The springings that make shortening worse
Fixing an arch at its springings is the stiffer, cheaper and usual way to build one in concrete, and it makes the arch six times as sensitive to its own shortening. The thrust it loses acts at the elastic centre, two thirds of the way up, so the moment lands at the springings as well as the crown, twice as large and the other way round — at the section the fixed arch is designed at, not away from it.
Two welds, and the one that decides
A member welded twice has two soft zones in series. If they were identical, both would reach their ultimate strength at the same load and the member would stretch twice as far as with one weld before either necked. They are never identical, and the flat top of an aluminium zone's stress–strain curve means that a second zone five per cent stronger than the first gives only sixty per cent of its stretch. Every weld added makes the member weaker, by the statistics of its weakest link, and more ductile, by less than it would if the welds matched.
The perimeter whose middle is not the column's
At an edge column the slab's own edge cuts the control perimeter, and what is left has its centroid 363 mm inside the column's centre. The slab's end moment moves the shear's resultant inward too, by a distance that grows with the end span. What twists the perimeter is the gap between the two: nothing at a 5 m end span, enough by 7.2 m to put the check at 1.23 of its resistance where the 1.4 shortcut reads 0.97. And a bigger column makes it worse.
The abutment that spreads before it turns
A fixed arch is fixed only if its abutments hold still, and they have two ways not to. Turning releases the springing moment, but slowly: an abutment has to be a hundred times the rib's EI/L to hold nine tenths of it, and a footing on stiff clay under a slender concrete rib already is. Spreading does the opposite. The rib's own shortening is worth 13.6 mm of spread, so an abutment that gives 7 mm a side under the thrust doubles every secondary moment in the arch — and a footing on dense sand gives 8.
The weld that is weakest at fifty-five degrees
A soft heat-affected zone that the load crosses fails by necking along its own line, and it can do that only if nothing along the line has to stretch. Straight across the load, the parent on either side stops the zone contracting and lends it 15 per cent. At 54.7 degrees — the angle a free sheet necks along — it lends nothing, and the member carries the zone's own strength. Below 24 degrees the zone cannot neck alone at all, and a weld running along the member costs a tenth of its strength while adding to its stretch.
The screw that is pulled instead of bent
A screw square to a timber joint resists slip by bending, and its thread is engaged only when it has tilted far enough to be pulled. Lean the same screw to 45 degrees and the slip pulls it from the first millimetre. An 8 mm screw through two 100 mm members goes from 5.9 kN to 13.4, reached after 2.2 mm of slip instead of more than twelve, and the bending that Johansen's model is about becomes an eighth of the joint. The price is a joint that holds one way better than the other.
The floors that fill up together
A column may be designed for less than the sum of its floors' imposed loads because the floors do not reach their worst day together — an argument that assumes each floor's load is independent of every other's. Let any two floors be correlated, and the reduction the averaging can pay for shrinks, and stops shrinking at a higher floor. At a correlation of 0.16 that floor reaches the 0.7 the storey rule falls to. One tenant on five floors halves what twenty floors can average away.
The storey above the core decides
A building whose bending core runs to the roof shares one sway mode between its core and its frame, and the storey-by-storey stability check reads it wrongly twice. Stop the core five storeys short and the check becomes exact: the first storey of bare frame above the core reads the building's own critical factor to three figures, because the whole building buckles there and nowhere else. The check stays wrong below the core, and it goes wrong again when the frame above is more than about twice as stiff.
The web that moves the centre and not the twist
A thin plate closing a channel into a box changes its torsion at once and its shear centre hardly at all. An interior web dividing a box into two cells does the reverse. Off the middle of a 600 mm box, a web as thick as the walls takes 38 per cent of the vertical shear — more than either outer web — and pulls the shear centre 27 mm toward itself, while the torsion constant changes by less than one per cent. The two walls are the same kind of wall; what differs is which flow they are part of.
The cable that pays the factor back
A frame that loses a column carries the floor across the gap first by bending and then, as the beam sags, as a cable. The hope is that a path which stiffens as it deflects needs less than the factor of two a suddenly loaded spring does. On the bending plateau it does — 1.18 at nine tenths of the collapse load. But past one depth of sag the cable is a straight line again, and the factor climbs straight back toward two: 1.73 at one and a half times the collapse load. And the connections are asked for a tenth of a radian on the way.
The filler that cannot be gentle twice
A crushable filler in the gap between two buildings caps a collision at its crush force, but a filler soft enough to make the everyday contacts gentle runs out on the hardest one. Grade it — soft at the face, strong behind — and the soft layer takes the small contacts while the strong layer stops the large. The energy says otherwise. Every kilojoule the soft layer does not absorb, the strong layer must, in less depth: in a 40 mm filler, an outer half at 1.5 MPa needs an inner half at 56 MN, far above the 35 MN of the bare concrete it was meant to improve on.
The studs that send the check outward
Shear studs round a column fix a failing punching check, and they turn one check into three. The studs carry the control perimeter; past them the concrete alone must carry a perimeter long enough to need no help, and that outer perimeter stands further from the column the larger the load, so the studs follow it out. At a 10 m bay they reach four effective depths from the face, and the steel they need grows as the shear to the power 3.5. The third check, at the column face, is the one no stud reaches, and it ends the series at 11.8 m.
The counter fitted after the load
A truss with a counter-diagonal in every panel cannot take a change of length for free, so a camber cut into its members might seem to lock force into it. One cutting list locks in nothing — every member shortened by its own dead-load stretch — and the simpler lists lock in little. What locks in force is the shop: a millimetre of error per member puts 174 kN into some member of a truss whose largest dead-load force is 471. Leave the counters loose until the dead load is on and cut them to the gap, and the same errors lock in nothing at all.
The tension a fire leaves behind
A steel beam held at its ends by the structure around it is pushed into compression as a fire heats it, and yields, because its strength is falling while its expansion is not. When the fire goes out the expansion comes back and the yield does not. Held at a tenth of its own stiffness, a beam that peaked at 134 N/mm² of compression on the way up ends the fire at 195 N/mm² of tension — more than it was ever pushed, arriving hours after the fire was out, and on connections that were designed to carry shear.
The piles that would lift the ground
A basement too light to stay down can be pinned down with tension piles, each holding by the friction on its shaft. Add enough of them, close enough together, and the ground between them stops being something they grip and becomes something they carry: the group lifts out as a block, and the block's weight is all it can hold. For 600 mm piles 15 m long that happens closer than 2.06 m apart, a spacing with no raft, no water and no load in it — and every pile past that point is paid for twice.
The tendon that pulls before the deck arrives
A stressed ribbon is hung one span at a time, and the obvious fear is the stage at which one span carries its deck and the next does not: the pier between them asked for a whole span's thrust. It is not asked for that, because tendons cut to the finished length are already stretched across the empty span and pulling. For two 100 m spans at a fiftieth, the rigid pier's stage force is 4,109 kN against a crowd's 9,440 — unless the tendons were sized generously, when the stage overtakes the crowd.
Two reserves for one buckled web
A slender web keeps carrying shear after it buckles, and design uses two models of how: Basler's band of tension anchored on the stiffeners, and the rotated stress field spread over the whole web and anchored at its ends. Given the same 1,500 × 8 mm panel they agree about the buckling and disagree about everything after it — and in particular about what an intermediate stiffener is for. One says stiffeners save 37 per cent of the steel; the other, 1 per cent.
The reaction that is made of short waves
Run a wide-flanged girder continuously over a support and its worst moment moves to the support. That moment is made by a reaction, a reaction is made of short waves, and a short wave puts its stress next to the web. Over the support of two 20 m spans with a 3 m overhang the flange works over a third of its width, against four fifths at the sagging peak, so the stress at the web there is 4.2 times the sagging peak for a moment only 1.7 times as large — and how much flange works depends on what the support bears on.
The fuse that protects the strand and not the wall
A rocking wall's tendon loses its prestress when it yields, so give it a fuse: a short link in series that yields first and is replaced afterwards. The strand then never passes 1,000 kN and stays elastic. But the fuse caps the restoring moment lower, so under the same 1.5 g pulse the wall rocks to 110 mrad instead of 89, and the line loses all its prestress just as the strand did. A new fuse gives the prestress back; the bars' stretch stays, and the next pulse takes the wall to 134 mrad.
The thinner cover carries more
A plate spliced with a cover on each face is the standard cure for a lap joint's eccentricity, and the covers are usually sized as if they shared the load in proportion to their areas. A free body cut across the splice says otherwise. With nothing but the two covers crossing the cut, their forces must balance about the line the load acts on, so they share by lever arm and not by area — and the thinner cover, which sits nearer that line, carries more than half the load on less than half the steel.
The relief that belongs to the pressure line
An inclined tendon carries part of a prestressed beam's shear, and the rule is to subtract its vertical component, P times the slope of the tendon. In a continuous beam the tendon also provokes reactions, and the reactions make a shear of their own — a constant in each span, too small to look at. It is not small where it matters. Beside the end support of a two-span beam it doubles the shear left for the links, and moving the tendon without changing the beam at all can make the tendon's slope report that there is none.
Two slips are a shear test
One failed slope gives a line of soils, every one of which fits the failure. Two failed slopes give two lines, and where they cross is a soil that fits both. Whether the crossing means anything depends on how differently the two slopes loaded the ground: two slips at one angle cross only at zero cohesion, two at nearby angles cross anywhere in a twenty-degree band, and a flat, tall slope beside a steep, short one pins the soil to within two degrees — because each slip is a shear test at one normal stress, and a strength line needs two tests far apart.
One column is enough to find the sway
The unit load that finds a deflection may be carried on any structure that can carry it, so in a fixed-base portal the sway can be found from one column's two end moments and nothing else. Carry it on a three-hinged frame instead and the same sway comes out of all four members, one of them contributing a negative amount. Every structure gives the same total and a different account of where it came from — which means "how much of the sway is axial shortening" has no answer until a structure is named, and only one structure's answer is worth having.
The law that throws the tuning away
An actuator that pushes against a tuned mass and listens only to the structure pumps the mass's own mode. A law that also listens to the mass can be made safe in one move — cancel the mass's spring, so that it has no mode to pump — and every such law is stable. But cancelling the spring throws away the tuning that made the mass useful, and the actuator has to earn it back: below a third of the force on the structure, the law is worse than the passive mass it replaced. What it buys above that, it buys mostly by letting the mass travel further.