A built-up column has a second way to bend. A 24 m column of two chords 800 mm apart, joined by single lacing. On the left it buckles the way a solid column does, by bending; on the right the chords stay straight and the lattice racks, which a solid column cannot do at all. Neither happens alone, and the two flexibilities add rather than the two stiffnesses — so the critical load is 3832 kN against an Euler load of 4629 kN, which is 83% of it, and the column behaves as though its slenderness were 66 rather than 60. Stability

The lacing decides the force it has to carry

A perfectly straight column carries no shear, so the diagonals of a built-up column are resisting a force that exists only because the column is crooked. Computing it turns out to be circular — the shear is amplified by the very flexibility the lacing supplies — and the rule of thumb that replaces the calculation is wrong by a factor that grows as the lacing gets worse.

The worst force in a pile is not at the top of it. A 0.75 m pile 30 m long through ground that is settling, carrying 1200 kN at its head. Above the neutral plane the soil moves down past the shaft and the friction acts downward, so the axial force grows with depth; below it the friction acts upward in the ordinary way and the force falls again to the 600 kN the base takes. The maximum is 2331.39 kN at 18.86 m — 1.94 times the load applied, and it is at a depth where nothing is applied, nothing is connected and nothing can be inspected. A pile section chosen for the head load is under-sized by that factor over the middle third of its length. Internal forces

The coating that takes the resistance with it

The cure for downdrag is to make the pile slippery, and it works — a bitumen slip layer takes the drag on this pile from 1,131 kN to 34. It also removes the shaft friction that was holding the pile up, in the same proportion and over the same length, and past a certain smoothness there is no neutral plane to find because there is no equilibrium.

Cut the throat, and the face carries a moment and a tension at once. A crane hook of trapezoid section, 50 to 120 mm radius and 40 to 15 mm wide, carrying 100 kN, drawn beside the section at the cut and the stress across it. The load hangs on a line through the centre of curvature, so cutting the throat and taking everything below the cut as the free body leaves a face carrying a direct tension of 100 kN and a moment of N·R = 7.970 kN·m about the section's own centroid, which sits a full R = 79.70 mm from the load line. The stress is a hyperbola, zero at r = 75.04 mm rather than at the centroid 4.65 mm outside it, reaching 497.5 N/mm² of tension at the inner fibre and 281.3 of compression at the outer. The straight-beam formula, drawn dashed, reports 323.4 N/mm² for the bending part against the true 445.5, and leaves the 51.9 N/mm² of direct tension out altogether — between them, 54% under the real peak, at the fibre where a hook actually breaks. This is why a hook is trapezoidal: both effects are worst inside, so the material goes there. Sections and stress

The wide side goes inside

A crane hook's section is a trapezoid with its broad face towards the centre of curvature, and that is not a casting convenience. Turn the same section round — same area, same depth, same moment — and the stress at the fibre that breaks rises by thirty-nine per cent. The shape is doing two things at once, and only one of them is in a straight beam's arithmetic.

A buckled panel is a truss that nobody drew. A 1500 × 2000 panel of 8 mm web, at d/t = 188. It buckles in shear at 41.0 N/mm², which is 492 kN — and it then carries 1187 kN, 2.41 times as much, because the tension diagonal takes over from the compression one that has gone. The band runs at 18.5° with a membrane stress of 348 N/mm² over a width of 788 mm, and it pulls on the flange at 280.2 N per millimetre of its length. A web that never buckled at all would have reached 2460 kN, so the panel ends at 48% of a stocky web's capacity on a fraction of its steel. Stability

The tension has to pull on something

A buckled web carries its shear on a diagonal band of membrane tension, and the band pulls sideways on the flanges and stiffeners that bound it. That pull is the design output nobody plots — it runs from 72 to 603 newtons per millimetre across ordinary panel proportions, it is largest exactly where the panel is most efficient, and at the end of the girder there is nothing beyond to take it.

One of these two curves is a stiffness and the other is a statement of statics. The torque a spandrel beam carries, against how much of its torsional stiffness is left. The rising curve is compatibility torsion — a floor beam framing into the side of the spandrel, which shares its fixed-end moment of 197 kNm between the spandrel's torsional stiffness and its own flexural one. Uncracked, the spandrel takes 51% of it, or 100 kNm; at a quarter of that stiffness it takes 21%, or 41 kNm, and the floor beam picks up what was shed. The flat line is equilibrium torsion — a canopy cantilevering 2.2 m off the same spandrel, whose 116 kNm is fixed by statics and contains no stiffness at all. The first can be designed away by accepting a rotation. The second cannot be designed away by anything. Internal forces

The torque that should not be shed

A compatibility torque can be let go, because the load has somewhere else to go. What the rule does not say is what it costs the somewhere else — a twenty per cent rise in a floor beam's midspan moment, a crack width nobody limits, and a rotation the spandrel has to actually deliver. There is a size of torque past which shedding is the wrong answer, and no code states it.

Removing each member in turn. Every member of a 8-panel pratt truss removed one at a time, with the worst demand on the survivors plotted against the member removed. Four of the 35 leave a mechanism — the bars drawn to the top of the frame — and for those there is no redistribution to compute, because there is no structure left. The rest redistribute, and the worst of them asks a survivor for 2.04 times what it carried before. A single number for robustness does not exist: it depends on which member goes. Structural form

A determinate truss has no robustness at all

Remove any one of a Warren truss's thirty-one members and what is left is a mechanism. Not weakened — gone, with no set of forces that holds the load in any position. Robustness is not a property a structure has by degree; it is bought by adding members that carry nothing until something else stops carrying, and a truss without them has none of it to measure.

One pulse, two blocks of the same shape. Rotation as a fraction of the toppling angle, under a single 0.8 s sine pulse of 1.00 g, for two blocks of identical proportion whose sizes differ by a factor of 3. Both lift off at the same instant, because uplift depends on the shape alone. The small one reaches the toppling angle and goes over; the large one reaches 46%. The kinks are impacts: there is no dashpot anywhere in this model, and the only energy the block loses is lost when it lands on its other corner, at a velocity ratio of 0.926 per landing — 14% of the energy each time, decided by the block's shape and by nothing else. Dynamics

The only damping is the landing

A rocking block has no dashpot in it. The only energy it ever loses is lost at the instant it lands on its other corner, and how much is a property of the block's proportions — 14 per cent for a slender one and 38 for a stocky one. That single number decides whether it settles or goes over, and a real base does not deliver the value the theory computes.