s finding about the beams, met again in the other direction. There the check could not see the analysis’s stiffness assumptions because they were in both of the numbers it compared. Here it cannot see the analysis’s loading, for the same reason.
Turning the principle the other way round
The principle of virtual work has a second reading, in which the forces are real and the displacement is imagined. Give the real frame, in its real swayed position, a small imaginary sway of one storey: every column of that storey turns through the same small angle about its foot, as a mechanism with hinges at both ends of each column, and everything above the storey moves sideways by the same amount. The real forces then do work on that imaginary motion, and for the frame to be in equilibrium the work must add up to nothing.
The wind above the storey does work by moving sideways with it. The columns’ end moments do work by turning through the hinge rotations, and that work, per unit of imaginary sway, is the storey’s total column shear. And the gravity above the storey does work too, because the frame is already leaning: in the real swayed position every vertical load above the storey stands on columns tilted by the drift over the height, and an imaginary further sway drops it a little, by that tilt. The leaning columns’ load is in that last term, along with the frame’s own, and there is no way to leave it out. The term is the whole of the gravity above the storey, times the storey’s drift, over its height.
In the complete analysis the three terms balance in every storey: the columns carry the wind and the gravity’s lean together. In the ground storey the columns carry 444 kN of shear, of which 380 is the wind above and 65 the gravity of the whole building leaning over a drift of 3.6 mm in 3.5 m. In the second storey the P–Δ shear is 112 kN against 340 of wind, a third as much again. It is largest relative to the wind in the second to fourth storeys, where the drifts are biggest and most of the building’s weight is still above.
This is the same equation the load that is really a lean found behind every notional load: a vertical load acting through a tilt is a horizontal force of the tilt times the load. There the tilt was an erection tolerance. Here it is the sway the wind has caused, and the equation is the storey’s equilibrium in the position the frame has actually reached.
What a checker brings to it
The difference between the two readings is what each asks the checker to supply. The column-line check takes everything from the analysis, the moments and the sways, and asks only whether they agree. The storey check takes the column moments and drifts from the analysis but takes the gravity from somewhere else: a load take-down, done once for the foundations, which knows nothing about which columns are in the frame model and which are not. That independent number is what makes it a check on the loading.
The complete analysis balances to within 2 per cent of the wind in every storey, the residue being the small differences between one column line’s drift and another’s. The analysis that forgot the leaning columns is short in every storey by exactly their missing lean: 12 per cent of the wind in the ground storey, 22 per cent in the third. Its column shears are what its own, smaller, gravity requires and no more. The first-order analysis is short by more again, 14 and 26 per cent, because it carries none of the gravity’s lean at all.
The shortfall is the check’s verdict, and it says which storey is underdesigned and by how much. It costs one line a storey: the sum of that storey’s column end moments, divided by its height, against the wind above plus the total gravity above times the drift over the height. A storey of this frame has five columns, so the whole check is a hundred end moments and ten drifts, about twice the column-line integral’s forty numbers and of the same order of effort.
How large the lean is
The ratio of the P–Δ shear to the wind shear, computed with the first-order drift, is the stability index θ of each storey, and the usual estimate of how much second-order effects grow a storey’s drift is 1/(1 − θ). With the leaning columns included, that estimate can be compared with what the second-order analysis actually found.
The index reaches 0.26 in the third storey, where the predicted growth of 1.36 is close to the 1.32 the analysis found. In the ground storey it is wrong the other way: θ is small, because the ground storey’s drift is small on its fixed bases, and the predicted growth is 1.16, but the storey’s drift actually grows by 1.25. The ground storey’s top is the first floor, whose rotation is set by the storeys above as much as by the ground storey’s own columns, and those storeys are leaning harder. The stability index treats each storey as if it swayed alone, which is the same simplification the earlier essay found in the drift: a storey’s drift is mostly the rotation of the floor below it, and the floor’s rotation belongs to the whole frame.
So the index is a good estimate where it matters most and an underestimate at the base, by about 8 per cent here. The column that leans on its neighbours found that sway buckling is a property of a storey rather than of a member; the ground storey’s numbers say that, in a frame of many storeys, the amplification of a storey is not quite a property of the storey either.
What the lean costs the columns
The design consequence is in the moments, and it lands where the moments were already largest.
The windward column’s base moment is 184 kN·m to first order and 192 with the frame’s own gravity leaning. The gravity columns at four times the frame’s load bring it to 236, 23 per cent more than the analysis that forgot them; at eight times, 304. The base moment grows a little faster than the leaning load — 44 kN·m for the first four times the frame’s gravity, 68 for the next four — because the sway the lean adds is itself leaned on. That is the shear that the analysis without leaning columns omitted, and the storey check found it as 22 per cent of the wind in the third storey because that is where it is largest against the wind; in the base moment it shows as 23 per cent of the moment.
A designer who checked the analysis with the column-line integral, found it exact, and designed the columns for 192 kN·m would have under-designed them by a fifth, with every check of the arithmetic passing. The load that makes itself worse explained why second-order effects take the shape they do. Here the shape is right in both analyses; it is the load that differs.
Neither check can see the beams
The earlier essay’s finding about the beams has not gone away. The beams of a concrete frame may be cracked to a third of their gross stiffness or less, and the second-order sway depends on that choice far more than on anything else.
The complete second-order analysis sways 17.3 mm with gross beams, 42.0 at 0.35 and 76.8 at 0.2 — a factor of four and a half, larger than the factor of three and a third the first-order analysis showed over the same range, because the softer frame drifts further and so leans harder. Every one of those analyses passes the column-line check exactly, and every one passes the storey equilibrium check to within a per cent. The first check confirms the moments and the shape agree; the second confirms the moments and the loads agree. The stiffness that turns loads into moments and moments into shapes is in both numbers each time.
The two readings of the principle check two of the three things an analysis is made of. Virtual forces against real displacements is a compatibility check, and it cannot see a missing load. Real forces against virtual displacements is an equilibrium check, and it cannot see a wrong stiffness. Neither checks the constitutive relation, because neither has one of its own: both take it from the analysis, in the moments. One support too many made the same point about a redundant beam’s internal forces, which are consequences of the stiffness assumed. For the stiffness itself the only checks are of a different kind — a cracked-section calculation done independently, or a building whose measured period disagrees with the model’s.
The frame as modelled
Only the P–Δ effect is included: each column’s axial force acting through its storey’s chord rotation, as a negative lateral stiffness of N/h on its two ends. The P–δ effect, a column’s own bow between its ends, is left out; 600 mm columns 3.5 m long carry about one per cent of their own Euler load, so the bow adds about one per cent to their moments, and a member check would carry it. The axial forces come from the previous solve and are iterated to convergence, so the gravity’s own redistribution under wind is in them.
The floors are not rigid in their plane: the beams have their own axial stiffness and the column lines sway by slightly different amounts. The storey check reads the floor’s drift as the mean of the column lines’, which is what a checker would take from an analysis that reports one drift per floor, and the residue that leaves in the complete analysis is under 2 per cent of the wind in every storey. The leaning columns are pinned at every floor and continuous in nothing; real gravity columns are usually continuous through two or three storeys, which gives them a small stiffness of their own and makes them lean slightly less.
Everything is elastic and the loads are constant. There is no out-of-plumb: a real frame is checked for a notional horizontal load as well, which is the same lean caused by tolerance rather than wind, and which this frame would carry through the same three terms.
Still open: the column line that stops at a transfer
The unit load in both essays has gone down an unbroken column line from the roof to a fixed base. Many buildings have no such line. A column stopped at a transfer girder over an open ground floor, or a façade set back above a podium, leaves the line’s moment to turn the corner into a beam, and the unit load carried down that line must go through the beam to reach the ground. The check then needs the beam’s stiffness after all, and the cheapness that came from carrying the unit load past every beam is gone. Whether some other admissible path for the unit load still avoids every member whose stiffness is in doubt — down a neighbouring line that does reach the ground, perhaps, with the virtual load carried across by a floor that is only asked to transmit axial force — and whether the storey equilibrium check, which needs no path at all, is then the cheaper of the two, is the question an irregular building puts to both.
Named alongside this one
Essays reaching for the same objects. Nobody chose these; they are what the concept index makes visible.
- Choose what to take away compatibility · equilibrium · virtual work
- The drawing that is right except for a rotation compatibility · unit load method · virtual work
- The matrix that replaced the hand methods compatibility · equilibrium · virtual work
- The stiffness the load takes away compatibility · p-delta · second-order
- Two motions with one name drift · second-order · stability index
- Bending that arrives as twist compatibility · unit load method
The objects this essay names
Each one links to every other essay that touches it.
CompatibilityDriftEquilibriumLeaning columnP-deltaSecond-orderStability indexUnit load methodVirtual work