Field

Connections

Structures do not fail in the middle of a member. They fail where two of them meet — which is the one place the theory behind every other field explicitly does not hold.
A bolt group under an eccentric load. A 3 by 2 bolt group carrying 100 kN at 150 mm from its centroid, with the resultant force on each bolt drawn to scale, by the elastic vector method. The load is shared equally and the torque is not, so the worst bolt carries 50.37 kN against 16.67 kN of direct shear alone — 3.02 times as much.

The connection is not a point, and every diagram so far says it is

Every free body drawn here has joined its members at points. Real structures fail at the joints far more often than in the members, and the reason is that a joint is exactly the region the theory behind every other page explicitly excludes.

A bolt group under an eccentric load. A 3 by 2 bolt group carrying 100 kN at 150 mm from its centroid, with the resultant force on each bolt drawn to scale, by the elastic vector method. The load is shared equally and the torque is not, so the worst bolt carries 50.37 kN against 16.67 kN of direct shear alone — 3.02 times as much.

The bolt that carries more than its share

Six bolts, one hundred kilonewtons, and a worst bolt carrying fifty. The load is shared equally and the torque is not, and the second one is invisible on any drawing where the connection is a point.

Prying action in a tee stub. A tee stub pulled by its web with 100 kN per bolt. The 20 mm flange is in the one-hinge regime, so the prying force at the flange tip is 50.63 kN and the bolt carries 150.63 kN — 1.51 times what was applied. The flange stops prying entirely at 26.97 mm thick, and collapses on its own at 110 kN.

The force the bolt never saw applied

Pull a tee stub with a hundred kilonewtons and its bolt carries a hundred and fifty. The extra comes from the flange bending and pressing its own edge against the thing it is bolted to, and no free body of the connection as a point contains it.

Block shear: the metal between the holes. Three bolts in a 10 mm plate end connection. The shaded block tears out along a shear plane 180 mm long and a tension plane 40 mm long. Shear yields first, and the capacity is the sum of two different strengths on two different planes: 421.7 kN, of which the shear plane carries 70.43%.

The metal between the holes, which comes out as a block

A bolted end connection can fail without a single bolt breaking and without the plate reaching its tensile strength anywhere. A block of metal simply comes out, bounded by two surfaces with two different strengths on them.

The net section, and the path the tear takes. A 200 mm plate with two holes staggered by 50 mm at a gauge of 60 mm. The straight path through one hole leaves 178 mm; the diagonal path through both leaves 166.42 mm after the s²/4g correction adds 10.42 mm back. The shorter of the two decides, at 83.21% of the gross section.

The tear that goes diagonally, and the correction that has no derivation

Stagger the holes so that no straight line crosses more than one and the plate does not get its strength back. The tear runs at an angle instead, and the arithmetic that makes it come out right is a century-old piece of curve-fitting nobody has improved on.

Bearing and tear-out against end distance. A 20 mm bolt in a 10 mm plate. Below 165 mm of end distance the bolt tears a channel out to the end and the capacity is proportional to that distance; above it the plate crushes in front of the bolt and the end distance stops mattering. At 40 mm the capacity is 52.12 kN and the mode is tear-out.

The hole that goes oval, and the one that tears to the edge

A bolt pressing on the side of its hole either crushes the plate in front of it or shoves a channel of metal out to the end. Which one happens is decided entirely by a distance that is usually set by a minimum in a table.

A fillet weld is stronger across than along. Capacity of a 4 mm throat over 100 mm, against the angle between the weld's axis and the load. Loaded along its length it carries 116.83 kN; loaded across it, 143.09 kN. The ratio is 1.22, which is √3/√2 exactly, and it comes out of the failure criterion rather than out of a test.

The weld that is stronger across than along

The same fillet weld, the same size, the same steel, carries twenty-two per cent more when the load runs across it than along it. The factor is exactly the square root of three over the square root of two, and it comes out of the yield criterion rather than out of a test.

Throat stress round a fillet weld group. A c shape weld group carrying 100 kN at 150 mm from its centroid. The peak throat stress is 0.88 kN per mm of throat, at (79.5, -100); the worst point at maximum radius from the centroid carries 0.88. Checking by radius is right here, and points at identical radius differ by a factor of 1.

The corner that is not the worst point

Check the point furthest from the centroid. It is the standard rule for a weld group under an eccentric load, it is exactly right for some shapes, and for others it misses the peak by sixteen per cent — or picks one of four points it cannot tell apart whose stresses differ by two thirds.

A preloaded joint, before and after it slips. Two preloaded bolts at 137 kN each, on one friction face at μ = 0.5. The joint carries 137 kN by friction with the bolts in tension and not in shear at all; past that it slips into bearing and carries 188 kN with the bolts now in shear. Two different mechanisms, one joint.

The joint that carries nothing until it slips

Tighten the bolts hard enough and the plates are clamped together with a force nothing applied. The joint then carries shear by friction, the bolts are in tension and not in shear at all, and the load path has nothing in common with the joint it looks identical to.

An angle bolted through one leg. A 100 × 75 × 10 angle connected through its 100 mm leg with three bolts at 75 mm pitch. The centroid sits 19.77 mm from the connected face over a connection 150 mm long, so U = 1 − 19.77/150 = 0.87 and 13.18% of the net area is not working.

The angle that uses half of itself

Bolt an angle through one leg and the other leg is not fully working. The correction is one over a length — both halves of it are geometry, neither involves a material, and a two-bolt connection throws away a quarter of the section.

Moment against rotation, for three real joints. Three connections on one plot, with the classification boundaries for a beam of EI/L = 14000 drawn as rays through the origin. web cleats is pinned, flush end plate is semi-rigid, extended end plate is semi-rigid. The boundaries are multiples of EI/L, so the same joint is rigid on a short stiff beam and semi-rigid on a long slender one.

Neither pinned nor rigid, which is every real connection

Frame analysis offers two options for a joint and reality supplies a continuum between them. Worse, the boundaries are not properties of the connection at all — the same end plate is rigid on a short stiff beam and semi-rigid on a long slender one.

A joint is springs in series. The five components of an end-plate joint, with each bar the flexibility it contributes. The column flange in bending is 39.62% of the total on its own, and doubling its stiffness raises the joint's by a factor of 1.25 — while doubling the stiffest component buys 1.05. The joint's rotational stiffness is 25227.71 kN·m per radian.

A joint made of springs in series

A connection's stiffness is not a property of the connection. It is the series combination of the flexibilities of everything the force passes through — so the softest component decides, and stiffening any of the others changes almost nothing.

What the joint does to the beam. End moment as a fraction of the fixed-end value wL²/12, against the joint's rotational stiffness, for a beam of EI/L = 14000. At the rigid boundary of 112000 kN·m/rad the joint delivers 80% of it and at the pinned boundary 20%. Everything between the two lines is a redistribution nobody chose and every analysis assumed away.

The redistribution nobody chose

A beam designed as simply supported, on connections that are not pins, has end moments the analysis never predicted and a mid-span moment smaller than it was sized for. Usually that is safe. It is never intentional, and there is one direction in which it is not safe at all.

How a moment crosses a gap. A moment end plate with three bolt rows. The moment is carried as a couple: tension in the rows, compression through bearing at the bottom flange. The plastic distribution reaches 172.8 kN·m and the elastic one 142.29 kN·m, a factor of 1.21 — and the compression at the bottom flange is 540 kN either way, which is the check that gets forgotten because it is not a bolt.

Making a moment cross a gap

A moment is not a thing that can be handed across a joint. It has to be turned into a pair of forces, carried separately, and reassembled — and the whole design is a question of how the tension is shared between bolt rows that are not equally able to take it.

A base plate, and when the bolts start working. A 500 × 400 mm plate carrying 600 kN and 90 kN·m, so the resultant sits 150 mm from the centre against a kern of 83.33 mm. The plate is in partial contact: bearing over 300 mm at a peak of 10 N/mm², with the holding-down bolts carrying 0 kN. The plate lifts at 50 kN·m and crushes at 120 kN·m, and the bolts are not needed until 150 kN·m.

Where the structure meets the ground, and when the bolts start working

Push a base plate off its middle third and it lifts off the foundation. The holding-down bolts then carry exactly nothing, and go on carrying nothing until the plate has crushed the concrete underneath it.

The end bolts do the work and the middle ones very nearly nothing. A lap of 8 bolts at 70 mm pitch transferring 800 kN between two plates, with the force each bolt actually carries drawn above it and the flat line a division by the bolt count would have given drawn behind. The end bolts carry 1.09 of their nominal share and the middle ones 0.94. The reason is not in the bolts: at the leading end the first plate is carrying everything and the second nothing, so the two strain at different rates and the slip between them is largest there. In the middle they strain alike, there is almost no slip, and a bolt with no slip across it transfers almost no force. The mean over the worst is 0.918, and the end bolt has to slip 1.36 mm before the rest catch up.

The bolts that do not share

Every bolted connection in this collection has divided a force by a number of bolts. That is right for a short joint and wrong for a long one, and the reason has nothing to do with the bolts — it is that the plates they join are elastic, and stretch by different amounts at different points along the lap.

Six ways for one dowel to fail, and the capacity is the smallest. Johansen's single-shear mechanisms for a 12 mm dowel through 40 and 40 mm members, each drawn as the shape it is: the dowel straight and the timber crushing, the dowel rotating rigidly, one plastic hinge, then two. The capacity under each is that mechanism's own, and the joint's strength is the smallest — 5.02 kN by mode c, which is the dowel rotates rigidly and both members crush. That is the kinematic theorem of plasticity: every mechanism gives an upper bound and the true collapse is the lowest of them. The crushed timber is shaded, and the circles are plastic hinges in the steel.

The smallest of six failures

Everything else in this collection that fails does so in one way at a time. A dowel through timber does not — the wood can crush while the steel stays straight, or one plastic hinge can form in it, or two — and the capacity is the smallest of the six, which is the kinematic theorem of plasticity applied to a joint rather than to a frame.

The width nobody drew. A gusset plate with a brace bolted to it over 240 mm, and the width the profession has agreed to pretend is carrying the force. Everything else on this site arrives with a cross-section; a gusset does not, because it is a piece of steel with something attached somewhere in the middle of it and there is no geometry that says how much of it is working. The answer is the Whitmore section: assume the force spreads at 30° from the first fastener and take the width it has reached at the last, b_eff = w + 2L·tan30° = 367 mm. That is 4.08 times the width anything is actually attached to, and the rule comes from a 1952 master's thesis. It has since been checked against finite element work and holds to about ten per cent, which is fortunate, because moving the assumed angle by ten degrees moves the answer by 34%. On this plate the check that governs is not the stress the rule was written for: it is the Whitmore section buckles, at 721 kN against 1564.

The width nobody drew

Every other member in this collection arrives with a cross-section. A gusset plate does not — it is a piece of steel with a brace bolted to it somewhere in the middle, and no geometry says how much of it is working. The profession's answer is a thirty-degree spread from a 1952 master's thesis, it invents three quarters of the area being checked, and the check it was written for is not the one that governs.

A base plate, and when the bolts start working. A 500 × 500 mm plate carrying 600 kN and 180 kN·m, so the resultant sits 300 mm from the centre against a kern of 83.33 mm. The plate is in bolts engaged: bearing over 150.88 mm at a peak of 20 N/mm², with the holding-down bolts carrying 154.42 kN. The plate lifts at 50 kN·m and crushes at 126 kN·m, and the bolts are not needed until 150 kN·m.

The failure that is in the concrete

An anchor bolt is a steel component and its capacity is usually decided by something else entirely — a cone of concrete pulled out around it, failing in tension, in a material every other calculation on the project has assumed cannot take tension at all. The exponent in the capacity says so: it is not the square the geometry implies.

The end bolts do the work and the middle ones very nearly nothing. A lap of 10 bolts at 75 mm pitch transferring 800 kN between two plates, with the force each bolt actually carries drawn above it and the flat line a division by the bolt count would have given drawn behind. The end bolts carry 1.16 of their nominal share and the middle ones 0.89. The reason is not in the bolts: at the leading end the first plate is carrying everything and the second nothing, so the two strain at different rates and the slip between them is largest there. In the middle they strain alike, there is almost no slip, and a bolt with no slip across it transfers almost no force. The mean over the worst is 0.861, and the end bolt has to slip 1.16 mm before the rest catch up.

The joint that has to be as good as the member

A splice exists because members come in lengths and structures do not. It has to deliver the same force, at the same stiffness, in the same distribution across the section, through a discontinuity — and each of those three requirements is met by a different feature of the detail, with the third one usually left to look after itself.

The bearing that is drawn as a roller. The horizontal force a sliding bearing delivers, against the vertical load it is carrying, with its coefficient of friction on the same picture. The coefficient is not a constant: PTFE's falls as the contact pressure rises, and the standard fit is μ = 1.2/(10 + σ), so the bearing drawn is at 30.0 N/mm² and μ = 0.030 while the same bearing at a fifth of the load is at 0.075 — 2.5 times as much. The force curve is therefore strongly non-linear: a fifth of the load gives 50% of the force. Two readings follow and only one of them is usually taken. The largest force is at full load, 108 kN, and that is what the pier is designed for. The largest nuisance is at light load, where 54 kN of friction is 39% of the 140 kN of wind the bearing was put there to release the structure from. Cold makes it worse again: below about −5 °C the same bearing delivers 216 kN. A roller symbol on a drawing means this, and it is a pair of load cases rather than one, because friction opposes whichever way the deck happens to be going.

The roller that is not a roller

A sliding bearing is drawn as a roller and detailed as a sheet of PTFE, and it delivers a horizontal force of a few per cent of whatever it is carrying. The coefficient everybody quotes is the one at full design pressure, and PTFE's coefficient rises as the pressure falls — so the bearing is at its freest exactly where nobody checks it.

Four details, and no material anywhere on the plot. Stress range against cycles to failure for four detail categorys — 160, 112, 71, 36 N/mm² at two million cycles. The lines are parallel because they share a slope of three, and the spread between them is a factor of 4.4 in stress and therefore 88 in life. Nothing on this plot depends on the strength of the steel: the same detail in a grade twice as strong lies on the same line. At a stress range of 62 N/mm² the lives are 160: unlimited, 112: 2.1e+7, 71: 3.0e+6, 36: 3.9e+5 cycles. The knee in each line is the constant-amplitude limit, past which the slope becomes five.

The detail decides and the steel does not

A fatigue check contains no material strength anywhere. The same detail in a steel twice as strong lies on exactly the same line, because a fatigue life is decided by the geometry of a weld and by the stress range it sees — and two per cent of the traffic does most of the damage, because life goes as the inverse cube of the range.

Five millimetres short, and a hundred kilonewtons in every member. An X-braced bay 6 m by 4 m in which one diagonal was fabricated 5 mm short, with the force that leaves in every member. Nothing is applied to this frame. The forces are the self-stress state the frame's one redundancy supports, scaled so that the diagonal is pulled back to the length it should have been: tension in both diagonals at 100 kN, compression in the four members round the outside, and the whole set in equilibrium with nothing. That is 25% of the force the diagonal was sized to carry, and it is there for the life of the structure. Take one diagonal out and the frame becomes determinate: the short member then simply puts the joint somewhere else, and the structure is in the wrong place instead of under stress. Redundancy is bought, and this is the price.

Built to the wrong length

A redundant structure's members do not have independent lengths. Choose all but one and geometry decides the last, so a member made a different length has to be pulled or pushed into place — and the force required stays in the structure for as long as the structure does. Nothing has been applied to it, there is no load case and no factor, and the members are carrying real force.

The load path has a kink in it, and the kink is a plate thick. Two 10 mm plates lapped over 60 mm and pulled with 60 kN. The two load paths are offset by the thickness of a plate, so the joint carries a moment nobody applied: P × 10.0 mm / 2. Taken at face value that gives a peak stress 4.00 times the mean. The joint rotates under load and the moment falls to 86 per cent of it, leaving 3.57 times — a saving of 11 per cent and not, on a plate this thick, a rescue. The bolt is bent as well as sheared: 382 N/mm² of bending against 191 of shear.

The joint that is crooked by construction

Lap two plates and fasten them and the two load paths are offset by the thickness of a plate. The joint carries a moment nobody applied, the peak stress is four times the mean, and the rotation that is supposed to straighten it out saves eleven per cent — because the rescue works for thin sheet with a long lap and a bolted structural joint is neither.

The section that is checked is not the section that was chosen. A 457 mm beam coped 50 mm deep over 120 mm to frame into a girder. What is left is a tee with a section modulus of 3.836e+5 mm³ against the whole section's 1.438e+6 — 27 per cent. The moment at the end of the cope is the reaction on a lever arm of 130 mm: 23.4 kNm, giving 61 N/mm² and a flexural utilisation of 0.17. The web now has a free edge along the cope, so its buckling coefficient collapses from 4 to 0.425 — a factor of 9.4 — and the re-entrant corner has a stress concentration of 5.5 on a 10 mm radius.

The section that is checked is not the one chosen

A beam framing into a girder has its top flange cut away so the two can sit at the same level. What is left is a tee with a quarter of the section modulus, a web with a free edge, and a re-entrant corner — and the beam was selected on a table entry that describes none of it.

The moment a joint makes out of geometry. Bending stress in the chord divided by the axial stress already in it, against how far the diagonal's working line misses the node. A truss analysed as pin-jointed is drawn with its members as lines through their own centroids meeting at a point, because that is what makes the joint a pin with nothing but forces in it. A fabricated joint is not obliged to oblige, and the resultant then has a moment about the node — 16 kNm at the 60 mm drawn. It divides between the members meeting there in proportion to their rotational stiffnesses, 4EI/L or 3EI/L, which is the moment-distribution rule applied to an unbalanced moment that came from geometry rather than from load. The chord takes 48 per cent of it and carries 25 per cent of its axial stress again in bending. Ten per cent arrives at 28 mm, which on a chord of any depth is a detailing decision rather than a mistake.

The joint that is not where it was drawn

A truss is drawn as lines through the centroids of its members meeting at points. A fabricated joint is under no obligation to oblige, and when the working lines miss each other the resultant has a moment about the node that has to go somewhere.

Steel has a third direction and it is not as good. Through-thickness strain demand against weld size, on a 30 mm plate, with the ductility the plate can supply in each of its three directions drawn across it. Rolling stretches the plate's inclusions into flat stringers, so a bar cut along the rolling direction, one cut across it and one cut THROUGH it are three different specimens of one steel — 60, 45 and 15 per cent reduction of area, which converts exactly to a true fracture strain of ln(1/(1 − Z)): 0.916, 0.598 and 0.163. A factor of four in the reported percentage is 5.6 in the strain the material can take. The demand goes as the deposited area over the square of the thickness, so doubling the weld size quadruples it: the 12 mm throat drawn asks for 5.4 per cent, which an ordinary plate supplies and a plate with a bad inclusion cluster does not.

The direction a plate was never tested in

A rolled plate is not one material. Rolling stretches its inclusions into flat stringers lying in the plane, so a bar cut along it, one cut across it and one cut through it are three different specimens of one steel — and every mill certificate reports the first.

A weld is a force, and it is applied where the weld is. The bow a welded girder leaves the shop with, against how far its welds sit from the section's centroid. A weld cannot contract while the plate holds it, so it yields in tension and what is left when everything is cold is a locked-in force at about the yield stress: 312 kN for the 1.2 kJ/mm of heat drawn, over a shrinkage zone of 439 mm². Applied 210 mm off the centroid that is a moment, and a moment applied along a member is a curvature: the 12 m girder comes out bowed 12.5 mm, which is L/962 against a fabrication tolerance of L/1000. It also comes out 1.2 mm shorter. Welding symmetrically about the centroid puts the resultant on the neutral axis and the bow becomes 0.00 mm — the same heat, the same force, and no moment at all.

The shape that came out of the shop

A weld cools by seven hundred degrees while the plate holds it, so it yields in tension and stays that way. What is left is a locked-in force of three hundred kilonewtons applied where the weld is, and if that is not on the centroid the member leaves the shop bent.

Throat stress round a fillet weld group. A l shape weld group carrying 150 kN at 200 mm from its centroid. The peak throat stress is 2.17 kN per mm of throat, at (139.53, 100); the worst point at maximum radius from the centroid carries 1.99. Checking by radius is wrong here by 9.17%, and points at identical radius differ by a factor of 1.

The radius rule, and where it fails

A weld group under an eccentric load is checked at the point furthest from its centroid, on the reasoning that the stress from the twist grows with the radius. That reasoning ignores the direction the two stresses point in, and for one common shape it misses the peak by nine per cent.

Prying against flange thickness. The ratio of bolt force to applied force, for a tee stub carrying 140 kN per bolt, as the flange thickness varies. Prying disappears above 31.91 mm and the flange has become a mechanism below 22.75 mm, where the shaded region begins and the bolt has stopped being the thing that decides.

The thickness that decides who fails

A bolt in a tee stub carries more than the load applied to it, because the flange bends and levers against its own edge. How much more, and whether the bolt or the flange is the thing that gives way, are both decided by one dimension — and the two regimes it separates fail in completely different ways.

A preloaded joint, before and after it slips. Four preloaded bolts at 172 kN each, on one friction face at μ = 0.5. The joint carries 344 kN by friction with the bolts in tension and not in shear at all; past that it slips into bearing and carries 362 kN with the bolts now in shear. Two different mechanisms, one joint.

The hole made bigger so the steel would fit

A preloaded joint carries load by friction, and the friction is reduced by the shape of the hole the bolt passes through — not by how much steel the hole removes, but by a coefficient in a table. An oversize hole costs fifteen per cent of the resistance; a long slot costs thirty-seven. Both are provided because the steel would not otherwise line up.

Block shear: the metal between the holes. Three bolts in a 9 mm plate end connection. The shaded block tears out along a shear plane 180 mm long and a tension plane 55 mm long. Shear ruptures first, and the capacity is the sum of two different strengths on two different planes: 524.79 kN, of which the shear plane carries 63.03%.

The end that is only a plate

Cut one flange off a beam's end and what is left is a tee. Cut both and what is left is a plate with holes in it — no flanges, no section modulus worth the name, and none of the checks the beam was selected by. Three plate checks replace them, and the one that governs depends on dimensions that appear in no section table.

The part of a base plate that is delivering anything. A plan of the plate: the 260 × 260 column in the middle, and the shaded region it can reach — its own outline grown by 43 mm, which is t√(f_y/3f_jd) for a 20 mm plate on grout at 20 N/mm². That is 78176 mm² of a 200000 mm² plate, or 39 per cent of it. The corners are outside it and are carrying nothing: a plate cantilevers from the column's perimeter and runs out of bending capacity at c, so making it larger in plan beyond that changes nothing at all, and making it thicker changes everything.

The plate that is only as big as it is thick

A base plate's design is presented as a bearing calculation: an area, a bearing strength, and a check that the pressure fits. The area in that calculation is the plate, and the plate cannot deliver it — a 20 mm plate on a 500 square reaches 43 mm past the column and the corners carry nothing at all.

Force and capacity round a weld group, which do not vary together. Utilisation round the c shape group under 100 kN at 150 mm, walked from one end of the weld to the other, with the force scaled onto the same axis for comparison. The capacity is 1460 N/mm where the force runs along the weld and 1789 where it runs across it — √1.5 more — so the utilisation is not simply the force in different units. The worst point is at 47 degrees to the weld, where the capacity is 1612 N/mm, and the group carries 182 kN against the 165 the along-the-weld value would allow.

The weld that is stronger where it is pulled

A fillet weld pulled across its axis is √1.5 stronger than the same weld pulled along it. On a group under an eccentric load the direction of the pull varies from point to point, so the capacity does too — and the gain that follows is worth twenty per cent at one eccentricity and nothing at all at another.

Where the span moment and the support moment cross. Span moment and support moment against the joint's stiffness, for a 6 m beam under 30 kN/m. They move in opposite directions because they add to a constant — the simple-span 135 kN·m is fixed by statics and the joint only decides how it is split. They cross at 68 kN·m, where the joint is delivering 75 per cent of the fixed-end moment, and neither the crossing nor the fraction depends on the beam, the span or the load: it is the point where f·wL²/12 equals wL²/8 − f·wL²/12, which is f = 0.75 for every beam there has ever been.

The joint that was chosen

A joint's stiffness decides how a beam's moment divides between its span and its supports, and the two add to a constant. So there is a stiffness at which they are equal, the beam is sized by the smaller of two numbers rather than the larger of one, and the design moment is half what a simple connection leaves behind.

The whole line works, and the axis is not a choice. A weld group 200 mm deep carrying 15 kNm about an axis in its own plane, together with 100 kN of vertical shear. The bending force per unit length runs linearly from 1125 N/mm at one extreme to the same the other way at the other, through zero at the group's own centroid — and the centroid is where the neutral axis is because a weld carries compression across its throat as readily as tension. The 250 N/mm of shear runs along the weld and is uniform over the whole 400 mm, so the two components are perpendicular to one another and are combined on the throat rather than added as vectors in the plane.

The eccentricity at right angles to the drawing

A bracket's load stands off the plane of its welds as well as being offset within it, and the second eccentricity produces a completely different object — bending about an axis through the group rather than torsion about a point in it. The weld line has no compression zone to argue about, so its neutral axis is its own centroid, and the whole length works.

Three fasteners, three completely different clocks. What each of three shear fasteners carries against how far the joint has moved. A 400 kN fillet weld is linear to 0.4 mm and then gone — it is stiff and it is not ductile. A 380 kN bolt in a hole 2 mm larger than itself carries nothing until the hole closes and then rises over several millimetres of hole elongation. A 250 kN preloaded bolt is at its slip resistance in under a tenth of a millimetre and holds it until it slips. Two of these in one joint are at the same displacement, so the one that gets there first carries the load — and the weld gets there 23 times sooner than the bearing bolt does.

Two fasteners that never arrive together

Every steel code forbids adding a weld's capacity to a bolt's in one shear joint, and states it as a rule rather than deriving it. It is derivable. Two fasteners in parallel are at the same displacement rather than the same force, and a weld has ruptured at four tenths of a millimetre while a bolt in a standard hole has not yet touched the side of it.

Two ways for the same plate to fold. An end plate 200 mm wide with a bolt 45 mm from the web face and 55 mm from the edge, and the two families of yield line it can collapse along. The circle closes round the bolt and is 283 mm of hinge — a circle round the bolt. The straight pattern runs out to the plate's free edges and is 249 mm — hinges to the plate edges. The plate folds along whichever is cheaper, which here is the fan, and the 200 mm that comes out is the length of the equivalent tee stub — a dimension that is nowhere on the plate and is 100 per cent of its width.

How much of the plate is bending

A tee stub is an object nobody builds, and the whole component method rests on replacing a real end plate with one. The length of the substitute is not a dimension of the plate — it is the length of the cheapest fold the plate can collapse along, and two families of fold compete for it on a criterion with no strength in it at all.

Nine-tenths of a tightening torque stretches nothing. Where the torque applied to the nut of an M20 grade 10.9 bolt goes, against the coefficient of friction in its thread and under its nut, taken as equal. The bottom band is the thread's lead — the only part of the work that stretches the bolt — the middle band is friction in the thread and the top band is friction under the nut. At μ = 0.14 the lead takes 11% of the torque, the thread 39% and the nut face 50%. At μ = 0.06 the lead's share is 22% and at 0.24 it is 6%, so a coefficient nobody measured decides how much of a specified torque arrives in the bolt as preload.

The torque that goes into the thread

A preload specified as a torque is a preload specified through two coefficients of friction that nobody measures. Nine-tenths of the torque on a bolt is spent turning against its own thread and the face of its nut, so a change in the grease moves the clamping force by half — and the one method that escapes it does so by yielding the bolt on purpose.

The compression is under the flange, not at the edge of the plate. A 500 × 400 mm base plate, 20 mm thick, under a 260 mm column carrying 300 kN and 120 kN·m, with holding-down bolts 60 mm from the tension edge. A plate this thick can deliver bearing only 43 mm past the compressed flange, so the compression sits under that flange, 124 mm from the column's centre, and the lever arm to the bolts is 314 mm: the bolts carry 264 kN and the flange zone 564 kN. The dashed block is the rigid-plate answer, 54 mm deep at the plate's far edge with its resultant 223 mm out, which needs only 128 kN in the bolts. Both satisfy equilibrium; only one is a plate that can carry the pressure where it is drawn.

The compression that stays under the flange

Put a moment on a base plate and a pressure-block calculation pushes the compression out to the plate's edge, where the lever arm to the holding-down bolts is longest. A plate that is not rigid cannot put it there. The compression stays within a few tens of millimetres of the compressed flange, the lever arm shrinks, and the bolts carry twice what the pressure block said.

Each repair reaches the checks its plate touches, and no others. The four checks on a 457 mm beam coped 50 mm deep over 200 mm, carrying a reaction of 300 kN through three bolts, as utilisations, for the end as coped and with three repairs: an 8 mm doubler on the web, a 100 × 10 mm plate along the free edge, and both. As coped the utilisations are flexure 0.46, shear 0.41, tear-out 0.57 and local buckling 0.46. The doubler thickens the web, which is most of what a coped tee is, and lowers all four; the edge plate gives the tee back a flange and lowers only flexure and buckling, leaving shear and tear-out exactly where they were. What governs: as coped, tear-out at 0.57; doubler, tear-out at 0.30; edge stiffener, tear-out at 0.57; both, tear-out at 0.30.

The repair that fixes the wrong check

A coped beam end that fails its checks is usually repaired by welding a plate along the edge the cope left, because the cope removed a flange and the plate puts one back. On ordinary proportions that repair restores the check that was not failing. The check that governs is carried by the web, and only a plate on the web reaches it.

The joint yields first and the span takes the rest. The end and span moments of a beam of span 9 m and flexural rigidity 61,700 kN·m², with a plastic moment of 522 kN·m, on joints of rotational stiffness 41,133 kN·m/rad, 6.00 EI/L, and resistance 261 kN·m, as a uniform load rises to collapse. While elastic the joints carry 0.75 of the fixed-end moment. The joints reach their resistance first, at 51.6 kN/m, and from there every further increment of load goes to the span, which reaches 522 kN·m at 77.3 kN/m. The collapse load is 8(Mp + Mj)/L² = 77.3 kN/m, between the 51.6 at which the beam would collapse on pins and the 103.1 it would reach on rigid full-strength ends, and it contains the joint's strength and not its stiffness.

The joint that has to keep turning

A beam on partial-strength joints collapses at 8(Mp + Mj)/L² however stiff the joints are. Stiffness decides only which yields first, and a joint that yields first has to go on rotating at full moment until the span catches up. A weak joint on a stiff connection has the most turning to do — more than a rigid full-strength one.

Made from one side, the throat misses the load and its root takes the difference. Two plates 20 mm thick joined by a partial-penetration butt weld with 10 mm of throat, pulled apart by a force on their mid-thickness, with the stress across the throat drawn beside each joint as a multiple of the mean. Above, welded from one side: the throat runs from the top face down to 10 mm, so the force passes 5.0 mm below its centroid. The moment adds tension at the root and removes it at the face: the root carries 4.00 times the mean stress and the face −2.00, which is compression. The unfused 10 mm below the root is a notch, and it is on the tension side. Below, the same 10 mm of throat split between the two faces: the force passes through its centroid and every part of it carries the mean stress.

The throat that misses the load

A partial-penetration butt weld's throat faces the load squarely, so a millimetre of it carries more than a fillet's, and in every grade what limits it is a cap on normal stress rather than the directional criterion. Made from one side, the throat sits off the plates' line of action. At half penetration it keeps a quarter of that capacity, and the stress the eccentricity adds lands on the root, which is a crack.

A plate welded to a loaded beam carries only the load that comes after it. The bending stress across the depth of a 457 mm beam coped 200 mm long and 50 mm deep, carrying a reaction of 300 kN, at the end of the cope, repaired with a doubler 8 mm thick on the web. With 60 per cent of the reaction already on the beam when the plate is welded, the original steel carries that share on its coped section and the rest on the repaired one. At the web's free edge it reaches 137 N/mm², against 164 as coped and 97 if the plate had been there from the start. The plate carries only the later load, 39 N/mm² at its outer edge. The repair has removed 40 per cent of the stress it would have removed on an unloaded beam.

The plate that arrives after the load

A repair plate welded to a beam already in use carries only the load that arrives after its weld has cooled. The elastic checks remember that order — a doubler welded under 60 per cent of the reaction removes 40 per cent of the stress it would remove from an unloaded beam — while tear-out, a plastic mechanism, gets the whole of the repair. Propping the beam is what hands the plate the load already there.

One bracket, three neutral axes, three sets of bolt forces. A bracket 300.0 mm deep with three rows of two bolts at 75.0 mm pitch, carrying 15.0 kN·m about an axis in the plane of the bolts. Taking the axis at the group's centroid puts the outer rows at 50.0 kN of tension and 50.0 of compression, with the middle row idle. Taking it at the plate's compression edge puts every row in tension — 7.1, 14.3, 21.4 kN from the bottom up — with the top row at 21.4. Solving for it instead, with the plate bearing over 200.0 mm of width and the bolts as areas, puts it 40.2 mm above the edge and the top row at 24.6 kN. All three make the applied moment exactly. The top row differs between them by a factor of 2.33.

The bolt group has no neutral axis

A bolt group carrying a moment about an axis in its own plane has some bolts in tension and something in compression somewhere else. Where that somewhere else is decides the answer, nothing in the group decides it, and the two defensible choices give the worst bolt 50 kilonewtons and 21.

Two collapses for the same plate, and only one of them fits. The same three bolt rows at 90 mm pitch, folding two ways. On the left each row folds on its own pattern — 249 mm of hinge line round each bolt — and the patterns overlap, because 249 mm of fold cannot fit in a 90 mm pitch. On the right the plate does what it can actually do: the hinges run straight from one row to the next, and the whole group folds on 429 mm rather than 746. The arithmetic follows the drawing — 377 kN for the group against 657 for the rows added up.

The rows have to share one fold

Each bolt row of an end plate is checked on its own, and the answers are added up. Two rows ninety millimetres apart cannot each fold the plate on a pattern two hundred and fifty millimetres long, because there is only one plate — so the group folds on one shorter pattern, and the sum was never available.

The bolt force is the larger of two lines. What an M20 bolt in a 25 mm tee flange actually carries, against the tension applied to the flange. Preloaded to 171 kN it starts there and climbs at Φ = 0.185 — the bolt's own stiffness over the bolt's plus the clamped plates', 857 against 3781 kN/mm — so 18 per cent of every kilonewton applied reaches it and the rest is unloading the contact. At 138 kN the contact runs out and the line joins the one an ordinary bolt has followed from the start, climbing at 2.12. The two lines meet, so the strength is the same either way; what differs is the slope, by a factor of 11.5. The flange's own mechanism is at 172 kN, comfortably past the crossing.

The bolt that was already stretched

Prying is a lever that needs the flange to lift before it can act, and a preloaded bolt does not let it. The bolt carries a fifth of every kilonewton applied until the plates part, and everything after that is the ordinary calculation — which is why preload changes the fatigue answer by a factor of a thousand and the strength answer by nothing at all.

Capacity against load direction, layout by layout. The same capacities as a function of direction on straight axes, for a load through (150, 150) mm. Three rows of two is weakest at 138°, 135.8 kN. Two rows of three is weakest at 312°, 135.8 kN. A ring of six, r = 70.4 mm is weakest at 132°, 150.3 kN. The curves cross: no layout is strongest in every direction, and the one to choose is the one whose lowest point is highest.

The bracket pushed from the wrong side

A six-bolt bracket checked for a load straight down carries 198.5 kN. Push the same load through the same point at 138 degrees and it carries 135.8 — the direction changes the torque as well as the shear, and the worst direction is one no drawing shows. The capacity of a group whose load can turn is a closed curve, the bolt that governs it changes as the load turns, and what the curve rewards is not a larger polar moment but a smaller distance to the furthest bolt.

The two methods, direction by direction. Capacity against the direction of the load for three rows of two bolts of 100 kN each, loaded through (150, 150) mm. The elastic method bottoms out at 135.8 kN at 138°; the instantaneous centre at 168.3 kN at 136°, 23.9 per cent higher. Both spike to 600.0 kN where the load aims at the centroid and every bolt carries an equal share. The gap between the curves is not constant: it is widest where the elastic distribution is most uneven, which is the same place the group is weakest.

The better method flatters the worse layout

The instantaneous centre method finds capacity the elastic method cannot see, and how much it finds depends on the layout it is applied to. On a six-bolt rectangle under a load of unknown direction it is worth 24 per cent; on a ring of six with a smaller polar moment it is worth 14. The two methods agree on which layout to choose and disagree by a factor of five about the margin — and the reason is that a layout the elastic method already likes is one with nothing left to redistribute.

What each missing bolt costs. The weakest-direction capacity of six bolts at 75 by 75 mm, loaded through a point (150, 150) mm from the centroid, with the whole group and with each bolt in turn left out. The full group carries 135.8 kN. Leaving out bolt 3 leaves 90.2 kN, a loss of 34 per cent; leaving out bolt 2 leaves 131.1 kN, a loss of 4. One sixth of the bolts is not one sixth of the capacity, and which sixth it is matters by a factor of 10. The dashed line is the capacity a group that lost a proportional share would have, 113.2 kN.

The bolt that was never fitted

A six-bolt bracket found with five bolts in it has lost a sixth of its fasteners and between four and thirty-four per cent of its capacity, depending which one is missing. The share is the smallest of the three things that changed: the centroid moves away from the gap, which lengthens the load's own lever arm, and the polar moment falls by more than the count does. The bolt whose absence costs most is not the bolt that governed the check.

Four ways to put six bolts in one plate. Six bolts inside a 150 × 150 mm field of bolt centres, no two closer than 60 mm, loaded through a point (200, 0) mm from the field's centre. The two-column layout carries 193.5 kN complete and 138.8 kN with its worst bolt missing. The ring carries 167.2 kN complete and 117.8 kN with its worst bolt missing. The strongest found carries 234.3 kN complete and 149.7 kN with its worst bolt missing. The most robust found carries 231.6 kN complete and 174.7 kN with its worst bolt missing. The layout found by maximising the complete capacity and the layout found by maximising the worst omission are different layouts, 1 per cent apart when complete and 17 per cent apart with a bolt missing, and both beat the ring — the most evenly spread of the four — on both counts. The dashed line runs from each group's centroid to the load: 200 mm, 200 mm, 180 mm, 188 mm. The ringed bolt is the one each group can least afford to lose.

The strongest layout leans on one bolt

Search a plate for the six bolt positions that carry most and the answer carries 234 kN — and loses 36 per cent of it if one particular bolt is missing. Move that one bolt fifty millimetres, into the corner the optimum had just left, and the group carries 232 kN and loses 25 per cent whichever bolt goes. Robustness here costs one per cent of strength, and a search for strength alone will never find it.

A tubular K joint with a 12.6 mm gap. A 168.3 × 8.0 mm chord with two 114.3 × 6.3 mm braces at 45°, their toes 12.6 mm apart on the chord's crown. The braces' working lines, carried down through the chord, meet 3.0 mm below the chord's axis — an eccentricity of 0.02 chord diameters, inside the band of −93 to +42 mm in which the joint rules let its moment be neglected. Nobody chose that number. It follows from the gap, the brace diameter and the angle, and the gap was chosen so both toes could be welded. The working lines would meet on the chord's axis at a gap of 6.7 mm, which is a joint no rule permits.

The joint whose lines may not meet

In a welded tubular truss the noding eccentricity is not a fabrication error. It is fixed by the brace diameter, the brace angle and the gap between the toes, and the gap is chosen for the welder. For a third of ordinary proportions the one gap at which the working lines would meet lies in a band no fabrication rule permits — so the concurrent joint the truss was analysed with is the one joint that cannot be built.

Two flanges, one bolt, one prying force. An end plate 18 mm thick with its bolt 45 mm from the beam web, bolted to a column flange 14 mm thick with the same bolt 30 mm from the column web; their tips are 35 mm beyond the bolt and bear on each other, so the prying force there is one force acting on both. Checked as two separate tee stubs on rigid bases, the end plate carries 109.3 kN per bolt (mode 2, web hinge and bolt) and the column flange 104.4 (mode 1, both hinges), so the component method gives the joint 104.4. The pair carries 92.3 kN, 12 per cent less, with the prying force at 44.7 kN and hinges in the end plate at its web and the column flange at the bolt line — the end plate's web hinge working with the column flange's bolt-line hinge, a mechanism that exists in neither tee stub on its own.

The hinge that forms in the other flange

An end plate bolted to a column flange is two tee stubs sharing one bolt, and the force at their tips is one force pressing on both. Checked separately, as the component method checks them, the end plate carries 109 kN a bolt and the column flange 104. Together they carry 92 — by a mechanism with one hinge in each flange that neither tee stub has on its own.

The thin plate straightens onto the load line. The centre lines of a 10 mm plate lapped on a 20 mm plate, 100 mm wide, over 60 mm, carrying 60 kN with the grips 1200 mm from the overlap, over 480 mm either side of the overlap, with every vertical distance drawn 14 times the lengthwise scale; dotted, where the centres would be if the joint could not rotate. The load pulls along the straight line between the grips, each of which holds its plate on its own centre, and the moment where a plate enters the overlap is the load times the gap between that line and the plate's centre. The thin arm, flexible under tension, has swung toward the line: its gap is 0.49 of the rigid one, e/2. The overlap has turned with it, and the thick arm, too stiff to follow, is left 1.34 of e/2 from the line. Peak stresses: 193 N/mm² in the thin plate and 121 in the thick one, against 330 and 98 if the joint could not turn.

The thicker plate takes the bend

A lap joint's eccentricity puts a moment into both plates, and the rule is that each takes half of the load times the offset. That is true only while the joint cannot turn. Let it turn, and a thin plate lapped on a thick one straightens under its own tension and hands its share across: the thick plate ends up bending a third more than the rule says, the thin one half as much, and in the limit the thick plate would take the whole of it.

The bolt that governs is worst at only one thing. The plate of a bracket of six M20 grade 8.8 bolts in three rows of two at 75 mm, loaded 150 mm to the side of the group and 150 mm in front of the column face, with the load at 60° from straight down, drawn at the group's capacity on the elliptical interaction, 227 kN. Each bolt's arrow is its shear in the plane of the plate and its disc grows with its tension, which comes from the load's distance in front of the column: bottom left 9 kN and 67 kN; middle left 33 kN and 76 kN; top left 74 kN and 84 kN; bottom right 40 kN and 35 kN; middle right 51 kN and 43 kN; top right 84 kN and 51 kN. The most shear is on the top right bolt and the most tension on the top left; the one that reaches its interaction first is the top left, and the next, the top right, is at 0.97 of its own.

The bracket with no worst bolt

A bracket that stands out from its column is pulled off the column by the same load that twists it in its plane, so every bolt carries shear and tension at once. Straight down, one corner bolt is worst at both and the check is that bolt's. Tilt the load and the most sheared bolt and the most pulled bolt come apart; the one that fails is whichever of them its interaction reaches first, and at the angle where they swap the group has two worst bolts and no single one.

A butt throat is strongest a little off square. The resultant a millimetre of throat can carry in S355 against the direction of the load, from straight across the weld (0°) to straight along it (90°). The fillet's falls throughout, from 385 to 314 N/mm². The butt's rises from 441 to 478 at 22.7°, because its cap limits only the normal stress and a little shear costs it nothing, and then falls to 314. So the butt's advantage over the fillet is 1.15 straight across, 1.29 at 22.7°, and none straight along.

The shear that helps a butt weld

A partial-penetration butt throat pulled straight across its weld is capped at 0.9fu, which in S355 makes it 15 per cent stronger than a fillet throat. Add a little shear along the weld and the butt throat gets stronger, not weaker, because the cap limits only the normal stress — until the shear is 42 per cent of the pull, where it is 29 per cent stronger than the fillet and carries its largest resultant, 478 N/mm² against 441 straight across. Along a moment connection's web weld the mix of pull and shear sweeps through that peak, and in the direction that is all shear a single-sided throat is as good as two.

The modes that tilt, and the ones that do not. Johansen's mechanisms for a 12 mm bolt with washers in single shear through 40 and 40 mm of timber of density 350 kg/m³, each with the rope term the fastener's axial resistance of 6.64 kN adds to it. Modes a and b, where the fastener only translates, gain nothing; the modes in which it tilts gain a quarter of its axial resistance, capped at a quarter of their own Johansen value. The joint's capacity rises from 5.02 kN (mode c) to 6.28 kN (mode c), 25 per cent.

The pull that Johansen left out

Johansen's mechanisms treat a timber fastener as a beam in a bed of crushing wood, bent and pushed sideways and nothing else. A real fastener that tilts across the joint is also pulled along its own axis, and if a washer or a thread resists the pull, it clamps the two members together and adds to what the joint can carry. The addition is a quarter of the axial resistance, it goes only to the modes in which the fastener tilts, and it is capped by fastener type — nothing for a dowel, a quarter for a bolt, all of it for a screw — which is how a screw keeps gaining strength past the thickness at which Johansen's capacity stops.

What the frame notices. An 8 m by 4 m portal whose columns stand on bases of every rotational stiffness, in units of the column's EI/L on a logarithmic scale: solid, the portal's sway under a load at the knee as a multiple of the fixed-based portal's; dashed, the columns' effective length factor in sway (fixed bases 1.13, pinned 2.26). Bolts sleeved 300 mm, 5.3 EI/L: 1.45 times the fixed portal's drift, an effective length factor of 1.30 and 75 per cent of its buckling load; as detailed, 9.1 EI/L: 1.28 times the fixed portal's drift, an effective length factor of 1.23 and 83 per cent of its buckling load; rigid by EN 1993-1-8, 30.0 EI/L: 1.09 times the fixed portal's drift, an effective length factor of 1.16 and 94 per cent of its buckling load.

The fixed base the bolts decide

A column base drawn as fixed is a spring, and the component method says what it is made of: the grout squeezed under the flange, the plate bending under the bolt row, and the anchor bolts stretching over their free length. For a 500 mm plate on two M24 bolts the bolts are three fifths of its flexibility, so the base comes out at nine times the column's EI/L — under a third of what EN 1993-1-8 calls rigid — and no thickness of plate can lift it above fifteen. Leave the bolts free in sleeves for erection tolerance and it falls to five. The frame on it drifts 28 per cent more than a fixed-based one and buckles at 83 per cent of the load.

Where each check bites. The c shape group with a 5.0 mm throat drawn to scale, loaded 1 mm from its vertical run. Offset from each weld, the use of each point: solid for the static directional check, dashed for fatigue at 2 × 10⁶ cycles, each scaled to its own worst point, which is marked. The static check's worst point is where the force runs most nearly along a weld; the fatigue check's is where it runs most nearly across one. Here the two checks are governed at different points, and a fatigue check made only at the static peak allows a load range 2.25 times the group's.

Strongest across, and first to crack across

A fillet weld pulled across its length is √1.5 stronger than one pulled along it, and every static check of a weld group uses that. In fatigue the same two directions are rated the other way round: the part of the force across the weld is checked against a detail category of 36 and the part along it against 80. The point of a group that governs the static check need not govern the fatigue one, and checking fatigue there can allow more than twice the load range the weld will take.

Lean a screw and its bending stops mattering. The peak load on an 8 mm fully threaded screw (yield moment 20 N·m, tensile capacity 20 kN) through two 100 mm softwood members of density 350 kg/m³, against the angle it is driven at to the joint: the joint, its two resistances added slip by slip (solid); the thread's alone, resolved along the joint with its friction (dashed); the bending and embedment's alone (dotted); and the square screw with the rope effect, 5.9 kN (thin). At 45 degrees the joint carries 13.4 kN, 2.3 times the square screw, of which the bending gives 1.8; at 30, 19.1. The bending is the larger share only steeper than 85.7 degrees, within 4.3 of square. Withdrawal is taken to peak at 1.5 mm of axial movement and soften after it; bending follows Foschi's curve from EN 1995-1-1's slip modulus — shapes, not measurements.

The screw that is pulled instead of bent

A screw square to a timber joint resists slip by bending, and its thread is engaged only when it has tilted far enough to be pulled. Lean the same screw to 45 degrees and the slip pulls it from the first millimetre. An 8 mm screw through two 100 mm members goes from 5.9 kN to 13.4, reached after 2.2 mm of slip instead of more than twelve, and the bending that Johansen's model is about becomes an eighth of the joint. The price is a joint that holds one way better than the other.

The area rule's even stress, and the stress the cut finds. The tensile stress through the depth of the two covers where they cross the gap of a 20 mm main plate 200 mm wide, spliced with a 15 mm cover on one face and an 8 mm cover on the other, carrying 900 kN; the main plate's centre line, on which the load acts, is at zero. Shared by area every fibre would work at 196 N/mm² (dashed). The free body puts the covers' resultant on the load line instead, and the stress varies across them: 107 to 179 N/mm² in the 15 mm cover and 275 to 313 in the 8 mm one — the thin cover's outer face at 1.60 times the area rule's stress.

The thinner cover carries more

A plate spliced with a cover on each face is the standard cure for a lap joint's eccentricity, and the covers are usually sized as if they shared the load in proportion to their areas. A free body cut across the splice says otherwise. With nothing but the two covers crossing the cut, their forces must balance about the line the load acts on, so they share by lever arm and not by area — and the thinner cover, which sits nearer that line, carries more than half the load on less than half the steel.

Preload makes the base rigid, until the bed lets go. Moment against rotation at the base of a 500 × 400 × 20 mm base plate under a 260 mm column, with two M24 holding-down bolts in each of two rows 60 mm from its ends: with no preload (dashed), 58,609 kN·m per radian, 9.8 times the column's EI/L; with bonded anchors whose free length is 136 mm (dotted), 13.9 EI/L; preloaded to 150 kN a bolt (solid), 45.6 EI/L until the bed under the plate lets go at its tension edge at about 57 kN·m, then softening toward the unpreloaded base. Faint: the slope of EN 1993-1-8's rigid boundary, 30 EI/L.

The base that is rigid until the bed lets go

A column base drawn as fixed is a spring about a tenth as stiff as the rule for "rigid" requires, and most of its softness is the holding-down bolts stretching. Shortening the bolts helps less than it seems: even 60 mm of free length leaves the base below two thirds of the rigid boundary. Preloading them works completely — the base becomes half as stiff again as the boundary asks — but only while the grout under the plate stays in compression. The preload is spent at a definite moment, the same moment the column's own weight would buy for free, and the shorter the bolt the faster creep of the grout takes the preload away.

One ratio decides how much of a row works. The share of n single screws' peaks a row reaches, for rows of 10, 20 and 30 8 mm screws at 45° to the joint, 56 mm apart along the grain, in two 100 mm softwood members of modulus 11,500 N/mm² with 40, 80 and 160 mm of member depth each, and threads peaking at 0.5, 1, 1.5 and 2.5 mm, against one ratio: the slip difference the members' stretch puts between the end screw and the middle one at the row's peak, PL(1/EA₁ + 1/EA₂)/8, over the width of a single screw's curve above nine tenths of its peak. Thirty-six rows fall on one curve: every row with the ratio below 0.3 reaches at least 1.00 of its screws' sum; at a ratio of 1 they reach about 0.96; and the most stretched, at 3.5, 0.72. The colour is the thread's peak slip; a brittler thread has a narrower plateau and lands further right for the same row.

Twenty screws that peak together

A leaning screw reaches its peak at two millimetres of slip and then lets go, so a row of twenty along the grain looks like the long bolted joint again — the end screws past their peak and falling while the middle ones have barely started. Follow the row slip by slip and it is not: in a member of ordinary depth twenty leaning screws carry 98 per cent of twenty times one, against the 74 per cent the effective-number rule allows. What decides it is one ratio — the slip the timber's stretch spreads along the row against the width of a screw's peak — and the rule is right only for a brittle thread in a thin member.

A bigger top column attracts more moment, and only the joint stops it. The top storey of the edge column of a braced six-storey frame — 4 m storeys, a 254 UC 89 below the splice and a 203 UC 60 above — carrying a 9 m beam at every floor on partial-strength joints of 261 kN·m, with each of seven columns that might be chosen for it: the moment its floor's edge joint delivers at the design load of 60 kN/m (dark) and at the beams' collapse load (light), against what the column can carry at its top end, its plastic moment reduced for the axial force (line). 203×203 UC 46: 148 and 195 against 167; 203×203 UC 60: 171 and 225 against 230; 203×203 UC 71: 189 and 247 against 283; 203×203 UC 86: 205 and 261 against 347; 254×254 UC 73: 218 and 261 against 352; 254×254 UC 89: 232 and 261 against 435; 254×254 UC 107: 243 and 261 against 527. A stiffer column attracts more of the joint's moment until the joint's 261 kN·m caps it; the lightest column that carries what it attracts at collapse is the 203 × 203 UC 60.

The column on the other side of the joint

A partial-strength joint is sold as a fuse: it caps the moment a beam can put into its support at the joint's own resistance. At an interior column that is true. At the edge of a frame the column is not a support that stays still; it is a spring in series with the joint, so the joint delivers less than its resistance in service and almost exactly what a rigid joint would. The column then carries three times the moment the simple-construction rule gave it, and at the top storey, where it stands alone and is lightest, it is weaker than the joint it was meant to be protected by.

A crack at the cope's corner, and the hole its tip needs. A 457 × 190 beam end coped 150 mm long and 80 mm deep, reacting 350 kN of which 70 per cent comes and goes with traffic, to scale. A fatigue crack has grown 30 mm down the web from the corner where the cope's two cuts meet, the most stressed point of the coped section. At that depth the live load's range of stress intensity at its tip is 15.6 MPa√m, and a hole drilled with the tip inside it stops the crack only if its radius is at least (ΔK/10.5√fy)², 6.2 mm: a 12 mm hole. The crack and the hole together leave 341 mm of the 377 mm coped section below them.

The hole at the tip of the crack

The commonest reason to repair a coped beam end is a fatigue crack at the corner of the cope, and the commonest repair needs no plate at all: a hole drilled so that the crack's tip is inside it, turning a crack into a smooth notch that the traffic can no longer drive. The hole has to be big enough, and how big is set by the crack — its radius grows in step with the crack's length. A 30 mm crack at a stringer's cope needs a 12 mm hole, a 60 mm crack a 24 mm one. The repair stops working at about 100 mm, where the hole outgrows a site drill and the section left beside it runs out of capacity at nearly the same depth. Most of the crack's life is spent far shorter than that, which makes the repair a matter of how early the crack is found.

The base comes back to a different joint. Moment against rotation at the base of a 500 × 400 × 20 mm base plate with two M24 holding-down bolts in each of two rows, preloaded to 150 kN a bolt, through four cycles to ±170 kN·m. It is stiff until the bed lets go at 57 kN·m, softer past it, and near 170 kN·m the bolts on the tension side yield and stretch for good. Coming back through zero the base is not the base it was: its bolts have kept 83 per cent of their preload, and it lets go at 46.0 kN·m instead of 56.6. After the first full cycle the loops lie on top of one another.

The base that lets go and closes again

A column base whose holding-down bolts are preloaded is rigid until the moment on it lifts the plate off its bed, and then softer. Under a storm the moment goes one way and then the other, many times, and the question is whether the preload survives. It does, entirely, as long as no bolt yields — and on an ordinary base the bolts do not yield until the moment is three times what first lifts the plate. Past that the yielded bolts lose part of their preload once, and the loss stops within a cycle or two: the base settles rather than ratchets. What decides how much is lost is how close to its yield the bolt was tightened, so that past a point a larger preload leaves less after the storm.

A plate pulled off an unstiffened flange. Looking down the column at a 250 × 20 mm plate on a 300 × 19 mm flange with a 11 mm web and 27 mm root radii, the plate pulled away from the flange. Shaded on the plate's welded edge: the force per millimetre of weld while everything is elastic, 47% of it entering over the web and its root radii and peaking at 2.67 times the uniform value at the toe of the radius. Dotted: the uniform force P/bp a rigid flange would give. Dashed: the same force spread over the effective width EN 1993-1-8 gives the joint, 191 mm — a plastic width, 2.8 times the 69 mm the elastic share fits at the web's average.

A quarter of the weld takes half the pull

A beam flange welded straight on to an unstiffened column flange is checked with an effective width of 191 mm out of 250. While the joint is elastic the plate's force does not use anything like that width: 47 per cent of it goes through the 65 mm over the web, and the flange has already yielded at 30 per cent of the force the rule allows. The rule's width is a plastic width, and the full-strength weld it insists on is what lets the joint get there.

The room left between two planes of braces. The surface of a 168.3 mm chord unrolled flat — along the chord across, round it up — with the footprints where 114.3 mm braces at 45 degrees are welded to it: two from a K joint in one plane (solid), two from a K joint in a plane 90 degrees round the chord (dashed), both nodes at the same section, each with a 12.6 mm gap between its own toes. The narrowest gap between a brace of one plane and a brace of the other is 6.5 mm, against the 12.6 mm two welds need: too little to weld. Each footprint spans 85.6 degrees of the chord's circumference.

Two planes of braces and one circumference

A tower leg or a triangular girder's chord receives K joints from two planes at once, and each can be checked as a planar joint: its gap, its eccentricity, its band. What the planar checks cannot see is that the two planes' braces are welded to the same tube. A 114 mm brace takes up 86 degrees of a 168 mm chord's circumference whatever its gap, so a square tower's two planes leave 6.5 mm between them where the welds need 12.6, and a triangular girder's braces land on each other. And two eccentricities at the edge of their band give the chord √2 or √3 times the moment the band was written for.

A doubler is put to work through its welds, and most of the work is at its ends. A 457 mm beam coped 200 mm long and 50 mm deep, carrying 300 kN, with a 8 mm doubler 393 mm deep on its web, the plate welded along its two long edges and running 200 mm past the end of the cope. The shaded bands along the two welds are the shear flow each passes into the plate, averaged over 50 mm: the top weld passes up to 1,056 N/mm and the bottom 821, both largest where the plate ends. At the cut through the cope's end the plate gives 92 per cent of the relief a plate joined at every point would give: the free edge is at 94 N/mm², against 152 as coped and 88 fully joined.

How far a doubler has to run

A doubler on a coped web is joined to the beam only along its welds, and the force reaches it through those welds from wherever it is welded. Stopped at the end of the cope, a plate welded along its two long edges gives about two fifths of the relief a fully joined plate would give at the very section it was put there for. Run on past the cope by four tenths of its own depth, it gives nine tenths. Welded all round, it is fully joined at any length.

Retightened after every storm, the bolts stretch in every storm. The permanent stretch in the worse bolt row of a 500 × 400 × 20 mm base plate with two M24 holding-down bolts in each of two rows, accumulated over ten storms of four cycles to ±170 kN·m, with the nuts retightened after every storm to 200 kN, to the 150 kN they were first given, to the 124 kN the first storm left, or left alone. Left alone, the bolts stretch 0.12 mm in the first storm and not at all after it. Retightened to 150 kN they add 0.12 mm in every storm, 1.25 mm after ten; to 200 kN, 0.43 mm a storm. Retightened only to what the first storm left, they stretch no more than if they had been left alone.

The nut turned after the storm

A preloaded column base that has been through a storm has lost some of its preload, and the obvious repair is to retighten its bolts. Left alone, the bolts stretched once in the first storm and never again; the base settled. Retightened, they are given back the preload the storm could not live with, and the next storm takes it away again by stretching them again. Retightening after every storm turns a base that settles into one that ratchets, a tenth of a millimetre at a time, and the count of storms it has in it is set by the bolt's elongation.

Below a limit the row settles; above it, it ratchets. The end screw's slip at the top of each cycle, against the number of cycles, for 20 leaning screws 56 mm apart with 40 mm of member depth per row loaded again and again from new to four levels, each screw, reloaded, reaching the slip it had been to with 85% of the load it had there. At 0.94 it settles at 2.50 mm after 3 cycles; at 0.96 it settles at 2.83 mm after 7 cycles; at 0.97 of the peak the end slip grows every cycle until the row cannot reach the load, at cycle 21; at 0.99 of the peak the end slip grows every cycle until the row cannot reach the load, at cycle 8. The row's first peak is 263 kN; every level drawn is below it.

The row that remembers its overload

A row of twenty leaning screws reaches 98% of twenty screws' peak, once. Loaded again, a screw that has been past its peak comes back along a softer path and reaches the slip it had been to with less load than it carried there. So a row loaded again and again neither simply evens out nor simply ratchets down: below 0.965 of its first peak it settles after a few cycles with the middle screws catching up, and above it the end screws are pushed back onto their curve every cycle, lose a little more each time, and the row fails at a load it carried the first time. One large overload costs it less than many smaller ones near the peak.

The series sum is exact for matched flanges and errs by their mismatch. The pair's stiffness over the series of its two flanges as tee stubs on rigid bases, each with half the bolt's length, against the end plate's lever arm from web to bolt, for end plates 14, 18, 25 mm thick on a column flange 14 mm thick with its bolt 30 mm from its web, tips 35 mm beyond the bolt. Where the end plate matches the column flange — 14 mm thick at 30 mm — the ratio is exactly one: two identical flanges back to back meet on their plane of symmetry, which is the rigid base. A 14 mm end plate is 0.95 of the series with its bolt at 45 mm and 0.85 at 65; an 18 mm end plate is 0.97 of the series with its bolt at 45 mm and 0.86 at 65; a 25 mm end plate is 1.00 of the series with its bolt at 45 mm and 0.93 at 65.

The flanges that lean on each other

A bolted end-plate joint's stiffness is built from springs in series: the end plate as a tee stub on a rigid base, the column flange as another, the bolt shared between them. The rigid base is not a fiction. It is exactly the plane of symmetry between two identical flanges bolted back to back, so for matched flanges the series sum is exact. A real end plate and column flange are not matched, and each tip bears on a tip that moves differently from its own. Solved as a pair, the error is the mismatch: 3% for an 18 mm end plate on a 14 mm column flange with similar lever arms, 12–15% when the end plate's bolt is twice as far from its web.

The single side's strongest direction is not the double side's. The resultant a millimetre of throat can carry in S355 against the direction of the load: a double-sided butt throat, a fillet throat, and a 20 mm plate's single-sided throat at penetrations of 0.5 and 0.7, counted plastically. The double-sided butt is strongest at 22.7°, 478 N/mm². The single side at 0.5 rises from 183 straight across to 314 straight along and is strongest along the weld; at 0.7 it rises from 291 to 357 at 40° and falls to 314, and from 38° to 88° it carries more than the fillet.

The root that has to stretch for it

A partial-penetration weld made from one side carries its pull off the plates' line, and counted elastically it keeps a quarter of a double-sided weld at half penetration. Let the throat yield and it keeps 0.41 — but the same 0.41 at every direction up to the one where the double-sided weld is strongest, so that weld's peak advantage is never won back. What the yielding does instead is move the single side's own strongest direction out to 40° or beyond, where a deep single-sided throat outcarries a fillet. Every per cent of it is paid for with strain at the root, which is the tip of an unfused land.

The preload a storm can live with, raised by a spring under the nut. The largest preload the bolts of a 500 × 400 × 20 mm base plate with two M24 holding-down bolts in each of two rows can be given and come out of a storm without stretching, against the stiffness of a stack of disc springs under each nut, for storms to ±165, ±170, ±175 kN·m; dashed, the same for the bare base; dotted, the bolt's yield of 226 kN. To ±170 kN·m the bare base keeps at most 128 kN; with a stack of 500 kN/mm, 150; 100 kN/mm, 187; 20 kN/mm, 214; 5 kN/mm, 223.

The spring under the nut

Retightening a column base after every storm makes its bolts ratchet, because a storm can only live with 128 kN of preload and the spanner keeps putting back 150. A stack of disc springs under each nut changes what the storm can live with. Soft enough, the bolts never reach their yield: the compression side keeps its preload, the bed's resultant moves out to the plate's edge, and the moment rides on lever arm rather than on bolt force. A stack as stiff as the bolt itself keeps 150 kN through every storm. Much softer, and the storm the bolts no longer feel lands on the grout.

The pair holds its clamp longer than the stub it is checked by. The tension a bolt at which the clamp lets go, as a share of the 110 kN preload, against the end plate's lever arm from web to bolt, for an end plate 18 mm thick on a column flange 14 mm thick at 30 mm: the pair (solid), the end plate's stub (dashed) and the column flange's (dotted). With the end plate's bolt at 30 mm the pair and the stubs nearly agree. At 45 mm the pair lets go at 88.2 kN and the end plate's stub already at 81.1, the pair holding 9 per cent more; at 60 mm, 82.0 against 71.2, 15 per cent more.

The clamp the pair holds longer

A preloaded bolt clamps an end plate to a column flange, and the joint stays closed until the tension relieves the clamp. The joint diagram says that happens at the preload over one minus the bolt's share — 122 kN for a 110 kN preload — but prying adds to the tension at the bolt line and the clamp lets go at 88. A component model checks each flange as a stub on a rigid base and lets the joint go when its weaker stub does, at 81 kN. The real pair, its tips leaning on a column flange that gives way, pries less than the end plate alone would, and holds its clamp nine per cent longer — fifteen when its lever arms are two to one.

Across the gap the splice plates bend as one section. The top half of the splice of a 612 mm deep I-beam with 229 by 19.6 mm flanges, spliced at 700 kN·m by a 15 mm outer cover on each flange, two 8 mm inner covers beside the web under it and two 8 mm web plates 480 mm deep, to scale, cut at the gap where only the plates cross (the beam's own flange and web dashed beyond), and the stress through it. Bent as one section, the outer cover works at 206 N/mm² at its centre and the inner covers at 186, in proportion to their distances from the neutral axis; the hand design's area rule gives both 193; the plate splice's lever rule gives the outer 123 and the inner 350.

The splice that bends as one section

A plate spliced with two unequal covers shares its load by lever arm about the line the load is held on, and the thinner cover carries more. A beam's flange splice looks like the same joint, and the rule that worked for the plate puts the thin inner covers at the edge of yield. They are working at half that. A beam's halves are not held on any line; they turn, and every splice plate across the gap turns with them, so the plates bend as one section and share the beam's moment by their distances from its neutral axis. The outer cover works hardest, the inner covers less, and the web plates less than the hand design hands them.

The worst direction is the long axis of an ellipse. For a bracket of six M20 grade 8.8 bolts in three rows of two at 75 mm, loaded 150 mm to the side of the group and 150 mm in front of the column face: the demand on the governing bolt, top right, per kilonewton of load, drawn as a radius in the direction the load acts — straight down at the bottom — under the elliptical interaction (solid), which in each quadrant of directions is an arc of one ellipse, and under the straight line (dashed), which is not. The ellipse's longest radius, at 16.0°, is its eigenvector: 0.0058 of the bolt's interaction used for every kilonewton, a capacity of 172.5 kN, found without trying a single direction.

The worst direction is an eigenvector

A bracket whose load can come from any direction in the plane of its bolts has a capacity that is a closed curve, and once the load also pulls the bracket off its column the curve becomes a surface over direction and distance. Finding its lowest point looks like a search. Under the elliptical interaction of shear and tension it is not: inside each quarter-turn of directions every bolt's demand squared is a quadratic form in the load's direction, so the worst direction is that form's eigenvector, and the bracket's least capacity is a 2 × 2 eigenvalue per bolt. Under the straight line EN 1993-1-8 prints it is a search, because a straight line has no curvature to make an ellipse of — and the hand check that sets the worst shear anywhere against the worst tension anywhere is a tenth too low in the plane and a fifth too low once the bracket is pulled.

Two neutral axes in one cut. Stress against height through a girder with a 300 by 30.0 mm top flange, a 229 by 19.6 mm bottom flange and a 573 by 11.9 mm web, spliced at 700 kN·m. The girder's own neutral axis is 374 mm above its underside, and its flanges work at 133 and 201 N/mm². Its splice, each flange's covers sized to that flange's force at 250 N/mm², has its own centroid at 326 mm — 48 mm lower — and across the gap the plates bend about it: the top outer cover at 244 N/mm², the bottom outer at 269, the web plates from 179 at their top to 212 at their foot. Shaded: the covers' heights (darker) and the web plates'.

The splice that finds its own axis

Splice a girder whose top flange is heavier than its bottom one and the splice plates, sized flange by flange, have a centroid 48 mm below the girder's. It looks as if the splice must then carry an axial force the girder does not, or be proportioned to keep the two axes together. It carries none: a cut through the gap carries what the girder carries, and the girder carries no force. Held at both ends, the mismatch makes less than a kilonewton. What the offset does instead is move the web's own force into plates that were not sized for it.

Between the two counts, and the root's toughness says where. What a 20 mm S355 plate welded from one side to 0.5 of its thickness keeps of a double-sided butt throat, pulled straight across, against the toughness of the metal at its root: assessed as a crack on the strip-yield line (solid), by the toughness alone (dashed), and by the elastic and plastic counts (dotted, 0.25 and 0.41). Below 30 MPa√m the root tears before the elastic count's load; at 46 MPa√m the toughness alone would allow the whole plastic count, but the assessment gives 0.34, and it takes 66 MPa√m to reach 95 per cent of it. At 30, 50 and 100 MPa√m the root keeps 0.25, 0.35 and 0.41.

The land that is already a crack

A partial-penetration weld made from one side leaves the rest of the joint unfused, and pulled across, that unfused land is an edge crack whose tip is the root. Counted as a crack it keeps neither the elastic quarter of a double-sided weld nor the plastic 0.41, but a share between them that the root's toughness chooses — and the toughness of a crack front is the toughness of its length, which for a weld is the whole weld. A long weld in a cold structure can tear below the elastic count, and the same joint drawn twice as large tears sooner, which no count of stresses can see.

The more of the load that comes back, the less of it the row can carry for ever. The largest load 20 screws leaning at 45° in a row 56 mm apart carries for ever, as a share of its forward peak, against the share of it that comes back the other way each cycle (0 the same load repeated, 1 fully reversed), for each screw carrying none, half and all of its thread's first loss into the other way. Carrying 0 per cent: 0.96 repeated, 0.96 half reversed, 0.82 fully reversed; carrying 50 per cent: 0.96 repeated, 0.94 half reversed, 0.79 fully reversed; carrying 100 per cent: 0.96 repeated, 0.92 half reversed, 0.76 fully reversed.

The row that is pushed as often as it is pulled

A row of leaning screws in a shear wall is loaded one way by the wind and then the other, and a screw that leans is pulled along its axis one way and pushed the other. Pulled, its axial force clamps the joint and friction helps it; pushed, it prises the joint open and the friction goes. So the row has a weaker side, and under a reversing load it settles exactly as it settles under a repeated one — the reversal does not start the ratchet again — but at a ceiling the pushed side sets, 0.79 of the pulled peak against 0.97. And it settles with a gap in the middle that every reversal crosses carrying nothing.

An old joint passes the bolts that have lost their preload. The chance that an M20 grade 10.9 bolt holds the inspection torque of 647 N·m without its nut turning, against the tension actually in it as a fraction of the minimum preload, for a joint new and 1 year old, 5 years old and 20 years old. New, a bolt at half the minimum preload passes 0% of the time and one at the minimum 83%; 20 years old, the bolt at half passes 80% of the time and one at a quarter 9%.

The wrench that reads the rust

The obvious check on a preloaded joint that has been in service for years is a wrench on the nut, and it measures the wrong thing. The nut holds against the bolt's tension times a friction bracket, and twenty years of rust raise the bracket until a bolt with half its preload passes four times in five. The washer that could have said more remembers only the day it was crushed.

A yielded joint is a hinge for gravity and a spring for sway. The elastic critical factor of a storey of two 8 m bays on 4 m pin-based columns, each column carrying 300 kN from above, under 20 kN/m, its joints of initial stiffness 3.0 EI/L, after the gravity load, against the joints' resistance. Reading every joint at its limit as a hinge gives 0.00 at 10 kN·m, where all four have yielded, 3.71 at 60 kN·m and 8.27 once none has. Letting a joint unload at its full stiffness where sway unloads it gives 3.71, 6.48 and 8.27.

A hinge one way and a spring the other

A frame whose partial-strength joints have all yielded under gravity looks like a set of beams on hinges standing on pinned columns, and on that reading it has no sway stiffness at all. It stands anyway, and the arithmetic of the hinges is the thing that is wrong. A joint at its hogging limit will not take any more hogging, but sway takes hogging off one end of every beam, and that end answers at its full stiffness. Half the joints the gravity load has spent are still there for the wind. They last only until they run out of range, which is why a critical factor taken from them can be right and tell a designer almost nothing.

The group's load against the plates' travel, fitted and misaligned. The force on eight bolts in holes misaligned within ±2.0 mm, against the same bolts fitted, as the plates travel. The misaligned group needs 3.9 mm to reach half its nominal strength where the fitted one needs 0.9, and it peaks at 95% of nominal against 98%, at 8.6 mm, as its first bolt fails.

The bolts that arrive one at a time

A bearing bolt sits in a hole two millimetres bigger than itself, so a group of them is not in contact until the plates have moved, and each bolt reaches its hole at a different moment. Every calculation then shares the load equally. That is nearly right at failure and wrong on the way there, and what repairs it is a property nobody writes on the drawing: how far a bolt can travel before it breaks.

Where a spliced girder turns, held by friction and in clearance holes. The moment across a girder splice against the rotation of its two halves at the gap. Preloaded bolts hold the plates by friction and the splice turns 1.6 mrad at 700 kN·m; snug bolts centred in 2 mm of clearance turn 11.7 mrad by the time the plates have taken it, and one drawn fit-up 12.5. All three reach the plates' plastic moment of 1,164 kN·m.

The splice that waits for its covers

Put a girder splice's bolts in ordinary clearance holes and every plate has two millimetres to cross before it carries anything. The plates do not cross it together. The ones furthest from the axis arrive first, so at the design moment the web plates are nearly idle, the bottom cover is a third over its stress, and the plate that yields first is chosen by where the erector's drift pin happened to leave the bolts.

The splice's moment against its rotation, through four reversals. The girder splice of 2 mm clearance holes driven four times to ±700 kN·m, its rotation across the cut in milliradians, with snug bolts in a drawn fit-up and with the same bolts preloaded to 171.5 kN. Snug, each reversal crosses 13.3 mrad of slack at almost no moment and the peaks reach ±11.8; preloaded, 0.09 mrad and ±1.6.

The splice that forgets how it was bolted

A girder splice bolted through clearance holes picks up its plates in an order set by how the bolts happened to sit, and under a moment one way a bad fit-up can yield a cover at half the moment a centred one reaches. Reverse the moment and the order is lost: the first excursion pushes every plate across its hole, the fit-up is forgotten, and from then on every splice of 2 mm holes behaves alike. It does not ratchet. It crosses 13.6 milliradians of slack at every reversal, and above about 726 kN·m its covers yield both ways every cycle — 150 below the same splice with fitted bolts.

The loop a proof load traces, with the stuck part taken away. One cycle of shear between ±17 kN on the bolt's patch, the slide less what a patch stuck everywhere would give, in micrometres: at the full 172 kN preload the loop is 0.169 µm wide at zero load; at half, 0.401. The slides the two share, 4.46 µm at the peak, are left out.

The joint that hides its clamp in its loop

A friction joint loaded well below slip looks like a piece of solid steel, and the stiffness it shows a passing lorry has no clamp in it at all: a bolt at half its preload starts out exactly as stiff as one at full. The clamp is not in the stiffness but in the loop. Cycle the joint through a fifth of its slip load and the edge of each clamped patch slips a little, both ways, and the loop it traces is 0.17 µm wide at full preload and 0.40 at half. A proof load can read a joint's clamp, but only by its hysteresis, and only with a gauge good to a tenth of a micrometre.

A splice's loop, and the one loose bolt it can show. The loop a gauge across a lap splice of six bolts at a 70 mm pitch in two 140 by 15 mm plates, each bolt clamped by 172 kN with a friction of 0.50 draws under a cycle of ±120 kN, drawn as the reading less the tight row's straight line, so that only what is not elastic shows: all six tight, the end bolt at half its clamp, and the third bolt at half. Its width at no load is 0.710 µm tight, 1.381 with the end bolt loose and 0.712 with the third.

The loop that sees only the end bolts

A friction joint's hysteresis loop below slip carries its clamp in it, so a gauge across a splice reading a small loop could in principle tell a loose bolt from a tight one. In a row of six it can tell only some of them. The plates between the bolts share the load so that the two end bolts carry 38 kN of a 120 kN cycle and the middle two 7, and a loop's width goes as the square of a bolt's force: the end bolts draw the loop, the middle ones barely touch it. One end bolt at half its clamp nearly doubles the loop; the third bolt at half changes it by a third of a per cent. Forty rows of scattered clamps read their end bolts' mean with a correlation of 0.99 and their weakest bolt's with 0.51.

All essays