Connection design — where it appears
Named by 11 essays across 3 fields — each of them below, with the objects they name alongside it.
The bolts that do not share
Every bolted connection in this collection has divided a force by a number of bolts. That is right for a short joint and wrong for a long one, and the reason has nothing to do with the bolts — it is that the plates they join are elastic, and stretch by different amounts at different points along the lap.
The smallest of six failures
Everything else in this collection that fails does so in one way at a time. A dowel through timber does not — the wood can crush while the steel stays straight, or one plastic hinge can form in it, or two — and the capacity is the smallest of the six, which is the kinematic theorem of plasticity applied to a joint rather than to a frame.
The width nobody drew
Every other member in this collection arrives with a cross-section. A gusset plate does not — it is a piece of steel with a brace bolted to it somewhere in the middle, and no geometry says how much of it is working. The profession's answer is a thirty-degree spread from a 1952 master's thesis, it invents three quarters of the area being checked, and the check it was written for is not the one that governs.
The weld that is stronger where it is pulled
A fillet weld pulled across its axis is √1.5 stronger than the same weld pulled along it. On a group under an eccentric load the direction of the pull varies from point to point, so the capacity does too — and the gain that follows is worth twenty per cent at one eccentricity and nothing at all at another.
The joint that was chosen
A joint's stiffness decides how a beam's moment divides between its span and its supports, and the two add to a constant. So there is a stiffness at which they are equal, the beam is sized by the smaller of two numbers rather than the larger of one, and the design moment is half what a simple connection leaves behind.
The joint that has to keep turning
A beam on partial-strength joints collapses at 8(Mp + Mj)/L² however stiff the joints are. Stiffness decides only which yields first, and a joint that yields first has to go on rotating at full moment until the span catches up. A weak joint on a stiff connection has the most turning to do — more than a rigid full-strength one.
The throat that misses the load
A partial-penetration butt weld's throat faces the load squarely, so a millimetre of it carries more than a fillet's, and in every grade what limits it is a cap on normal stress rather than the directional criterion. Made from one side, the throat sits off the plates' line of action. At half penetration it keeps a quarter of that capacity, and the stress the eccentricity adds lands on the root, which is a crack.
The shear that helps a butt weld
A partial-penetration butt throat pulled straight across its weld is capped at 0.9fu, which in S355 makes it 15 per cent stronger than a fillet throat. Add a little shear along the weld and the butt throat gets stronger, not weaker, because the cap limits only the normal stress — until the shear is 42 per cent of the pull, where it is 29 per cent stronger than the fillet and carries its largest resultant, 478 N/mm² against 441 straight across. Along a moment connection's web weld the mix of pull and shear sweeps through that peak, and in the direction that is all shear a single-sided throat is as good as two.
The tension a fire leaves behind
A steel beam held at its ends by the structure around it is pushed into compression as a fire heats it, and yields, because its strength is falling while its expansion is not. When the fire goes out the expansion comes back and the yield does not. Held at a tenth of its own stiffness, a beam that peaked at 134 N/mm² of compression on the way up ends the fire at 195 N/mm² of tension — more than it was ever pushed, arriving hours after the fire was out, and on connections that were designed to carry shear.
The beam that pays the fire back in sag
A steel beam held at its ends and kept straight through a fire yields short on the way up and pulls on its connections with its plastic shortening on the way down. A beam carrying a floor does not stay straight. Squeezed by its own expansion, it forms a hinge at about 500 °C and bows out of the way, hangs as a catenary while still hot, and keeps a metre of sag when it cools — length it no longer has to be pulled for. It ends the fire pulling a third as hard as the straight beam, nearly whatever holds it, and the hard pull comes earlier instead: at 800 °C, on connections that are as hot as it is.
The slab that catches what the joints let go
When an interior column is lost, the beams that crossed over it sag into cables and the slab over the four bays round it sags with them, into a membrane hanging from the floor that did not lose anything. Whether the floor's robustness belongs to its steelwork or to its concrete turns on one number with no span in it: the slab's mesh only starts to carry its full tension when the beams' ends have turned through about 0.09 radians, more than any ordinary joint can follow. So the membrane arrives after the joints have gone. And then it catches the floor — a metre down, alone — and with an ordinary mesh it holds half as much again as the beams could.
Named alongside it
The objects these essays reach for when they reach for this one.
DuctilityBearingDirectional methodEccentricityEnd platePlastic hingeStress combinationWeld strengthCatenaryContinuityDesign momentDetailing