Erection stability — the series

One essay so far on this idea, and more questions about it than one essay answers.
  1. How stiff a brace has to be before the frame stops swaying. The effective length factor of a swaying portal against the stiffness of a horizontal spring at its head. The curve starts at k = 1.317, the unbraced value, and falls to 0.774 — the factor for the same frame with its head held — at a brace stiffness of 23.2 EI/L³. Past that point the frame buckles in the non-sway mode, which the brace does not restrain, and further stiffness buys nothing at all. The threshold is worth stating as 1.41 N꜀ᵣ/L, which is the form the number is memorable in: for a storey carrying a thousand kilonewtons over four metres it is about 0.35 kN per millimetre of sway. Against the frame's own lateral stiffness of 12.0 EI/L³ it is a factor of 1.93.

    The most dangerous day is before it is finished

    A structure is analysed once, complete, with every restraint present. It spends weeks in states nobody drew — a beam landed with no deck on it holds 17% of the moment its section is worth, a frame not yet braced buckles at a third of the load it will, and a bolt not yet tightened is a pin where the analysis assumed a fixity.