Take that one away and the load finds another route
Take that one away and the load finds another route. A 6-panel pratt truss under 20 kN at each top node, before and after member 2 is removed. The load redistributes. The worst-affected survivor now carries 2.03 times what it did, and four members that carried nothing before are now working. Whether that is survival depends on how much spare capacity was there, which is a different question from whether the frame was strong enough.
7 essays call
member-loss. The drawing above is what it returns with no arguments at all; every
call below passes it something, because a placement that passes nothing draws whichever
member of the family the generator happens to default to rather than the one its essay
argues about.
Where it is called
Changing this generator changes every one of these figures.
The structure that survives losing a member
Every check in this collection asks what a structure carries. None of them asks what is left when part of it is gone — and two frames with the same members, the same weight and the same factor of safety can answer that question completely differently.
The force nobody put in the model
A slab strip whose ends cannot move apart is not the strip in the yield-line calculation. Deflecting shortens the chord between its ends, the ends do not come in, and the strip is forced into an arch — worth four times the load it was designed for, at a movement nobody would see.
The columns that lean
A framed tube carries its wind load by bending the spandrel beams between its columns, and it does it badly — the corner columns take nearly six times what the middle ones do. Tilt the columns instead, so the perimeter is triangulated, and the same shear is carried axially. The concentration falls to 1.21 and the tube recovers most of the stiffness the plan said it had.
A determinate truss has no robustness at all
Remove any one of a Warren truss's thirty-one members and what is left is a mechanism. Not weakened — gone, with no set of forces that holds the load in any position. Robustness is not a property a structure has by degree; it is bought by adding members that carry nothing until something else stops carrying, and a truss without them has none of it to measure.
The factor of two belongs to one mode
A member that fails suddenly hands its force to the structure around it all at once, and the convention is to double the static answer: a load applied suddenly to a spring overshoots to twice its static deflection. A truss is not one spring. Take a diagonal out of a counter-braced truss in an instant and some members swing to three times their change of force, one swings the wrong way first, and a bottom chord whose force does not change at all passes through half as much again as it carries — because every mode overshoots by two, at its own time, and a member is a sum of modes.
The cable that pays the factor back
A frame that loses a column carries the floor across the gap first by bending and then, as the beam sags, as a cable. The hope is that a path which stiffens as it deflects needs less than the factor of two a suddenly loaded spring does. On the bending plateau it does — 1.18 at nine tenths of the collapse load. But past one depth of sag the cable is a straight line again, and the factor climbs straight back toward two: 1.73 at one and a half times the collapse load. And the connections are asked for a tenth of a radian on the way.
The slab that catches what the joints let go
When an interior column is lost, the beams that crossed over it sag into cables and the slab over the four bays round it sags with them, into a membrane hanging from the floor that did not lose anything. Whether the floor's robustness belongs to its steelwork or to its concrete turns on one number with no span in it: the slab's mesh only starts to carry its full tension when the beams' ends have turned through about 0.09 radians, more than any ordinary joint can follow. So the membrane arrives after the joints have gone. And then it catches the floor — a metre down, alone — and with an ordinary mesh it holds half as much again as the beams could.