Theme

Scale changes everything — page 6

Essays 121 to 144 of 175 on this thread, in the same order.
How far a local load spreads, and what is nearest its limit. Along a steel-faced polyurethane cladding panel, 0.5 mm faces of 320 N/mm² steel on an 80 mm core crushing at 0.12 N/mm², from the middle of a strip load of 3.0 N per mm of width spread over 10 mm: the face's deflection over its value under the load, the core's compressive stress over its crushing strength, and the face's bending stress over its yield stress. The load spreads over a length set by the fourth root of the face's bending stiffness over the core's, 1/β = 20.5 mm; the deflection is 1.44 mm under the load and changes sign beyond 48 mm. The core is at 0.60 of its crushing strength and the face at 0.89 of its yield stress: this panel's face yields at 3.36 N/mm and its core crushes at 5.00. Sections and stress

The face that dents and the core that crushes

A sandwich panel carries bending as a couple between its faces, and that is a calculation about the whole panel. Put a local load on one face — a foot, a fixing, a dropped tool — and the face becomes a thin beam on a soft bed, spreading the load over a length the fourth root of their stiffnesses sets. Then either the face yields and dents, or the core crushes beneath it, and which comes first is decided by one thickness: below it the face gives, above it the core does, and a steel-faced roof panel is on the wrong side of it for anyone who walks on it.

A deck holds the middle of the span. The twist along an 8 m open section on forks, free to warp, carrying 12 kN/m at 75 mm from its shear centre — 900 Nmm of torque per mm of span. With nothing fastened to it the beam twists 6.25° at mid-span; a deck resisting the top flange's rotation at 5.0 kNm per metre per radian holds it to 4.20°, and one four times as stiff to 2.10°. The deck works where the beam is weakest, in the middle; near the supports the beam's own torsional stiffness does most of the work whatever is fastened to it. Deflection

A deck is a spring, not a wall

An open-section beam loaded off its shear centre twists, and the usual reassurance is that the deck fastened to its top flange will stop it. The deck resists the flange's rotation with a stiffness per metre of span, and that stiffness has to be compared with the beam's own. On an 8 m beam a screwed deck of ordinary stiffness removes a third of the twist; on a 16 m beam the same deck removes three quarters, because the beam's torsional stiffness falls with the square of its span and the deck's does not.

Ductile until it was welded. A 2.0 m 6082-T6 member pulled in tension, as supplied and with one weld across it whose heat-affected zone is 60 mm long: the load per unit of parent section against the member's overall strain, to the maximum load, where the weaker part begins to neck. The plain member reaches 310 N/mm² at 7.0% strain, 140 mm of stretch. The welded one reaches 185 N/mm² at 0.62%, 12.3 mm — 8.8% of the plain member's, and the parent never reaches its proof stress of 260 N/mm². (uniform elongations assumed: 7.0% for the parent, 12% for the zone) Materials

The soft zone that takes all the stretch

The metal beside a weld in heat-treated aluminium is weaker than the rest of the member and more ductile, and it is tempting to read the second fact as a consolation. It is not. A member welded across stretches only where it is weak, and the weak zone is sixty millimetres long; a two-metre 6082-T6 tie that would extend 140 mm before necking extends 12 mm once welded, and the parent metal never yields at all. What decides it is one ratio, the zone's ultimate strength over the parent's, and the ductility returns only when that ratio reaches one.

Wrong in both directions until the building racks. Across buildings from a pure bending tower to a pure racking frame (αH on a logarithmic scale), each 20 storeys with gravity putting its own critical factor at 5.0: solid, the least storey sway factor over the building's own, which is what taking the least storey as the building's costs; dashed, the ground storey's second-order increase estimated from its own sway factor, over the true increase. At αH = 0.1 the least storey factor is 0.77 of the true one and the ground storey's estimate 0.09 of the true increase; at αH = 10, 0.86 and 0.37; at αH = 100, 0.94 and 0.98. The first error is on the safe side and the second is not, and both vanish only for a building that racks. Stability

The storey that cannot see the building lean

A sway check made storey by storey asks each storey how much it drifts under a push and how much gravity sits on it, and reads a critical load factor for the storey from the two. For a frame whose storeys rack like a stack of shelves that is exact. For a building that bends — a braced core, a wall — it is wrong twice. Taking the least storey as the building's reads a critical factor of 3.9 for a building whose own is 5. And amplifying each storey by its own factor finds a 2 per cent second-order increase at the ground storey, where the truth is 20, because the ground storey hardly drifts and carries the lean of everything above it.

The roller's pressure, not the soil's. Horizontal pressure down the back of a wall, for backfill of 20 kN/m³ and φ′ = 30° behind a wall 3.0 m high, compacted by a roller of 60 kN per metre of its width. Dashed, the soil's own active pressure, Kₐ·γz (Kₐ = 0.33), and at-rest pressure, K₀·γz (K₀ = 0.50). Solid, Ingold's compaction envelope: rising as the passive limit γz/Kₐ to 27.6 kPa at 0.46 m, then constant at √(2pγ/π) = 27.6 kPa all the way down, since the active pressure would not reach it until 4.15 m. Its thrust is 76.6 kN per metre of wall against the active 30.0, and its moment about the base 106.3 kN·m against 30.0. Equilibrium

The pressure the roller leaves behind

A retaining wall is designed for the pressure of the soil it holds, a triangle growing with depth. The soil behind most walls was not tipped there. It was placed in layers and rolled, and each pass of the roller pushed the soil sideways against the wall harder than the soil's own weight ever could, and left most of that push locked in when it moved on. Behind a 3 m wall compacted by an ordinary vibrating roller the locked-in pressure is a constant 28 kPa from half a metre down, the thrust two and a half times the active triangle's and the moment at the base three and a half.

A few per cent between two welds is most of the second one's stretch. For a 2.0 m 6082-T6 member with two welds whose heat-affected zones are each 60 mm long, the stretch beyond the elastic at maximum load as a multiple of one weld's (solid), against how much stronger the second zone is than the first; dashed, the share of its own uniform plastic strain the stronger zone reaches when the weaker peaks, (1/(1 + gap))ⁿ with the zone's hardening exponent n = 10.4. Identical zones give 2.00 times one weld's stretch; 1.74 at a gap of 3 per cent, 1.23 at 15. The stronger zone gives half its stretch at a gap of 7.1 per cent. (uniform elongation of the zone assumed at 12%, and each zone's proof stress and ultimate scaled together) Materials

Two welds, and the one that decides

A member welded twice has two soft zones in series. If they were identical, both would reach their ultimate strength at the same load and the member would stretch twice as far as with one weld before either necked. They are never identical, and the flat top of an aluminium zone's stress–strain curve means that a second zone five per cent stronger than the first gives only sixty per cent of its stretch. Every weld added makes the member weaker, by the statistics of its weakest link, and more ductile, by less than it would if the welds matched.

How stiff an abutment has to be to count as fixed. The shortening moments in a 60 m parabolic concrete rib at a 6 m rise (EI 420,000 kN·m²) under 60 kN/m as shares of the fixed rib's, against the rotational stiffness of each springing as a multiple of EI/L on a logarithmic scale: at the springings (solid, −112 kN·m when fixed) and the crown (dashed, 58 kN·m fixed, 29 two-hinged). The springing moment is half the fixed value at kθ = 11.3 EI/L and nine tenths at 102 EI/L; at EI/L itself it is 8 per cent. The crown moment never falls below the two-hinged rib's 51 per cent of the fixed value. Deflection

The abutment that spreads before it turns

A fixed arch is fixed only if its abutments hold still, and they have two ways not to. Turning releases the springing moment, but slowly: an abutment has to be a hundred times the rib's EI/L to hold nine tenths of it, and a footing on stiff clay under a slender concrete rib already is. Spreading does the opposite. The rib's own shortening is worth 13.6 mm of spread, so an abutment that gives 7 mm a side under the thrust doubles every secondary moment in the arch — and a footing on dense sand gives 8.

The floor under the reduction rises with the correlation. The least factor a column carrying ever more floors may take, against the correlation between floors, for an office imposed load with a coefficient of variation of 0.6, its characteristic value the 95th percentile, loads normal: (1 + zv√ρ)/(1 + zv). With independent floors it is 0.503, the floor the independence argument found; at a correlation of 0.1 it is 0.660, at 0.3 0.775, at 0.5 0.855. EN 1991-1-1's storey rule falls to ψ₀ = 0.70 (dashed), and the two cross at a correlation of 0.157: floors that move together any more than that make the rule's tall-building reduction larger than the averaging can pay for. Equilibrium

The floors that fill up together

A column may be designed for less than the sum of its floors' imposed loads because the floors do not reach their worst day together — an argument that assumes each floor's load is independent of every other's. Let any two floors be correlated, and the reduction the averaging can pay for shrinks, and stops shrinking at a higher floor. At a correlation of 0.16 that floor reaches the 0.7 the storey rule falls to. One tenant on five floors halves what twenty floors can average away.

The buckling mode moves up to where the spine is not. The building's first buckling mode, each floor's sideways movement as a fraction of the roof's, up the height of a 20-storey building of a bending spine and a racking frame (αH 1.0), its gravity scaled to an elastic critical factor of 5.0, under an equal lateral load at every floor: the spine to the roof, and stopping at storeys 15 and 10. With the spine to the roof the mode is the bending tower's, growing all the way up. With the spine stopping, at storey 15 its top moves less than a thousandth as far as the roof, and at storey 10 its top moves less than a thousandth as far as the roof: the building buckles in the first storey of frame above the spine, every floor above that storey moving with it as one, and the spine takes no part. Stability

The storey above the core decides

A building whose bending core runs to the roof shares one sway mode between its core and its frame, and the storey-by-storey stability check reads it wrongly twice. Stop the core five storeys short and the check becomes exact: the first storey of bare frame above the core reads the building's own critical factor to three figures, because the whole building buckles there and nowhere else. The check stays wrong below the core, and it goes wrong again when the frame above is more than about twice as stiff.

The flange over the support works over a third of its width. The effective width of the flange as a share of its overhang along two continuous 20 m spans with a flange overhang of 3.0 m each side of the web, the support bearing over 1.0 m, under a uniform load, left out where the moment is under three tenths of its peak (solid), with EN 1993-1-5's factors over the regions they apply to (dashed) and the simply supported span's mid-span value (dotted). At the sagging peak, 7.6 m from the end, the flange works over 0.81 of its width; over the support, over 0.33. EN 1993-1-5 gives 0.83 in the span and 0.34 over the support, from effective lengths of 17.0 and 10.0 m; a single span of 20 m has 0.88 at mid-span. Sections and stress

The reaction that is made of short waves

Run a wide-flanged girder continuously over a support and its worst moment moves to the support. That moment is made by a reaction, a reaction is made of short waves, and a short wave puts its stress next to the web. Over the support of two 20 m spans with a 3 m overhang the flange works over a third of its width, against four fifths at the sagging peak, so the stress at the web there is 4.2 times the sagging peak for a moment only 1.7 times as large — and how much flange works depends on what the support bears on.

The limit moment goes as the square root of the ring's stiffness, and pressure is part of it. Brazier's limit moment for a steel tube of radius 600 mm and wall 2.5 mm (r/t = 240), as a multiple of its value with no pressure, against the pressure as a multiple of the ring's own buckling pressure, pc = 3D/r³ = 4.07 kPa; positive inside. The dots are the peaks of the moment–curvature path found by minimising the energy at each curvature; the line is √(1 + p/pc). Half pc outside leaves 0.71 of the bending capacity, and the capacity is gone at pc; pc inside gives 1.41, three times pc 2.00. The pressure enters only by adding to the ring's stiffness against the oval, (3D/r³ + p) where it had 3D/r³. Stability

Three kilopascals that halve a tube in bending

A long thin tube in bending flattens until its section can carry no more, at an oval of exactly two ninths of its radius. Put a pressure on it and nothing about that shape changes. What changes is how much bending it takes to get there — as the square root of one plus the pressure over the ring's own buckling pressure — and for a steel tube 1.2 m across with a 2.5 mm wall that unit is 4 kPa. Three kilopascals of suction halve its bending capacity; a fifth of an atmosphere inside doubles it and hands the tube to another failure entirely.

The arm goes in almost the same place whatever shape the wind is. The share of the tip drift removed by one outrigger on a 200 m core of bending stiffness 1.2 × 10¹⁰ kN·m² carrying 6,000 kN of wind in all, with an outrigger of 1.0 × 10⁸ kN·m per radian, against the outrigger's level as a share of the height, for the three profiles of the same total wind. uniform: best at 0.745 of the height, removing 45.6 per cent; power law: best at 0.749 of the height, removing 45.9 per cent; triangle: best at 0.757 of the height, removing 46.4 per cent. The curves lie almost on one another: the triangle, with three quarters of its load in the upper half against the uniform wind's half, moves the best level up by 1.2 per cent of the height. Structural form

The arm that ignores the shape of the wind

The outrigger arithmetic is usually done for a wind that is the same at every height, and real wind is not: it grows with height, and an earthquake's first mode loads a building as a triangle. The natural guess is that a load concentrated towards the top moves the best place for the arm. It barely does. Put the same total wind on a 200 m core as a uniform load, a power-law wind and a triangle, and the best level moves by just over one per cent of the height. What moves is the force in the arm — half as much again under the triangle — and how far the top goes, while the arm's own stiffness shifts its best level thirty times as far as the wind's shape does.

The linear answer has the ground holding the ends down. The contact pressure along a strip 16 m long, EI 5.40 × 10⁵ kN·m², on a bed of 50 × 10³ kN/m² per metre of its length, under a column of 1,000 kN. With springs that pull as readily as they push (dashed) the bed presses 197 kN/m under the column and pulls down on the ends at up to 34 kN/m — tension the ground cannot supply. With the pulling springs released (solid), the strip touches the ground only from 3.97 m to 12.03 m, 8.05 m in all, and presses 213 kN/m under the column, 8 per cent more; beyond that it carries nothing. Internal forces

The ends the ground was holding down

Winkler's springs pull as readily as they push, and on a long footing strip the linear answer quietly uses that: it has the ground holding the strip's ends down. Take the pull away and the correction under the column is modest — eight or nine per cent on the pressure and the moment — but the shape of the answer changes completely. A weightless strip longer than about eight metres keeps exactly eight metres of itself on the ground, whatever length was poured, and the rest rises off as straight cantilevers carrying nothing. The middle-third rule turns out to be a property of rigid footings: an eight-metre strip lifts at a fiftieth of the eccentricity the kern allows.

A cambered girder is an arch on its slings. A 40 m precast girder of 11 kN/m, lateral stiffness 2.55 × 10⁵ kN·m², hung 0.90 m below its roll axis, picked 2 per cent of its length in from each end, with 100 mm of camber at mid-length, drawn in elevation with the camber exaggerated. The girder's centre of gravity is two-thirds of the camber above the line through its ends, 67 mm; its lifting points, on the arc 2 per cent in from each end, are 8 mm above it. It rolls about the line through the picks (dashed), so the camber has lifted its centre of gravity 59 mm towards the roll axis: the girder hangs as though its hook were that much lower. Deflection

The camber that lowers the hook

A camber is built into a girder so that it ends up level in the finished structure, and nothing about it matters until then — except on the day it is lifted. A cambered girder hanging from its ends is a shallow arch, its centre of gravity two-thirds of the camber above the line through its lifting points, and it rolls about that line as though its hook were that much lower. On a long precast girder already close to its lifting limit, a hundred millimetres of camber takes the factor of safety against roll from 2.3 to 1.4. The camber grows while the girder waits in the yard, so the same girder becomes harder to lift every week it is stored. Pick it a fifth of its length in from each end and the camber drops out of the problem altogether.

On a flexible tower the full tank is not the worst one. The tower's base shear against how full the tank is, for a 12 m tank holding up to 8 m of water on a 25 m tower: a stiff tower (period 1.20 s with the tank full) and a flexible one (2.50 s), the liquid and tower coupled (solid) and with all the water bolted to the container (dashed). The stiff tower's shear rises all the way to full, 2,141 kN, against 2,728 kN rigid. The flexible tower's peaks at 84% full, 688 kN, and falls to 665 kN full; rigid water says 884 kN, flat from 37% full, because past the spectrum's last corner a heavier mass on the same spring draws the same force. Dynamics

The tank that sloshes the tower

On the ground a tank's liquid splits into a part that moves with the wall and a part that sloshes at its own long period, and the two answers can be added afterwards because they are orders apart. Lift the tank onto a tower and the tower's period moves up towards the sloshing period, the two masses stop being separate, and the system has two modes that belong to neither. Adding the ground answers then overstates the base shear by a third, treating the water as solid by as much again, the wave grows by half, and a flexible tower is worst with the tank about five-sixths full.

Two members each half-way to ponding are unstable together. The girder's ponding parameter Cp against the joist's Cs. Either member alone is stable up to 1; together the roof is stable only below the solid curve, (1 − Cp)(1 − Cs) = (8/π²)·Cp·Cs, which meets the diagonal at 0.526 — two members each about half-way to ponding on their own are critical together. The dashed line is the simplified rule Cp + 0.9Cs ≤ 0.25. The marked roof is a 12 by 9 m bay whose girders and joists are each sized to deflect L/240 under 1.5 kN/m²: Cp = 0.26 and Cs = 0.19, stable, with its joists' sag amplified 1.79 times where the joist alone would say 1.24 and the girder alone 1.35. Deflection

The roof that ponds on its girders

A flat roof's joists sit on girders, and the water fills the sum of both their sags. Two members each half-way to ponding on their own are unstable together, and long before that the growth of the water is far larger than either member's own amplification says. AISC's simplified rule turns out to be a line of constant growth, and a member sized to a deflection limit has a ponding parameter proportional to its span — so a bay sized to L/240 under 1.5 kN/m² meets the rule up to 6 m, doubles its water at 12 and ponds at 24.5.

A stiff building bridges the trough it stands in. The settlement of a building 30 m long centred on the trough, over a trough 30 mm deep whose inflection points are 15 m from its centre (dashed: the ground with no building), measured from the building's settlement under its own weight, for relative stiffnesses EI/(kₛ·B⁴) of 10⁻⁴, 10⁻³ and 10⁻². At 10⁻⁴ its deflection ratio is 95% of the ground's; at 10⁻³ its deflection ratio is 66% of the ground's; at 10⁻² its deflection ratio is 17% of the ground's. The stiff building settles almost as a rigid body and leaves the trough's curvature to the ground beneath it. Deflection

The building the trough cannot bend

A tunnel leaves a settlement trough, and damage criteria are applied to the trough's deflection ratio over the length of each building above it. But a building is not the ground: it has a bending stiffness, and it takes only as much of the ground's curvature as that stiffness lets it. One number decides how much — the building's stiffness over the soil's modulus times its length to the fourth — and over two decades of it a building goes from following the trough to bridging it. Because the length enters to the fourth power, the same building is stiff when short and soft when long.

A girder softer to short waves sheds a little of its support moment. For two continuous 20 m spans of a girder whose flanges are 6.0 m wide and 30 mm thick, 1.20 m apart on 24 mm of web — the flanges 97% of its stiffness — under a uniform load, each interior support 1.0 m long: the bending moment along the girder per unit load, sagging up — for a prismatic girder (dashed), which is what a global analysis gives with one effective width per span, and for the girder whose every wave of moment bends it with that wave's own effective flange (solid). The interior reaction falls by 0.88%, and because the support moment is the difference of two much larger moments, that becomes 4.6% of the support moment, 47.0 to 44.8; the sagging peak rises by 2.9%, 28.1 to 28.9. Sections and stress

The reaction moves one per cent and the moment five

Over the support of a wide-flanged continuous girder the flange works over a third of its width, so the girder there should be softer and shed moment into its spans. It does — but it is the reaction that the softness changes, by less than one per cent, and the support moment, a small difference of two large ones, moves by five. The stress spike over the support follows the reaction rather than the moment and eases by two. A prismatic analysis is right about the moments to a few per cent, and the spike stays a problem of the section.

The gaps that open after the arch is closed. For the 60 m fixed concrete rib rising 6 m under 60 kN/m, closed at 28 days with its abutments jacked apart to take up the day's gap: the gap between the rib and its springings that each movement opens after closure, in millimetres, against the years since, on a log scale — the rib's creep under its thrust, its shrinkage, and the ground consolidating under the thrust by 1.0 times its 8 mm immediate spread with 90% done at 10 years. After a hundred years they are 24.8, 16.2 and 8.0 mm, 48.9 in all, against the 13.6 mm the thrust shortened the rib on the day. The rib resists them while it creeps itself, so the gap it acts as if fixed against is 20.9 mm (fine dashes). Deflection

The jacks the arch forgets

Jack a fixed concrete arch's abutments apart before the crown is closed, by exactly the gap its thrust and its footings open on the day, and the springings start with no moment at all. A century later they carry 173 kN·m — half as much again as the 112 the jacks were set to remove. The thrust's own moment never relaxes; the jacks' correction does, as the rib creeps; and shrinkage and the ground's consolidation arrive after the jacks have gone. No single setting cancels movements that run on different clocks.

The deck moves the frames' feet, and the chord goes with them. A chord 24 m long, EI 2.52 × 10¹² N·mm², held by U-frames of 1,400 N/mm every 4 m, carrying 930 kN, in plan, sideways movements drawn 6 times the scale of the length: each frame's foot pushed 7.5 mm inward by its cross-girder's rotation under the deck (arrows), the chord's movement under that push alone (solid), and under the worst bow alone, four half-waves at 12.0 mm (dashed). The chord follows the push, and under its compression goes a little further — 9.1 mm at its middle frames against the 7.5 mm the feet moved — because a chord 24 m long is far softer sideways than the frames holding it; the frames that carry most are the end ones, beside the chord's fixed ends. Stability

The frames the deck pushes first

A half-through girder's U-frames are the ends of the cross-girders that carry its deck. Load the deck and every cross-girder sags, its ends rotate, and every frame's foot swings inward by millimetres before the compression chord has asked the frames for anything. It looks like a second imperfection on top of the chord's bow. It is a much weaker one: the frames all move together and the chord simply goes with them, so a 7.5 mm push adds 1.4 kN to frames that the bow loads with 13.6, and stiffer frames make it smaller, not larger. What the push leaves is mostly in the frames' own members, not in what they ask of the chord.

The columns and the core shorten apart for decades. For a 200 m concrete building built a storey every week, its perimeter columns at 12 N/mm² and its core at 6 at the base, with an outrigger at 149 m of 1.0 × 10⁸ kN·m a radian: how much the columns (solid) and the core (dashed) have shortened below the outrigger's level, and the difference between them (heavy), in mm, against the years since the first storey was cast, on a log scale. When the building tops out, in week 55, the difference is 7.0 mm; after fifty years it is 30.5. 77% of the difference arrives after the frame is finished — creep under the finishes and the floors above, and the thick columns' slower drying, most of which comes after the core's thinner walls have done theirs. Structural form

The arm connected late

An outrigger is often left unconnected until a concrete building is finished, so that the columns and the core can shorten by their different amounts without it. Most of their difference has not happened yet. Three-quarters of fifty years' differential shortening arrives after the frame tops out, and an arm connected then ends up carrying 3.5 MN of it — 60 per cent of what the design wind puts into the same arm, permanently, and in the same direction on both sides of the core. The connection date is the largest load the arm has, and a stiffer arm collects it faster than it collects the wind.

A building that crosses the trough at an angle stands on a warped surface. Plan of a 30 × 12 m building 10 m high, its walls 300 mm thick, over a trough 30 mm deep with its inflection 15 m from the tunnel's axis, its long axis 45° from square across the tunnel. The lines are the greenfield trough's settlement contours, 5, 10, 15, 20, 25 mm, parallel to the tunnel's axis (dashed). The corners settle A 27.4, B 18.4, C 27.4, D 18.4 mm, so they do not lie in a plane: A and C together settle 18.1 mm more than B and D. A building spanning square across the trough has no such warp, and one lying along it has none either; between the two, the trough twists the building as well as bending it. Deflection

The building the trough twists

A building that crosses a tunnel's settlement trough at an angle stands on ground that is warped as well as sagged. Its four corners do not settle into a plane, and beyond about twenty degrees of skew the warp is larger than the sag. Whether the building follows that warp or resists it depends on a property its bending never needed — whether its walls and floors close into a tube — and the same walls, closed or open, differ a thousandfold in their stiffness against it.

Where the outlet sits decides whether the roof ponds at all. The load the water puts in the more heavily loaded member of a square bay, over what the same head of water would put in it on a rigid roof, against the bay's side, with girders and joists each sized to deflect L/240 under 1.5 kN/m². With the level fixed by a scupper it is 2.01 at 12 m and 3.92 at 18 m, and the bay ponds at 24.5 m. With a drain on the girder line it is 1.24 and 1.41; with a drain at the bay's middle, 0.82 and 0.75, falling as the bay grows, because the water's surface goes down with the roof. Deflection

The roof that drains towards its sag

The depth of water a ponding check takes as given is set by the drainage: an overflow's height above the roof, plus the head a storm needs to leave through it. Which head a roof can carry depends less on how stiff it is than on where the overflow sits. With the level fixed by a scupper in the parapet, a 12 by 9 m bay allows 85 mm of water and an 18 m square bay 39. With a drain at the middle of the bay, whose inlet goes down as the roof sags, the same bays allow 182 and 205 mm — more than a rigid roof would — because the water's surface follows the sag down instead of filling it.

Ground already loaded rocks stiffer than springs that are not. The moment on the column against its rotation through a storm that takes the moment to ±1,000 kN·m and back, for an 8 m strip of EI 540 MN·m² on a bed of 50 MN/m² under a 1,000 kN column: on elastic springs that cannot pull, and on ground that unloads and reloads 4 times as stiffly as it first loads, in the first storm and the third. On elastic springs the column turns 1.418 milliradians at the peak, a rocking stiffness of 0.70 GN·m/rad, the same every storm. On the remembering ground it turns 1.116 in the first storm and 0.868 in the third — 0.90 and 1.15 GN·m/rad — because rocking unloads half the strip, and ground that has carried the column unloads stiffly. Internal forces

The footing the storms press down

A footing strip under a column that a storm rocks one way and then the other was expected to dig itself a bowl: its ends loaded half the time, compacted, and left hanging over the hollow. On ground that unloads and reloads four times as stiffly as it first loads, the bowl appears and the strip fills it. The column settles 26% more over three storms and then stops; the footing rocks 22% less than it did in its first storm and is 64% stiffer than on springs that forget, because rocking unloads half the strip and ground that has carried the column unloads stiffly. The storms change the settlement and the stiffness, and leave the moments almost where they were.

All themes